PART NAMES AND FUNCTIONS
4
●
Remote controller
Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
PCH-P2/2.5/3/4/5/6GAH
PCA-P2/2.5/3/4/5/6GA
●
Operation buttons
This switches between continuous
operation and the timer operation.
TIMER button
This sets the fan speed.
AIR SPEED button
Press this button to switch the
cooler electronic dry (dehumidify)
automatic and heater modes.
OPERATION SWITCH button
This sets of switches the current
time. start time and stop time.
TIME SETTING button
(This button does not operate in
this model)
This switches the horizontal fan
motion ON and OFF.
LOUVER button
This switches between the opera-
tion and stop modes each time it is
pressed. The lamp on this button
lights during operation.
ON/OFF button
Only press this button to perform
an inspection check or test opera-
tion Do not use it for normal opera-
tion.
CHECK-TEST RUN button
This resets the filter service indica-
tion display.
FILTER button
●
Indoor (Main) Unit
Air outlet
Intake grille
Air intake
Left/right guide vanes
Change the direction of airflow
from the horizontal blower.
Long-life fillter
Removes dust and foreigh matter from air coming in
through the grille (Recommended cleaning interval :
Approx, every 2,500 operating hours)
Up/down guide vanes
Change the direction of airflow from the
vartical blower.
This set the ventilation fan speed.
VENTILATION button
This adjust the current time, start
time and stop time.
TIMER ADJUSTMENT
button
This sets the room temperature
The temperature setting can be
performed in 1°C units
Setting range
Cooler
19°C to 30°C
Heater
17°C to 28°C
TEMP. ADJUSTMENT button
This adjusts the vertical angle of
the ventilation.
AIR DIRECTION button
This manual is suitable for devices
- Mitsubishi PCA-P2.5GA
- Mitsubishi PCA-P2.5GA1
- Mitsubishi PCA-P2GA
- Mitsubishi PCA-P2GA1
- Mitsubishi PCA-P3GA
- Mitsubishi PCA-P3GA1
- Mitsubishi PCA-P4GA
- Mitsubishi PCA-P4GA1
- Mitsubishi PCA-P5GA
- Mitsubishi PCA-P5GA1
- Mitsubishi PCA-P6GA
- Mitsubishi PCA-P6GA1
- Mitsubishi PCH-P2.5GAH
- Mitsubishi PCH-P2.5GAH1
- Mitsubishi PCH-P2GAH
- Mitsubishi PCH-P2GAH1
- Mitsubishi PCH-P3GAH
- Mitsubishi PCH-P3GAH1
- Mitsubishi PCH-P4GAH
- Mitsubishi PCH-P4GAH1
- Mitsubishi PCH-P5GAH
- Mitsubishi PCH-P5GAH1
- Mitsubishi PCH-P6GAH
- Mitsubishi PCH-P6GAH1
SPLIT-TYPE,HEAT PUMP AIR CONDITIONERS 1999
SPLIT-TYPE,AIR CONDITIONERS
No. OC182
REVISED EDITION-B
TECHNICAL & SERVICE MANUAL
Series PCH/PCA Ceiling Suspended R407C • Refer to the OCT03
REVISED EDITION-C as
Indoor unit [Service Ref.] 2001 regarding control
[Model names] PCH-P2GAH1 relation.PCH-P2GAH1, PCH-
1999, 2001 1999 PCH-P2.5GAH1 P2.5GAH1, PCH-P3GAH1,
PCH-P2GAH PCH-P3GAH1 PCH-P4GAH1, PCH-
PCH-P2GAH PCH-P2.5GAH PCH-P4GAH1 P5GAH1, PCH-P6GAH1,
PCH-P2.5GAH PCH-P3GAH PCH-P5GAH1 PCA-P2GA1, PCA-P2.5GA1,
PCH-P3GAH PCH-P4GAH PCH-P6GAH1 PCA-P3GA1, PCA-P4GA1,
PCH-P4GAH PCH-P5GAH 2001 PCA-P5GA1, and PCA-
PCH-P5GAH PCH-P6GAH PCA-P2GA1 P6GA1.Are added in
PCH-P6GAH 2000 PCA-P2.5GA1 REVISED EDITION-B.
PCA-P2GA PCA-P3GA1
2000, 2001 PCA-P2.5GA PCA-P4GA1 • Please void OC182
PCA-P3GA PCA-P5GA1 REVISED EDITION-A.
PCA-P2GA PCA-P4GA PCA-P6GA1
PCA-P2.5GA PCA-P5GA • This manual does not cover
PCA-P3GA PCA-P6GA outdoor units.When serving
PCA-P4GA them, please refer to the
PCA-P5GA service manual No.OC180
PCA-P6GA REVISED EDITION-A and
this manual in a set.
INDOOR UNIT CONTENTS
CHECK FILTER CENTRALLY CONTROLLED 1Hr. 1. TECHNICAL CHANGES ··································2
CHECK MODE ˚C 2. COMBINATION OF INDOOR AND OUTDOOR UNITS···2
TEST RUN ON OFF 3. SAFETY PRECAUTION ···································3
4. PART NAMES AND FUNCTIONS····················5
CHECK CLOCK 5. SPECIFICATIONS ············································9
6. DATA·······························································21
STAND BY ˚C NOT AVAILABLE FILTER 7. OUTLINES AND DIMENSIONS ·····················62
DEFROST CHECK MODE 8. WIRING DIAGRAM············································66
ERROR CODE TEST RUN 9. REFRIGERANT SYSTEM DIAGRAM ··················67
FUNCTION 10. TROUBLESHOOTING ···································69
11. DISASSEMBLY PROCEDURE·······················71
TEMP. ON/OFF 12. PARTS LIST ···················································76
13. OPTIONAL PARTS ········································94
PCH-P2,2.5,3,4,5,6GAH PCH-P2,2.5,3,4,5,6GAH1
PCA-P2,2.5,3,4,5,6GA PCA-P2,2.5,3,4,5,6GA1
REMOTE CONTROLLER
1 TECHNICAL CHANGES
PCH-P2GAH PCH-P2GAH1 PCA-P2GA PCA-P2GA1
PCH-P2.5GAH PCH-P2.5GAH1 PCA-P2.5GA PCA-P2.5GA1
PCH-P3GAH PCH-P3GAH1 PCA-P3GA PCA-P3GA1
PCH-P4GAH PCH-P4GAH1 PCA-P4GA PCA-P4GA1
PCH-P5GAH PCH-P5GAH1 PCA-P5GA PCA-P5GA1
PCH-P6GAH PCH-P6GAH1 PCA-P6GA PCA-P6GA1
q Outdoor units which are connected to PCH-P·GAH, PCH-P·GAH1, PCA-P·GA and PCA-P·GA1 have been added.
q The parts No. of REMOTE CONTROLLER has changed. (The following parts numbers are interchangeable.)
CHECK FILTER CENTRALLY CONTROLLED 1Hr.
CHECK MODE ˚C
TEST RUN ON OFF
CHECK CLOCK
STAND BY ˚C NOT AVAILABLE FILTER
DEFROST ERROR CODE CHECK MODE
TEST RUN
FUNCTION
TEMP. ON/OFF
[T7W E00 713] [T7W E06 713]
2 COMBINATION OF INDOOR AND OUTDOOR UNITS
Outdoor unit (OC180 REVISED EDITION-A)
Indoor unit Heat pump type Cooling only type
PUH-P · VGA / YGA PU-P · VGA / YGA
2VGA 2YGA 2.5VGA 2.5YGA 3VGA 3YGA 4YGA 5YGA 6YGA 2VGA 2.5VGA 3VGA 3YGA 4YGA 5YGA 6YGA
Heat pump with PCH-P2GAH ——————————————
electric heater
PCH-P2.5GAH — — ————————————
PCH-P3GAH — — — — ——————————
PCH-P4GAH — — — — — — —————————
PCH-P5GAH — — — — — — — ————————
PCH-P6GAH — — — — — — — — ———————
PCA-P2GA ——————— ——————
Heat pump without PCA-P2.5GA — — —————— —————
electric heater PCA-P3GA — — — — ————— ———
or PCA-P4GA — — — — — — —————— ——
Cooling only PCA-P5GA — — — — — — — —————— —
PCA-P6GA — — — — — — — — ——————
Outdoor unit (OC261)
Heat pump type Cooling only type
Indoor unit PUH-P · VGAA · UK / YGAA · UK PU-P · VGAA · UK / YGAA · UK
2VGAA 2YGAA 2.5VGAA 2.5YGAA 3VGAA 3YGAA 4VGAA 4YGAA 5YGAA 6YGAA 2VGAA 2YGAA 2.5VGAA 2.5YGAA 3VGAA 3YGAA 4VGAA 4YGAA 5YGAA 6YGAA
. UK . UK . UK . UK . UK . UK . UK . UK . UK . UK . UK . UK . UK . UK . UK . UK . UK . UK . UK . UK
Heat pump PCH-P2GAH1 ——————————————————
with PCH-P2.5GAH1 — — ————————————————
electric heater PCH-P3GAH1 — — — — ——————————————
PCH-P4GAH1 — — — — — — ————————————
PCH-P5GAH1 — — — — — — — — ———————————
PCH-P6GAH1 — — — — — — — — — ——————————
Heat pump PCA-P2GA1 ———————— ————————
without PCA-P2.5GA1
—— ———————— ——————
electric heater PCA-P3GA1 ———— ———————— ————
or
Cooling only PCA-P4GA1 —————— ———————— ——
PCA-P5GA1 ———————— ————————— —
PCA-P6GA1 — — — — — — — — — —————————
2
3 SAFETY PRECAUTION
Cautions for using with the outdoor unit which adopts R407C refrigerant.
· Do not use the existing refrigerant piping.
-The old refrigerant and refrigerant oil in the existing piping contains a large amount of chlorine which may cause the refriger-
ant oil of the new unit to deteriorate.
· Do not use copper pipes which are broken, deformed or discolour .
In addition, be sure that the inner surfaces of the pipes are clean, free of hazardous sulphur and oxides, or have no dust /
dirt, shaving particles, oils, moisture or any other contamination.
-If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the refrigerant oil will
result.
· Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before
brazing. (Store elbows and other joints in a plastic bag.)
-If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
· Use ester oil, ether oil or alkyl benzene (small amount) as the refrigerant oil to coat flares and flange connections.
-The refrigerant oil will degrade if it is mixed with a large amount of mineral oil.
Use liquid refrigerant to fill the system.
-If gas refrigerant is used to fill the system, the composition of the refrigerant in the cylinder will change and performance
may drop.
· Do not use a refrigerant other than R407C.
-If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the refrigerant oil to deteriorate.
· Use a vacuum pump with a reverse flow check valve.
-The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerant oil to deteriorate.
· Do not use the following tools that are used with conventional refrigerant.
(Gauge manifold , charge hose, gas leak detector, reverse flow check valve, refrigerant charge base, vacuum gauge,
refrigerant recovery equipment)
-If the conventional refrigerant and refrigerant oil are mixed in the R407C, the refrigerant may deteriorated.
-If water is mixed in the R407C, the refrigerant oil may deteriorate.
-Since R407C does not contain any chlorine, gas leak detectors for conventional refrigerant will not react to it.
· Do not use a charging cylinder.
-Using a charging cylinder may cause the refrigerant to deteriorate.
· Be especially careful when managing the tools.
-if dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deteriorate.
· Do not use the drier which is sold in the field.
-The drier for R407C refrigerant is per-attached to outdoor unit refrigerant circuit.
-Some drier in the field are not in conformity with R407C refrigerant .
3
[1] Service tools
Use the below service tools as exclusive tools for R407C refrigerant.
No. Tool name Specifications
1 Gauge manifold ·Only for R407C.
·Use the existing fitting SPECIFICATIONS. (UNF7/16)
2 Charge hose ·Use high-tension side pressure of 3.43MPa·G or over.
·Only for R407C.
3 Electronic scale ·Use pressure performance of 5.10MPa·G or over.
4 Gas leak detector
5 Adapter for reverse flow check. ·Use the detector for R407C.
6 Refrigerant charge base. ·Attach on vacuum pump.
7 Refrigerant cylinder.
·For R407C ·Top of cylinder (Brown)
8 Refrigerant recovery equipment. ·Cylinder with syphon
[2] Notice on repair service
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of
liquid refrigerant.
[3] Refrigerant recharging
(1) Refrigerant recharging process
1Direct charging from the cylinder.
·R407C cylinder are available on the market has a syphon pipe.
·Leave the syphon pipe cylinder standing and recharge it.
(By liquid refrigerant)
Unit
Gravimeter
(2) Recharge in refrigerant leakage case
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release the refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of
liquid refrigerant.
4
4 PART NAMES AND FUNCTIONS
q Indoor (Main) Unit
Left/right guide vanes
Change the direction of airflow
from the horizontal blower.
Air outlet
Long-life fillter
Removes dust and foreigh matter from air coming in
through the grille (Recommended cleaning interval :
Approx, every 2,500 operating hours)
Up/down guide vanes Air intake
Change the direction of airflow from the Intake grille
vartical blower.
q Remote controller
Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
PCH-P2/2.5/3/4/5/6GAH
PCA-P2/2.5/3/4/5/6GA
q Operation buttons
TIME SETTING button AIR SPEED button
This sets of switches the current This sets the fan speed.
time. start time and stop time.
TIMER button ON/OFF button
This switches between continuous This switches between the opera-
operation and the timer operation. tion and stop modes each time it is
pressed. The lamp on this button
OPERATION SWITCH button lights during operation.
Press this button to switch the AIR DIRECTION button
cooler electronic dry (dehumidify)
automatic and heater modes. This adjusts the vertical angle of
the ventilation.
TEMP. ADJUSTMENT button
FILTER button
This sets the room temperature
The temperature setting can be This resets the filter service indica-
performed in 1°C units tion display.
Setting range LOUVER button VENTILATION button CHECK-TEST RUN button
Cooler 19°C to 30°C
Heater 17°C to 28°C This switches the horizontal fan This set the ventilation fan speed. Only press this button to perform
motion ON and OFF. an inspection check or test opera-
TIMER ADJUSTMENT tion Do not use it for normal opera-
button (This button does not operate in tion.
this model)
This adjust the current time, start
time and stop time.
5
q Display
CENTRALLY CLOCK display In this display example on the bot-
CONTROLLED display tom left, a condition where all dis-
The current time , start time and stop play lamps light is shown for expla-
This indicates when the unit is con- time can be displayed in ten second nation purposes although this differs
trolled by optional features such as intervals by pressing the time switch from actual operation.
central control type remote controller. button. The start time or stop time is
always displayed during the timer AIR DIRECTION display
operation.
TIMER display This displays the air direction.
This indicates when the continuous FAN SPEED display
operation and time operation modes
are set. The selected fan speed is displayed.
It also display the time for the timer
operation at the same time as when ROOM TEMPERATURE display
it is set.
The temperature of the suction air is
OPERATION MODE display displayed during operation. The dis-
play range is 8° to 39°C. The display
This indicates the operation mode. flashes 8°C when the actual temper-
ature is less than 8° and flashes
39°C when the actual temperature is
greater than 39°C.
STANDBY display Operation lamp
This indicates when the standby This lamp lights during operation,
mode is set from the time the sleep goes off when the unit stops and
operation starts until the heating air flashes when a malfunction occurs.
is discharged.
CHECK MODE
DEFROST display
display
This indicates when the defrost oper-
ation is performed. TEST RUN
This display lights in the check mode
or when a test operation is per-
formed.
FILTER display
CHECK display This lamp lights when the filter need
to be cleaned.
This indicates when a malfunction
has occurred in the unit which should SET TEMPERATURE display POWER display
be checked.
This displays the selected setting This lamp lights when electricity is
temperature. supplied to the unit.
Caution
q Only the Power display lights when the unit is stopped and power supplied to the unit.
q When power is turned ON for the first time the (CENTRAL CTRL) display appears to go off momentarily but this is not a
malfunction.
q When the central control remote control unit, which is sold separately, is used the ON-OFF button, operation switch button
and TEMP. adjustment button do not operate.
q “NOT AVAILABLE” is displayed when the Air speed button are pressed.This indicates that this room unit is not equipped
with the fan direction adjustment function and the louver function.
q When power is turned ON for the first time, it is normal that “H0” is displayed on the room temperature indication (For max.
2minutes). Please wait until this “H0” indication disappear then start the operation.
6
q Remote controller
Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
PCH-P2/2.5/3/4/5/6GAH1
PCA-P2/2.5/3/4/5/6GA1
q Operation buttons
TEMP. ADJUSTMENT button TIME SETTING button AIR SPEED button
This sets the room temperature. The This sets the current time, start time This sets the ventilation fan speed.
temperature setting can be performed and stop time.
in 1: units ON/OFF button
CENTRALLY CONTROLLED 1Hr.
Setting range ˚C This switches between the operation
Cooler 19: to 30: ON OFF and stop modes each time it is pressed.
Heater 17: to 28: The lamp on this button lights during
CHECK CLOCK operation.
TIMER button
STAND BY ˚C NOT AVAILABLE FILTER AIR DIRECTION button
This switches between continuous DEFROST CHECK MODE
operation and the timer operation. ERROR CODE TEST RUN This adjusts the vertical angle of the
FUNCTION ventilation.
OPERATION SWITCH button
TEMP. ON/OFF FILTER button
Press this button to switch the cooler,
electronic dry (dehumidify), automatic FILTER This resets the filter service indication
and heater modes. CHECK TEST display
PAR-20MAA TIMER SET
LOUVER button VENTILATION button CHECK-TEST RUN button
This switch the horizontal fan motion This sets the ventilation fan speed. Only press this button to perform an
ON and OFF. inspection check or test operation.
Do not use it for normal operation.
(Not available for this model.)
7
q Display
CENTRALLY CLOCK display In this display example on the bot-
CONTROLLED display tom left, a condition where all dis-
The current time , start time and stop play lamps light is shown for expla-
This indicates when the unit is con- time can be displayed in ten second nation purposes although this differs
trolled by optional features such as intervals by pressing the time switch from actual operation.
central control type remote controller. button. The start time or stop time is
always displayed during the timer AIR DIRECTION display
operation.
TIMER display This displays the air direction.
This indicates when the continuous CENTRALLY CONTROLLED 1Hr. FAN SPEED display
operation and time operation modes ˚C
are set. ON OFF The selected fan speed is displayed.
It also display the time for the timer
operation at the same time as when CHECK CLOCK ROOM TEMPERATURE display
it is set.
˚C FILTER The temperature of the suction air is
OPERATION MODE display CHECK MODE displayed during operation. The dis-
ERROR CODE TEST RUN play range is 8° to 39°C. The display
This indicates the operation mode. FUNCTION flashes 8°C when the actual temper-
ature is less than 8° and flashes
STAND BY NOT AVAILABLE 39°C when the actual temperature is
DEFROST greater than 39°C.
TEMP. ON/OFF
STANDBY display FILTER Operation lamp
CHECK TEST
This indicates when the standby This lamp lights during operation,
mode is set from the time the sleep PAR-20MAA TIMER SET goes off when the unit stops and
operation starts until the heating air flashes when a malfunction occurs.
is discharged.
CHECK MODE
DEFROST display
display
This indicates when the defrost oper-
ation is performed. TEST RUN
This display lights in the check mode
or when a test operation is per-
formed.
FILTER display
CHECK display This lamp lights when the filter need
to be cleaned.
This indicates when a malfunction
has occurred in the unit which should SET TEMPERATURE display POWER display
be checked.
This displays the selected setting This lamp lights when electricity is
temperature. supplied to the unit.
Caution
q Only the Power display lights when the unit is stopped and power supplied to the unit.
q When power is turned ON for the first time the (CENTRAL CTRL) display appears to go off momentarily but this is not a
malfunction.
q When the central control remote control unit, which is sold separately, is used the ON-OFF button, operation switch button
and TEMP. adjustment button do not operate.
q “NOT AVAILABLE” is displayed when the Air speed button are pressed.This indicates that this room unit is not equipped
with the fan direction adjustment function and the louver function.
q When power is turned ON for the first time, it is normal that “H0” is displayed on the room temperature indication (For max.
2minutes). Please wait until this “H0” indication disappear then start the operation.
8
5 SPECIFICATIONS
1. Heat pump type Rating Conditions (ISO T1)
Service Ref. With Electric heater PCH-P2GAH PCH-P2.5GAH
Item Without Electric heater PCA-P2GA PCA-P2.5GA
Function Cooling Heating Cooling Heating
Capacity w1 Btu/h 18,800 22,300 (27,100) 23,900 24,900 (32,100)
W
5,500 6,550 (7,950) 7,000 7,300 (9,400)
Total input w1 kW 2.58 2.67 (4.07) 2.76 2.71 (4.81)
Service Ref. With Electric heater PCH-P2GAH PCH-P2.5GAH
Without Electric heater
PCA-P2GA PCA-P2.5GA
Power supply Single phase, 50Hz, 220-230-240V
Input w2 kW 0.10 0.10 <1.40> 0.13 0.13 <2.10>
Running current w2 A 0.43 0.43 <5.83> 0.55 0.55 <8.75>
Starting current w2 A 1.20 1.20 <5.83> 1.27 1.27 <8.75>
External finish Munsell 0.70Y 8.59 / 0.97
INDOOR UNIT Heat exchanger Plate fin coil
Fan Fan(drive) x No. Sirocco (direct) x 2 Sirocco (direct) x 3
Fan motor output kW 0.054 0.07
Airflow(Lo-Mi2-Mi1-Hi) K/min(CFM) 10-11-12-13 (353-338-424-459) 14-15-16-18 (494-530-565-635)
External static pressure Pa(mmAq) 0 (direct blow)
Booster heater w2 kW <1.4> <2.1>
Operation control & Thermostat Remote controller & built-in
Noise level(Lo-Mi2-Mi1-Hi) dB 37-38-40-42 37-39-41-43
Unit drain pipe I.D. mm(in.) 26 (1)
Dimensions W mm(in.) 1,000 (39-3/8) 1,310 (51-9/16)
D mm(in.) 680 (26-3/4)
H mm(in.) 210 (8-1/4)
Weight With Electric heater kg(lbs) 28.5 (63) 36 (79)
Without Electric heater kg(lbs)
27 (60) 34 (75)
Service Ref. PUH-P2VGA / PUH-P2YGA PUH-P2.5VGA1 / PUH-P2.5YGA1
Power supply Single phase, 50Hz, 220-230-240V / 3 phases, 50Hz, 380-400-415V (4wires)
Running current A 11.11 / 3.88 11.51 / 4.02 11.78 / 4.11 11.55 / 4.03
Starting current A 74 / 30 77 / 32
External finish Munsell 5Y 8/1
Refrigerant control Linear Expansion Valve
Compressor Hermetic
Model NE38VMJM / NE38YEJM NE41VMJM / NE41YEJM
OUTDOOR UNIT Motor output kW 1.7 1.9
Starter type Line start
Protection devices Inner thermostat, HP switch, Discharge thermo. / Thermal relay, Discharge thermo, HP switch, Anti-phase protector.
Crankcase heater W 38
Heat exchanger Plate fin coil
Fan Fan(drive) x No. Propeller (direct) x 1
Fan motor output kW 0.070 0.070
Airflow K/min(CFM) 55(1,940) 50(1,770)
Defrost method Reverse cycle
Noise level Cooling dB 48 48
Heating dB 49 50
Dimensions W mm(in.) 900(35-7/16)
D mm(in.) 330+20(13+3/4)
H mm(in.) 855(33-5/8)
Weight kg(lbs) 71(157) 82(181)
REFRIGERANT PIPING Refrigerant R407C
Charge kg(lbs) 3.1(6.8) 3.3(7.3)
Oil (Model) L 1.2 (Ester)MEL56
Pipe size O.D. Liquid mm(in.) 9.52 (3/8)
Gas mm(in.) 15.88 (5/8)
Connection method Indoor side Flared
Outdoor side Flared
Between the indoor & Height difference Max. 40m Max. 50m
outdoor unit Piping length Max. 40m Max. 50m
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Heating : Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Indoor Outdoor w1 : ( ) Shows the total rating.
D.B. 46˚C w2 : < > Shows the only booster heater rating.
Upper limit D.B. 35˚C, W.B. 22.5˚C D.B. -5˚C
Cooling Lower limit D.B. 19˚C, W.B. 15˚C
Heating Upper limit D.B. 28˚C D.B. 24˚C, W.B. 18˚C
Lower limit D.B. 17˚C D.B. -11˚C, W.B. -12˚C
3. Above data based on indicated voltage
Indoor Unit Single phase 240V 50Hz
Outdoor Unit Single phase 240V 50Hz / 3 phase 415V 50Hz
9
Rating Conditions (ISO T1)
Service Ref. With Electric heater PCH-P3GAH PCH-P4GAH
PCA-P4GA
Item Without Electric heater PCA-P3GA
Function Cooling Heating Cooling Heating
Capacity w1 Btu/h 25,600 31,700 (38,900) 33,100 36,300 (45,600)
W 7,500 9,300 (11,400) 9,700 10,650 (13,350)
Total input w1 kW 3.47 3.65 (5.75) 3.52 3.70 (6.40)
Service Ref. With Electric heater PCH-P3GAH PCH-P4GAH
Without Electric heater PCA-P3GA PCA-P4GA
Power supply Single phase, 50Hz, 220-230-240V
Input w2 kW 0.13 0.13 <2.10> 0.16 0.16 <2.70>
Running current w2 A 0.55 0.55 <8.75> 0.70 0.70 <11.25>
Starting current w2 A 1.27 1.27 <8.75> 1.48 1.48 <11.25>
External finish Munsell 0.70Y 8.59 / 0.97
INDOOR UNIT Heat exchanger Plate fin coil
Fan Fan(drive) x No. Sirocco (direct) x 3
Fan motor output kW 0.07 0.09
Airflow(Lo-Mi2-Mi1-Hi) K/min(CFM) 14-15-16-18 <494-530-565-635> 20-21-23-25 <706-741-812-883>
External static pressure Pa(mmAq) 0 (direct blow)
Booster heater w2 kW <2.1> <2.7>
Operation control & Thermostat Remote controller & built-in
Noise level(Lo-Mi2-Mi1-Hi) dB 37-39-41-43 40-41-43-45
Unit drain pipe I.D. mm(in.) 26 (1)
Dimensions W mm(in.) 1,310 (51-9/16)
D mm(in.) 680 (26-3/4)
H mm(in.) 210 (8-1/4) 270 (10-5/8)
Weight With Electric heater kg(lbs) 36 (79) 39.5 (87)
Without Electric heater kg(lbs) 34 (75) 37 (82)
Service Ref. PUH-P3VGA / PUH-P3YGA PUH-P4YGA
Power supply Single phase, 50Hz, 220-230-240V / 3 phase, 50Hz, 380-400-415V (4wires) 3 phase, 50Hz, 380-400-415V (4wires)
Running current A 14.64 / 5.46 15.43 / 5.76 5.49 5.79
Starting current A 93 / 41 45
External finish Munsell 5Y 8/1
Refrigerant control Linear Expansion Valve
Compressor Hermetic
Model NE52VNJM / NE52YDJM NE56YDJM
Motor output kW 2.5 2.7
OUTDOOR UNIT Starter type Line start
Protection devices VGA...Inner thermostat, HP switch, Discharge thermo.
YGA...Thermal relay, Discharge thermo, HP switch, Anti-phase protector.
Crankcase heater W 38
Heat exchanger Plate fin coil
Fan Fan(drive) x No. Propeller (direct) x 1 Propeller (direct) x 2
Fan motor output kW 0.070 0.070+0.070
Airflow K/min(CFM) 50 (1,770) 85 (3,000)
Defrost method Reverse cycle
Noise level Cooling dB 49 51
Heating dB 51 53
Dimensions W mm(in.) 900 (35-7/16)
D mm(in.) 330+20 (13+3/4)
H mm(in.) 855 (33-5/8) 1,260 (49-5/8)
Weight kg(lbs) 82 (181) 96 (212)
REFRIGERANT PIPING Refrigerant R407C
Charge kg(lbs) 3.7 (8.2) 4.0 (8.8)
Oil (Model) L 1.6 (Ester)MEL56
Pipe size O.D. Liquid mm(in.) 9.52 (3/8)
Gas mm(in.) 15.88 (5/8) 19.05 (3/4)
Connection method Indoor side Flared
Outdoor side Flared
Between the indoor & Height difference Max. 50m
outdoor unit Piping length Max. 50m
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Heating : Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Indoor Outdoor w1 : ( ) Shows the total rating.
D.B. 46˚C w2 : < > Shows the only booster heater rating.
Upper limit D.B. 35˚C, W.B. 22.5˚C D.B. -5˚C
Cooling Lower limit D.B. 19˚C, W.B. 15˚C
Heating Upper limit D.B. 28˚C D.B. 24˚C, W.B. 18˚C
Lower limit D.B. 17˚C D.B. -11˚C, W.B. -12˚C
3. Above data based on indicated voltage
Indoor Unit Single phase 240V 50Hz
Outdoor Unit Single phase 240V 50Hz / 3 phase 415V 50Hz
10
Rating Conditions (ISO T1)
Service Ref. With Electric heater PCH-P5GAH PCH-P6GAH
Item Without Electric heater PCA-P5GA PCA-P6GA
Function Cooling Heating Cooling Heating
Capacity w1 Btu/h 43,700 54,600 (64,800) 49,500 57,300 (67,600)
W
12,800 16,000 (19,000) 14,500 16,800 (19,800)
Total input w1 kW 5.49 5.71 (8.71) 6.60 6.67 (9.67)
Service Ref. With Electric heater PCH-P5GAH PCH-P6GAH
Without Electric heater
PCA-P5GA PCA-P6GA
Power supply Single phase, 50Hz, 220-230-240V
Input w2 kW 0.24 0.24 <3.00> 0.24 0.24 <3.00>
Running current w2 A 1.06 1.06 <12.50> 1.06 1.06 <12.50>
Starting current w2 A 2.20 2.20 <12.50> 2.20 2.20 <12.50>
External finish Munsell 0.70Y 8.59 / 0.97
INDOOR UNIT Heat exchanger Plate fin coil
Fan Fan(drive) x No. Sirocco (direct) x 4
Fan motor output kW 0.15
Airflow(Lo-Mi2-Mi1-Hi) K/min(CFM) 27-30-32-34 <953-1,059-1,130-1,200>
External static pressure Pa(mmAq) 0 (direct blow)
Booster heater w2 kW <3.0>
Operation control & Thermostat Remote controller & built-in
Noise level(Lo-Mi2-Mi1-Hi) dB 41-43-45-46 42-44-46-48
Unit drain pipe I.D. mm(in.) 26 (1)
Dimensions W mm(in.) 1,620 (63-3/4)
D mm(in.) 680 (26-3/4)
H mm(in.) 270 (10-5/8)
Weight With Electric heater kg(lbs) 46 (101) 48 (106)
Without Electric heater kg(lbs)
43 (95) 45 (99)
Service Ref. PUH-P5YGA PUH-P6YGA
Power supply 3 Phase, 50Hz, 380-400-415V(4wires)
Running current A 8.39 8.74 10.17 10.28
Starting current A 79 84
External finish Munsell 5Y 8/1
Refrigerant control Linear Expansion Valve
Compressor Hermetic
Model HE86YAA HE101YAA
OUTDOOR UNIT Motor output kW 4.3 5.1
Starter type Line start
Protection devices Anti-phase protector, Internal thermostat, LP switch, HP switch,Thermal relay,Discharge thermo
Crankcase heater W 38
Heat exchanger Plate fin coil
Fan Fan(drive) x No. Propeller (direct) x 2
Fan motor output kW 0.075+0.075
Airflow K/min(CFM) 95 (3,360) 100 (3,530)
Defrost method Reverse cycle
Noise level Cooling dB 53 55
Heating dB 55 57
Dimensions W mm(in.) 1050 (41-5/16)
D mm(in.) 330+20 (13+3/4)
H mm(in.) 1,260 (49-5/8)
Weight kg(lbs) 122 (269)
REFRIGERANT PIPING Refrigerant R407C
Charge kg(lbs) 5.8 (12.8)
Oil (Model) L 2.0 (Ester)MEL32
Pipe size O.D. Liquid mm(in.) 9.52 (3/8)
Gas mm(in.) 19.05 (3/4)
Connection method Indoor side Flared
Outdoor side Flared
Between the indoor & Height difference Max. 50m
outdoor unit Piping length Max. 50m
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Heating : Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Indoor Outdoor w1 : ( ) Shows the total rating.
D.B. 46˚C w2 : < > Shows the only booster heater rating.
Upper limit D.B. 35˚C, W.B. 22.5˚C D.B. -5˚C
Cooling Lower limit D.B. 19˚C, W.B. 15˚C
Upper limit D.B. 28˚C D.B. 24˚C, W.B. 18˚C
Heating Lower limit D.B. 17˚C D.B. -11˚C, W.B. -12˚C
3. Above data based on indicated voltage
Indoor Unit Single phase 240V 50Hz
Outdoor Unit Single phase 240V 50Hz / 3 phase 415V 50Hz
11
2. Cooling only type Rating Conditions (ISO T1)
Item Service Ref. PCA-P2GA PCA-P2.5GA
Function Cooling Cooling
Capacity Btu/h 18,800 23,900
W
5,500 7,000
Total input kW 2.58 2.76
Service Ref. PCA-P2GA PCA-P2.5GA
Power supply Single phase, 50Hz, 220-230-240V
Input kW 0.10 0.13
Running current A 0.43 0.55
Starting current A 1.20 1.27
External finish Munsell 0.70Y 8.59 / 0.97
Heat exchanger Plate fin coil
INDOOR UNIT Fan Fan(drive))No. Sirocco (direct))2 Sirocco (direct))3
Fan motor output kW 0.054 0.07
Airflow(Lo-Mi2-Mi1-Hi) K/min <CFM> 10 -11-12-13 <353-338-424-459> 14 -15-16-18 <494-530-565-635>
External static pressure Pa(mmAq) 0 (direct blow)
Booster heater kW — —
Operation control & Thermostat Remote controller & built-in
Noise level(Lo-Mi2-Mi1-Hi) dB 37-38-40-42 37-39-41-43
Unit drain pipe I.D. mm(in.) 26(1)
Dimensions W mm(in.) 1,000(39-3/8) 1,310(51-9/16)
D mm(in.) 680(26-3/4)
H mm(in.) 210(8-1/4)
Weight kg(lbs) 27(60) 34(75)
Service Ref. PU-P2VGA PU-P2.5VGA1
Power supply Single phase, 50Hz, 220-230-240V
Running current A 11.11 11.78
Starting current A 74 77
External finish Munsell 5Y 8/1
Refrigerant control Linear Expansion Valve
Compressor Hermetic
Model NE38VMJM NE41VMJM
OUTDOOR UNIT Motor output kW 1.7 1.9
Starter type Line start
Protection devices Internal thermostat. High-pressure switch,Discharge thermo.
Crankcase heater W 38
Heat exchanger Plate fin coil
Fan Fan(drive))No. Propeller (direct)!1
Fan motor output kW 0.070
Airflow K/min <CFM> 55 (1,940) 50 (1,770)
Defrost method —
Noise level Cooling dB 48
Dimensions W mm(in.) 900 (35-7/16)
D mm(in.) 330+20 (13+3/4)
H mm(in.) 855 (33-5/8)
Weight kg(lbs) 71 (157) 82 (181)
Refrigerant R407C
Charge kg(lbs) 3.1 (6.8) 3.3 (7.3)
REFRIGERANT Compressor oil (Model) L 1.2 (Ester)MEL56
PIPING
Pipe size O.D. Liquid mm(in.) 9.52 (3/8)
Gas mm(in.)
15.88 (5/8)
Connection method Indoor side Flared
Outdoor side
Flared
Between the indoor & outdoor unit Height difference Max. 40m Max. 50m
Piping length
Max. 40m Max. 50m
Notes1. Rating Conditions (ISO T1) 2. Guaranteed operating range
Cooling : Indoor : D.B. 27:(80oF), W.B. 19:(66oF)
Outdoor : D.B. 35:(95oF), W.B. 24:(75oF) Indoor Outdoor
Refrigerant piping length (one way) : 5m(16ft) D.B. 46:
Cooling Upper limit D.B. 35:, W.B. 22.5: D.B. -5:
3. Above data based on indicated voltage Lower limit D.B. 19:, W.B. 15:
Indoor Unit Single phase 240V 50Hz
Outdoor Unit Single phase 240V 50Hz
12
Rating Conditions (ISO T1)
Item Service Ref. PCA-P3GA PCA-P4GA
Function Cooling Cooling
Capacity Btu/h 25,600 33,100
W 7,500 9,700
Total input kW 3.47 3.52
Service Ref. PCA-P3GA PCA-P4GA
Power supply Single phase, 50Hz, 220-230-240V
Input kW 0.13 0.16
Running current A 0.55 0.70
Starting current A 1.27 1.48
External finish Munsell 0.70Y 8.59 / 0.97
Heat exchanger Plate fin coil
INDOOR UNIT Fan Fan(drive))No. Sirocco (direct) ! 3
Fan motor output kW 0.07 0.09
Airflow(Lo-Mi2-Mi1-Hi) K/min <CFM> 14-15-16-18 <494-530-565-635> 20-21-23-25<706-741-812-883>
External static pressure Pa(mmAq) 0 (direct blow)
Booster heater kW —
Operation control & Thermostat Remote controller & built-in
Noise level(Lo-Mi2-Mi1-Hi) dB 37-39-41-43 40-41-43-45
Unit drain pipe I.D. mm(in.) 26 (1)
Dimensions W mm(in.) 1,310 (51-9/16)
D mm(in.) 680 (26-3/4)
H mm(in.) 210 (8-1/4) 270 (10-5/8)
Weight kg(lbs) 34 (75) 37 (82)
Service Ref. PU-P3VGA / PU-P3YGA PU-P4YGA
Power supply Single-phase, 50Hz, 220-230-240V / 3-phase, 50Hz,380-400-415V (4wires) 3-phase, 50Hz,380-400-415V (4wires)
Running current A 14.64 / 5.46 5.49
Starting current A 93 / 41 45
External finish Munsell 5Y 8/1
Refrigerant control Linear Expansion Valve
Compressor Hermetic
Model NE52VNJM / NE52YDJM NE56YDJM
OUTDOOR UNIT Motor output kW 2.5 2.7
Starter type Line start
Protection devices
Crankcase heater VGA...Inner thermostat. High-pressure switch Discharge thermo
Heat exchanger YGA...Anti-phase protector, Thermal relay, Discharge thermo, High-pressure switch
W 38
Plate fin coil
Fan Fan(drive))No. Propeller (direct) ! 1 Propeller (direct) ! 2
Fan motor output kW 0.070 0.070+0.070
Airflow K/min <CFM> 50 (1,770) 85 (3,000)
Defrost method
—
Noise level Cooling dB 49 51
Dimensions W mm(in.) 900 (35-7/16)
D mm(in.) 330 + 20 (13+3/4)
H mm(in.) 855 (33-5/8) 1,260 (49-5/8)
Weight kg(lbs) 82 (181) 96 (212)
Refrigerant R407C
Charge kg(lbs) 3.7 (8.2) 4.0 (8.8)
REFRIGERANT Compressor oil (Model) L 1.6 (Ester) MEL56
PIPING
Pipe size O.D. Liquid mm(in.) 9.52 (3/8)
Gas mm(in.)
15.88 (5/8) 19.05 (3/4)
Connection method Indoor side Flared
Outdoor side Flared
Between the indoor & outdoor unit Height difference Max. 50m
Piping length Max. 50m
Notes1. Rating Conditions (ISO T1) 2. Guaranteed operating range
Cooling : Indoor : D.B. 27:(80oF), W.B. 19:(66oF)
Outdoor : D.B. 35:(95oF), W.B. 24:(75oF) Indoor Outdoor
Refrigerant piping length (one way) : 5m(16ft) D.B. 46:
Cooling Upper limit D.B. 35:, D.B. 22.5: D.B. -5:
Lower limit D.B. 19:, D.B. 15:
3. Above data based on indicated voltage
Indoor Unit Single phase 240V 50Hz
Outdoor Unit Single phase 240V 50Hz / 3 phase 415V 50Hz
13
Rating Conditions (ISO T1)
Item Service Ref. PCA-P5GA PCA-P6GA
Function Cooling Cooling
Capacity Btu/h 43,700 49,500
W
12,800 14,500
Total input kW 5.49 6.60
Service Ref. PCA-P5GA PCA-P6GA
Power supply Single phase, 50Hz, 220-230-240V
Input kW 0.24 0.24
Running current A 1.06 1.06
Starting current A 2.20 2.20
External finish Munsell 0.70Y 8.59 / 0.97
Heat exchanger Plate fin coil
Sirocco (direct)!4
INDOOR UNIT Fan Fan(drive))No.
Fan motor output kW 0.15
Airflow(Lo-Mi2-Mi1-Hi) K/min <CFM> 27-30-32-34 <953-1,059-1,130-1,200>
External static pressure Pa(mmAq) 0 (direct blow)
Booster heater kW —
Operation control & Thermostat Remote controller & built-in
Noise level(Lo-Mi2-Mi1-Hi) dB 41-43-45-46 42-44-46-48
Unit drain pipe I.D. mm(in.) 26 (1)
Dimensions W mm(in.) 1,620 (63-3/4)
D mm(in.) 680 (26-3/4)
H mm(in.) 270 (10-5/8)
Weight kg(lbs) 43 (95) 45 (99)
Service Ref. PU-P5YGA PU-P6YGA
Power supply 3 phases, 50Hz, 380-400-415V (4wires)
Running current A 8.39 10.17
Starting current A 79 84
External finish Munsell 5Y 8/1
Refrigerant control Linear Expansion Valve
Compressor Hermetic
Model HE86YAA HE101YAA
OUTDOOR UNIT Motor output kW 4.3 5.1
Starter type Line start
Protection devices Anti-phase protector, Internal thermostat, LP switch, HP switch,Thermal relay,Discharge thermo
Crankcase heater W 38
Heat exchanger Plate fin coil
Propeller (direct)!2
Fan Fan(drive))No.
Fan motor output kW 0.075+0.075
Airflow K/min <CFM> 95 (3,360) 100 (3,530)
Defrost method —
Noise level Cooling dB 53 55
Dimensions W mm(in.) 1050 (41-5/16)
D mm(in.) 330+20 (13+3/4)
H mm(in.) 1,260 (49-5/8)
Weight kg(lbs) 122 (269)
Refrigerant R407C
Charge kg(lbs) 5.8 (12.8)
REFRIGERANT Compressor oil (Model) L 2.0 (Ester)MEL32
PIPING
Pipe size O.D. Liquid mm(in.) 9.52 (3/8)
Gas mm(in.)
19.05 (3/4)
Connection method Indoor side Flared
Outdoor side
Flared
Between the indoor & outdoor unit Height difference Max. 50m
Piping length
Max. 50m
Notes1. Rating Conditions (ISO T1) 2. Guaranteed operating range
Cooling : Indoor : D.B. 27:(80oF), W.B. 19:(66oF)
Outdoor : D.B. 35:(95oF), W.B. 24:(75oF) Indoor Outdoor
Refrigerant piping length (one way) : 5m(16ft) D.B. 46:
Cooling Upper limit D.B. 35:, W.B. 22.5: D.B. -5:
3. Above data based on indicated voltage Lower limit D.B. 19:, W.B. 15:
Indoor Unit Single phase 240V 50Hz
Outdoor Unit 3 phase 415V 50Hz
14
3. Heat pump type Rating Conditions (ISO T1)
Service Ref. With Electric heater PCH-P2GAH1 PCH-P2.5GAH1
Item Without Electric heater PCA-P2GA1 PCA-P2.5GA1
Function Cooling Heating Cooling Heating
Capacity w1 Btu/h 18,400 21,300 (26,100) 22,600 24,900 (32,100)
W
5,400 6,250 (7,650) 6,650 7,300 (9,400)
Total input w1 kW 2.40 2.40 (3.80) 2.65 2.71 (4.81)
Service Ref. With Electric heater PCH-P2GAH1 PCH-P2.5GAH1
Without Electric heater
PCA-P2GA1 PCA-P2.5GA1
Power supply Single phase, 50Hz, 220-230-240V
Input w2 kW 0.10 0.10 <1.40> 0.13 0.13 <2.10>
Running current w2 A 0.43 0.43 <5.83> 0.55 0.55 <8.75>
Starting current w2 A 1.20 1.20 <5.83> 1.27 1.27 <8.75>
External finish Munsell 0.70Y 8.59 / 0.97
INDOOR UNIT Heat exchanger Plate fin coil
Fan Fan(drive) x No. Sirocco (direct) x 2 Sirocco (direct) x 3
Fan motor output kW 0.054 0.07
Airflow(Lo-Mi2-Mi1-Hi) K/min(CFM) 10-11-12-13 (353-338-424-459) 14-15-16-18 (494-530-565-635)
External static pressure Pa(mmAq) 0 (direct blow)
Booster heater w2 kW <1.4> <2.1>
Operation control & Thermostat Remote controller & built-in
Noise level(Lo-Mi2-Mi1-Hi) dB 37-38-40-42 37-39-41-43
Unit drain pipe I.D. mm(in.) 26 (1)
Dimensions W mm(in.) 1,000 (39-3/8) 1,310 (51-9/16)
D mm(in.) 680 (26-3/4)
H mm(in.) 210 (8-1/4)
Weight With Electric heater kg(lbs) 28.5 (63) 36 (79)
Without Electric heater kg(lbs)
27 (60) 34 (75)
Service Ref. PUH-P2VGAA.UK / PUH-P2YGAA.UK PUH-P2.5VGAA.UK / PUH-P2.5YGAA.UK
Power supply Single phase, 50Hz, 220-230-240V / 3 phases, 50Hz, 380-400-415V (4wires)
Running current A 10.26 / 3.70 10.57 / 3.82 11.90 / 4.48 11.51 / 4.34
Starting current A 62 / 31 77 / 35
External finish Munsell 5Y 7/1
Refrigerant control Linear Expansion Valve
Compressor Hermetic
Model NE36VMJMT / NE36YEKMT NE41VMJMT / NE41YEKMT
OUTDOOR UNIT Motor output kW 1.6 1.9
Starter type Line start
Protection devices Inner thermostat, HP switch, Discharge thermo. / Thermal relay, Discharge thermo, HP switch.
Crankcase heater W 38
Heat exchanger Plate fin coil
Fan Fan(drive) x No. Propeller (direct) x 1
Fan motor output kW 0.070 0.070
Airflow K/min(CFM) 55 (1,940) 50 (1,770)
Defrost method Reverse cycle
Noise level Cooling dB 48 48
Heating dB 49 50
Dimensions W mm(in.) 900 (35-7/16)
D mm(in.) 330+20 (13+3/4)
H mm(in.) 855 (33-5/8)
Weight kg(lbs) 71 (157) 82 (181)
REFRIGERANT PIPING Refrigerant R407C
Charge kg(lbs) 2.6 (5.7) 3.1 (6.8)
Oil (Model) L 1.2 (Ester) MEL56
Pipe size O.D. Liquid mm(in.) 9.52 (3/8)
Gas mm(in.) 15.88 (5/8)
Connection method Indoor side Flared
Outdoor side Flared
Between the indoor & Height difference Max. 40m Max. 50m
outdoor unit Piping length Max. 40m Max. 50m
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Heating : Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Indoor Outdoor w1 : ( ) Shows the total rating.
D.B. 46˚C w2 : < > Shows the only booster heater rating.
Upper limit D.B. 35˚C, W.B. 22.5˚C D.B. -5˚C
Cooling Lower limit D.B. 19˚C, W.B. 15˚C
Heating Upper limit D.B. 28˚C D.B. 24˚C, W.B. 18˚C
Lower limit D.B. 17˚C D.B. -11˚C, W.B. -12˚C
3. Above data based on indicated voltage
Indoor Unit Single phase 240V 50Hz
Outdoor Unit Single phase 240V 50Hz / 3 phase 415V 50Hz
15
Rating Conditions (ISO T1)
Service Ref. With Electric heater PCH-P3GAH1 PCH-P4GAH1
Item Without Electric heater PCA-P3GA1 PCA-P4GA1
Function Cooling Heating Cooling Heating
Capacity w1 Btu/h 25,600 31,300 (38,500) 33,100 36,300 (45,600)
W
7,500 9,200 (11,300) 9,700 10,650 (13,350)
Total input w1 kW 3.40 3.50 (5.60) 3.64 3.83 (6.53)
Service Ref. With Electric heater PCH-P3GAH1 PCH-P4GAH1
Without Electric heater
PCA-P3GA1 PCA-P4GA1
Power supply Single phase, 50Hz, 220-230-240V
Input w2 kW 0.13 0.13 <2.10> 0.16 0.16 <2.70>
Running current w2 A 0.55 0.55 <8.75> 0.70 0.70 <11.25>
Starting current w2 A 1.27 1.27 <8.75> 1.48 1.48 <11.25>
External finish Munsell 0.70Y 8.59 / 0.97
INDOOR UNIT Heat exchanger Plate fin coil
Fan Fan(drive) x No. Sirocco (direct) x 3
Fan motor output kW 0.07 0.09
Airflow(Lo-Mi2-Mi1-Hi) K/min(CFM) 14-15-16-18 <494-530-565-635> 20-21-23-25 <706-741-812-883>
External static pressure Pa(mmAq) 0 (direct blow)
Booster heater w2 kW <2.1> <2.7>
Operation control & Thermostat Remote controller & built-in
Noise level(Lo-Mi2-Mi1-Hi) dB 37-39-41-43 40-41-43-45
Unit drain pipe I.D. mm(in.) 26 (1)
Dimensions W mm(in.) 1,310 (51-9/16)
D mm(in.) 680 (26-3/4)
H mm(in.) 210 (8-1/4) 270 (10-5/8)
Weight With Electric heater kg(lbs) 36 (79) 39.5 (87)
Without Electric heater kg(lbs)
34 (75) 37 (82)
Service Ref. PUH-P3VGAA.UK / PUH-P3YGAA.UK PUH-P4VGAA.UK / PUH-P4YGAA.UK
Power supply Single phase, 50Hz, 220-230-240V / 3 phase, 50Hz, 380-400-415V (4wires)
Running current A 14.81 / 5.29 15.76 / 5.63 15.71 / 5.55 16.58 / 5.86
Starting current A 93 / 47 99 / 49
External finish Munsell 5Y 7/1
Refrigerant control Linear Expansion Valve
Compressor Hermetic
Model NE52VNJMT / NE52YDKMT NE56VNJMT / NE56YDKMT
Motor output kW 2.5 2.7
OUTDOOR UNIT Starter type Line start
Protection devices Inner thermostat, HP switch, Discharge thermo. /
Anti-phase protector. Thermal relay, Discharge thermo, HP switch.
Crankcase heater W 38
Heat exchanger Plate fin coil
Fan Fan(drive) x No. Propeller (direct) x 1 Propeller (direct) x 2
Fan motor output kW 0.070 0.070+0.070
K/min(CFM)
Airflow 50 (1,770) 85 (3,000)
Defrost method Reverse cycle
Noise level Cooling dB 49 51
Heating dB
mm(in.) 51 53
W mm(in.)
Dimensions D mm(in.) 900 (35-7/16)
H kg(lbs)
330+20 (13+3/4)
855 (33-5/8) 1,260 (49-5/8)
Weight 82 (181) 96 (212)
Refrigerant
REFRIGERANT PIPING R407C
Charge
Oil (Model) kg(lbs) 3.3 (7.3) 4.0 (8.8)
Pipe size O.D.
L 1.3 (Ester) MEL56
Connection method
Liquid mm(in.) 9.52 (3/8)
Between the indoor &
outdoor unit Gas mm(in.) 15.88 (5/8) 19.05 (3/4)
Indoor side Flared
Outdoor side Flared
Height difference Max. 50m
Piping length Max. 50m
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Heating : Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Indoor Outdoor w1 : ( ) Shows the total rating.
D.B. 46˚C w2 : < > Shows the only booster heater rating.
Upper limit D.B. 35˚C, W.B. 22.5˚C D.B. -5˚C
Cooling Lower limit D.B. 19˚C, W.B. 15˚C
Heating Upper limit D.B. 28˚C D.B. 24˚C, W.B. 18˚C
Lower limit D.B. 17˚C D.B. -11˚C, W.B. -12˚C
3. Above data based on indicated voltage
Indoor Unit Single phase 240V 50Hz
Outdoor Unit Single phase 240V 50Hz / 3 phase 415V 50Hz
16
Rating Conditions (ISO T1)
Service Ref. With Electric heater PCH-P5GAH1 PCH-P6GAH1
Item Without Electric heater PCA-P5GA1 PCA-P6GA1
Function Cooling Heating Cooling Heating
Capacity w1 Btu/h 42,300 50,800 (61,000) 48,700 58,300 (68,500)
W
12,400 14,900 (17,880) 14,300 17,100 (20,100)
Total input w1 kW 4.94 5.14 (8.14) 5.94 6.27 (9.27)
Service Ref. With Electric heater PCH-P5GAH1 PCH-P6GAH1
Without Electric heater
PCA-P5GA1 PCA-P6GA1
Power supply Single phase, 50Hz, 220-230-240V
Input w2 kW 0.24 0.24 <3.00> 0.24 0.24 <3.00>
Running current w2 A 1.06 1.06 <12.50> 1.06 1.06 <12.50>
Starting current w2 A 2.20 2.20 <12.50> 2.20 2.20 <12.50>
External finish Munsell 0.70Y 8.59 / 0.97
INDOOR UNIT Heat exchanger Plate fin coil
Fan Fan(drive) x No. Sirocco (direct) x 4
Fan motor output kW 0.15
Airflow(Lo-Mi2-Mi1-Hi) K/min(CFM) 27-30-32-34 <953-1,059-1,130-1,200>
External static pressure Pa(mmAq) 0 (direct blow)
Booster heater w2 kW <3.0>
Operation control & Thermostat Remote controller & built-in
Noise level(Lo-Mi2-Mi1-Hi) dB 41-43-45-46 42-44-46-48
Unit drain pipe I.D. mm(in.) 26 (1)
Dimensions W mm(in.) 1,620 (63-3/4)
D mm(in.) 680 (26-3/4)
H mm(in.) 270 (10-5/8)
Weight With Electric heater kg(lbs) 46 (101) 48 (106)
Without Electric heater kg(lbs)
43 (95) 45 (99)
Service Ref. PUH-P5YGAA.UK PUH-P6YGAA.UK
Power supply 3 Phase, 50Hz, 380-400-415V (4wires)
Running current A 7.60 8.15 9.03 9.56
Starting current A 65.5 74
External finish Munsell 5Y 7/1
Refrigerant control Linear Expansion Valve
Compressor Hermetic
Model ZR61KCE-TFD ZR72KCE-TFD
OUTDOOR UNIT Motor output kW 3.5 4.2
Starter type Line start
Protection devices Anti-phase protector, Internal thermostat, LP switch, HP switch,Thermal relay,Discharge thermo
Crankcase heater W 38
Heat exchanger Plate fin coil
Fan Fan(drive) x No. Propeller (direct) x 2
Fan motor output kW 0.070+0.070
Airflow K/min(CFM) 95 (3,360) 100 (3,530)
Defrost method Reverse cycle
Noise level Cooling dB 55 57
Heating dB 56 58
Dimensions W mm(in.) 1050 (41-5/16)
D mm(in.) 330+20 (13+3/4)
H mm(in.) 1,260 (49-5/8)
Weight kg(lbs) 122 (269)
REFRIGERANT PIPING Refrigerant R407C
Charge kg(lbs) 4.6 (10.1) 4.9 (10.8)
Oil (Model) L 1.690 (Ester) MMMA-POE 1.774 (Ester) MMMA-POE
Pipe size O.D. Liquid mm(in.) 9.52 (3/8)
Gas mm(in.) 19.05 (3/4)
Connection method Indoor side Flared
Outdoor side Flared
Between the indoor & Height difference Max. 50m
outdoor unit Piping length Max. 50m
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Heating : Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Indoor Outdoor w1 : ( ) Shows the total rating.
D.B. 46˚C w2 : < > Shows the only booster heater rating.
Upper limit D.B. 35˚C, W.B. 22.5˚C D.B. -5˚C
Cooling Lower limit D.B. 19˚C, W.B. 15˚C
Heating Upper limit D.B. 28˚C D.B. 24˚C, W.B. 18˚C
Lower limit D.B. 17˚C D.B. -11˚C, W.B. -12˚C
3. Above data based on indicated voltage
Indoor Unit Single phase 240V 50Hz
Outdoor Unit Single phase 240V 50Hz / 3 phase 415V 50Hz
17
4. Cooling only type Rating Conditions (ISO T1)
Item Service Ref. PCA-P2GA1 PCA-P2.5GA1
Function Cooling Cooling
Capacity Btu/h 18,400 22,700
W 5,400 6,650
Total input kW 2.40 2.65
Service Ref. PCA-P2GA1 PCA-P2.5GA1
Power supply Single phase, 50Hz, 220-230-240V
Input kW 0.10 0.13
Running current A 0.43 0.55
Starting current A 1.20 1.27
External finish Munsell 0.70Y 8.59 / 0.97
Heat exchanger Plate fin coil
INDOOR UNIT Fan Fan(drive))No. Sirocco (direct))2 Sirocco (direct))3
Fan motor output kW 0.054 0.07
Airflow(Lo-Mi2-Mi1-Hi) K/min <CFM> 10 -11-12-13 <353-338-424-459> 14 -15-16-18 <494-530-565-635>
External static pressure Pa(mmAq) 0 (direct blow)
Booster heater kW — —
Operation control & Thermostat Remote controller & built-in
Noise level(Lo-Mi2-Mi1-Hi) dB 37-38-40-42 37-39-41-43
Unit drain pipe I.D. mm(in.) 26 (1)
Dimensions W mm(in.) 1,000 (39-3/8) 1,310 (51-9/16)
D mm(in.) 680 (26-3/4)
H mm(in.) 210 (8-1/4)
Weight kg(lbs) 27 (60) 34 (75)
Service Ref. PU-P2VGAA.UK / PU-P2YGAA.UK PU-P2.5VGAA.UK / PU-P2.5YGAA.UK
Power supply Single phase, 50Hz, 220-230-240V / 3 phases, 50Hz, 380-400-415V (4wires)
Running current A 10.26 / 3.70 11.90 / 4.48
Starting current A 62 / 31 77 / 35
External finish Munsell 5Y 7/1
Refrigerant control Linear Expansion Valve
Compressor Hermetic
Model NE36VMJMT / NE36YEKMT NE41VMJMT / NE41YEKMT
OUTDOOR UNIT Motor output kW 1.6 1.9
Starter type Line start
Protection devices Internal thermostat. High-pressure switch,Discharge thermo. / Thermal relay, HP switch, Discharge thermo.
Crankcase heater W 38
Heat exchanger Plate fin coil
Fan Fan(drive))No. Propeller (direct) !1
Fan motor output kW 0.070
Airflow K/min <CFM> 55 (1,940) 50 (1,770)
Defrost method —
Noise level Cooling dB 48
Dimensions W mm(in.) 900 (35-7/16)
D mm(in.) 330+20 (13+3/4)
H mm(in.) 855 (33-5/8)
Weight kg(lbs) 71 (157) 82 (181)
Refrigerant R407C
Charge kg(lbs) 2.6 (5.7) 3.1 (6.8)
REFRIGERANT Compressor oil (Model) L 1.2 (Ester) MEL56
PIPING
Pipe size O.D. Liquid mm(in.) 9.52 (3/8)
Gas mm(in.) 15.88 (5/8)
Connection method Indoor side Flared
Outdoor side Flared
Between the indoor & outdoor unit Height difference Max. 40m Max. 50m
Piping length Max. 40m Max. 50m
Notes1. Rating Conditions (ISO T1) 2. Guaranteed operating range
Cooling : Indoor : D.B. 27:(80oF), W.B. 19:(66oF)
Outdoor : D.B. 35:(95oF), W.B. 24:(75oF) Indoor Outdoor
Refrigerant piping length (one way) : 5m(16ft) D.B. 46:
Cooling Upper limit D.B. 35:, W.B. 22.5: D.B. -5:
Lower limit D.B. 19:, W.B. 15:
3. Above data based on indicated voltage
Indoor Unit Single phase 240V 50Hz
Outdoor Unit Single phase 240V 50Hz / 3 phases 415V 50Hz
18
Rating Conditions (ISO T1)
Item Service Ref. PCA-P3GA1 PCA-P4GA1
Function Cooling Cooling
Capacity Btu/h 25,600 33,100
W
7,500 9,700
Total input kW 3.40 3.64
Service Ref. PCA-P3GA1 PCA-P4GA1
Power supply Single phase, 50Hz, 220-230-240V
Input kW 0.13 0.16
Running current A 0.55 0.70
Starting current A 1.27 1.48
External finish Munsell 0.70Y 8.59 / 0.97
Heat exchanger Plate fin coil
INDOOR UNIT Fan Fan(drive))No. Sirocco (direct) ! 3
Fan motor output kW 0.07 0.09
Airflow(Lo-Mi2-Mi1-Hi) K/min <CFM> 14-15-16-18 <494-530-565-635> 20-21-23-25 <706-741-812-883>
External static pressure Pa(mmAq) 0 (direct blow)
Booster heater kW —
Operation control & Thermostat Remote controller & built-in
Noise level(Lo-Mi2-Mi1-Hi) dB 37-39-41-43 40-41-43-45
Unit drain pipe I.D. mm(in.) 26 (1)
Dimensions W mm(in.) 1,310 ( 51-9/16 )
D mm(in.) 680 (26-3/4)
H mm(in.) 210 (8-1/4) 270 (10-5/8)
Weight kg(lbs) 34 (75) 37 (82)
Service Ref. PU-P3VGAA.UK / PU-P3YGAA.UK PU-P4VGAA.UK / PU-P4YGAA.UK
Power supply Single-phase, 50Hz, 220-230-240V / 3-phase, 50Hz, 380-400-415V (4wires)
Running current A 14.81 / 5.29 15.71 / 5.55
Starting current A 93 / 47 99 / 49
External finish Munsell 5Y 7/1
Refrigerant control Linear Expansion Valve
Compressor Hermetic
Model NE52VNJMT / NE52YDKMT NE56VNJMT / NE56YDKMT
OUTDOOR UNIT Motor output kW 2.5 2.7
Starter type Line start
Protection devices Inner thermostat. High-pressure switch Discharge thermo /
High-pressure switch Thermal relay, Discharge thermo
Crankcase heater W
38
Heat exchanger Plate fin coil
Fan Fan(drive))No. Propeller (direct) ! 1 Propeller (direct) ! 2
Fan motor output kW 0.070 0.070+0.070
Airflow K/min <CFM> 50 (1,770) 85 (3,000)
Defrost method —
Noise level Cooling dB 49 51
Dimensions W mm(in.) 900 (35-7/16)
D mm(in.) 330 + 20 (13+3/4)
H mm(in.) 855 (33-5/8) 1,260 (49-5/8)
Weight kg(lbs) 82 (181) 96 (212)
Refrigerant R407C
Charge kg(lbs) 3.3 (7.3) 4.0 (8.8)
REFRIGERANT Compressor oil (Model) L 1.3 (Ester) MEL56
PIPING
Pipe size O.D. Liquid mm(in.) 9.52 (3/8)
Gas mm(in.)
15.88 (5/8) 19.05 (3/4)
Connection method Indoor side Flared
Outdoor side
Flared
Between the indoor & outdoor unit Height difference Max. 50m
Piping length
Max. 50m
Notes1. Rating Conditions (ISO T1) 2. Guaranteed operating range
Cooling : Indoor : D.B. 27:(80oF), W.B. 19:(66oF)
Outdoor : D.B. 35:(95oF), W.B. 24:(75oF) Indoor Outdoor
Refrigerant piping length (one way) : 5m(16ft) D.B. 46:
Cooling Upper limit D.B. 35:, D.B. 22.5: D.B. -5:
Lower limit D.B. 19:, D.B. 15:
3. Above data based on indicated voltage
Indoor Unit Single phase 240V 50Hz
Outdoor Unit Single phase 240V 50Hz / 3 phase 415V 50Hz
19
Rating Conditions (ISO T1)
Item Service Ref. PCA-P5GA1 PCA-P6GA1
Function Cooling Cooling
Capacity Btu/h 42,300 48,700
W
12,400 14,300
Total input kW 4.94 5.94
Service Ref. PCA-P5GA1 PCA-P6GA1
Power supply Single phase, 50Hz, 220-230-240V
Input kW 0.24 0.24
Running current A 1.06 1.06
Starting current A 2.20 2.20
External finish Munsell 0.70Y 8.59 / 0.97
Heat exchanger Plate fin coil
Sirocco (direct) !4
INDOOR UNIT Fan Fan(drive))No.
Fan motor output kW 0.15
Airflow(Lo-Mi2-Mi1-Hi) K/min <CFM> 27-30-32-34 <953-1,059-1,130-1,200>
External static pressure Pa(mmAq) 0 (direct blow)
Booster heater kW —
Operation control & Thermostat Remote controller & built-in
Noise level(Lo-Mi2-Mi1-Hi) dB 41-43-45-46 42-44-46-48
Unit drain pipe I.D. mm(in.) 26 (1)
Dimensions W mm(in.) 1,620 (63-3/4)
D mm(in.) 680 (26-3/4)
H mm(in.) 270 (10-5/8)
Weight kg(lbs) 43 (95) 45 (99)
Service Ref. PU-P5YGAA.UK PU-P6YGAA.UK
Power supply 3 phases, 50Hz, 380-400-415V (4wires)
Running current A 7.60 9.03
Starting current A 65.5 74
External finish Munsell 5Y 7/1
Refrigerant control Linear Expansion Valve
Compressor Hermetic
Model ZR61KCE-TFD ZR72KCE-TFD
OUTDOOR UNIT Motor output kW 3.5 4.2
Starter type Line start
Protection devices Internal thermostat, HP switch,Thermal relay,Discharge thermo
Crankcase heater W 38
Heat exchanger Plate fin coil
Propeller (direct) !2
Fan Fan(drive))No.
Fan motor output kW 0.070+0.070
Airflow K/min <CFM> 95 (3,360) 100 (3,530)
Defrost method —
Noise level Cooling dB 55 57
Dimensions W mm(in.) 1050 (41-5/16)
D mm(in.) 330+20 (13+3/4)
H mm(in.) 1,260 (49-5/8)
122 (269)
Weight kg(lbs)
Refrigerant R407C
Charge kg(lbs) 4.6 (10.1) 4.9 (10.8)
REFRIGERANT Compressor oil (Model) L 1.690 (Ester) MMMA-POE 1.774 (Ester) MMMA-POE
PIPING
Pipe size O.D. Liquid mm(in.) 9.52 (3/8)
Gas mm(in.)
19.05 (3/4)
Connection method Indoor side Flared
Outdoor side
Flared
Between the indoor & outdoor unit Height difference Max. 50m
Piping length
Max. 50m
Notes1. Rating Conditions (ISO T1) 2. Guaranteed operating range
Cooling : Indoor : D.B. 27:(80oF), W.B. 19:(66oF)
Outdoor : D.B. 35:(95oF), W.B. 24:(75oF) Indoor Outdoor
Refrigerant piping length (one way) : 5m(16ft) D.B. 46:
Cooling Upper limit D.B. 35:, W.B. 22.5: D.B. -5:
3. Above data based on indicated voltage Lower limit D.B. 19:, W.B. 15:
Indoor Unit Single phase 240V 50Hz
Outdoor Unit 3 phase 415V 50Hz
20
6 DATA
1. PERFORMANCE DATA (240V)
1) COOLING CAPACITY<1>
PCH-P2GAH
PCA-P2GA
Indoor Indoor 20 Outdoor intake air D.B.(°C) 30
Intake air Intake air 25 CA SHC(W) SHF P.C.
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 5,445 3,376 0.62 2.06 5,280 3,274 0.62 2.18 5,115 3,717 0.62 2.31
20 18 5,830 2,915 0.50 2.10 5,665 2,833 0.50 2.22 5,473 2,736 0.50 2.37
20 20 6,270 2,383 0.38 2.17 6,133 2,330 0.38 2.27 5,986 2,268 0.38 2.43
22 16 5,445 3,812 0.70 2.06 5,280 3,696 0.70 2.18 5,115 3,581 0.70 2.31
22 18 5,830 3,381 0.58 2.10 5,665 3,286 0.58 2.22 5,473 3,174 0.58 2.37
22 20 6,270 2,884 0.46 2.17 6,133 2,821 0.46 2.27 5,968 2,745 0.46 2.43
24 16 5,445 4,247 0.78 2.06 5,280 4,118 0.78 2.18 5,115 3,990 0.78 2.31
24 18 5,830 3,848 0.66 2.10 5,665 3,739 0.66 2.22 5,473 3,612 0.66 2.37
24 20 6,270 3,386 0.54 2.17 6,133 3,312 0.54 2.27 5,968 3,222 0.54 2.43
24 22 6,683 2,807 0.42 2.22 6,545 2,749 0.42 2.35 6,380 2,680 0.42 2.50
26 16 5,445 4,683 0.86 2.06 5,280 4,541 0.86 2.18 5,115 4,399 0.86 2.31
26 18 5,830 4,314 0.74 2.10 5,665 4,192 0.74 2.22 5,473 4,050 0.74 2.37
26 20 6,270 3,887 0.62 2.17 6,133 3,802 0.62 2.27 5,968 3,700 0.62 2.43
26 22 6,683 3,341 0.50 2.22 6,545 3,273 0.50 2.35 6,380 3,190 0.50 2.50
28 16 5,445 5,118 0.94 2.06 5,280 4,963 0.94 2.18 5,115 4,808 0.94 2.31
28 18 5,830 4,781 0.82 2.10 5,665 4,645 0.82 2.22 5,473 4,487 0.82 2.37
28 20 6,270 4,389 0.70 2.17 6,133 4,293 0.70 2.27 5,968 4,177 0.70 2.43
28 22 6,683 3,876 0.58 2.22 6,545 3,796 0.58 2.35 6,380 3,700 0.58 2.50
30 16 5,445 5,445 1.00 2.06 5,280 5,280 1.00 2.18 5,115 5,115 1.00 2.31
30 18 5,830 5,247 0.90 2.10 5,665 5,099 0.90 2.22 5,473 4,925 0.90 2.37
30 20 6,270 4,891 0.78 2.17 6,133 4,783 0.78 2.27 5,968 4,655 0.78 2.43
30 22 6,683 4,410 0.66 2.22 6,545 4,320 0.66 2.35 6,380 4,211 0.66 2.50
32 16 5,445 5,445 1.00 2.06 5,280 5,280 1.00 2.18 5,115 5,115 1.00 2.31
32 18 5,830 5,713 0.98 2.10 5,665 5,552 0.98 2.22 5,473 5,363 0.98 2.37
32 20 6,270 5,392 0.86 2.17 6,133 5,274 0.86 2.27 5,968 5,132 0.86 2.43
32 22 6,683 4,945 0.74 2.22 6,545 4,843 0.74 2.35 6,380 4,721 0.74 2.50
34 16 5,445 5,445 1.00 2.06 5,280 5,280 1.00 2.18 5,115 5,115 1.00 2.31
34 18 5,830 5,830 1.00 2.10 5,665 5,665 1.00 2.22 5,473 5,473 1.00 2.37
34 20 6,270 5,894 0.94 2.17 6,133 5,765 0.94 2.27 5,968 5,609 0.94 2.43
34 22 6,683 5,480 0.82 2.22 6,545 5,367 0.82 2.35 6,380 5,232 0.82 2.50
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
21
COOLING CAPACITY<2>
PCH-P2GAH
PCA-P2GA
Indoor Indoor 35 Outdoor intake air D.B.(°C) 45
Intake air Intake air 40 CA SHC(W) SHF P.C.
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 4,895 3,035 0.62 2.48 4,675 2,899 0.62 2.66 4,455 2,762 0.62 2.88
20 18 5,280 2,640 0.50 2.54 5,115 2,558 0.50 2.73 4,785 2,393 0.50 2.94
20 20 5,720 2,174 0.38 2.61 5,500 2,090 0.38 2.79 5,170 1,965 0.38 2.99
22 16 4,895 3,427 0.70 2.48 4,675 3,273 0.70 2.66 4,455 3,119 0.70 2.88
22 18 5,280 3,062 0.58 2.54 5,115 2,967 0.58 2.73 4,785 2,775 0.58 2.94
22 20 5,720 2,631 0.46 2.61 5,500 2,530 0.46 2.79 5,170 2,378 0.46 2.99
24 16 4,895 3,818 0.78 2.48 4,675 3,647 0.78 2.66 4,455 3,475 0.78 2.88
24 18 5,280 3,485 0.66 2.54 5,115 3,376 0.66 2.73 4,785 3,158 0.66 2.94
24 20 5,720 3,089 0.54 2.61 5,500 2,970 0.54 2.79 5,170 2,792 0.54 2.99
24 22 6,160 2,587 0.42 2.66 5,940 2,495 0.42 2.86 5,610 2,356 0.42 3.04
26 16 4,895 4,210 0.86 2.48 4,675 4,021 0.86 2.66 4,455 3,831 0.86 2.88
26 18 5,280 3,907 0.74 2.54 5,115 3,785 0.74 2.73 4,785 3,541 0.74 2.94
26 20 5,720 3,546 0.62 2.61 5,500 3,410 0.62 2.79 5,170 3,205 0.62 2.99
26 22 6,160 3,080 0.50 2.66 5,940 2,970 0.50 2.86 5,610 2,805 0.50 3.04
28 16 4,895 4,601 0.94 2.48 4,675 4,395 0.94 2.66 4,455 4,188 0.94 2.88
28 18 5,280 4,330 0.82 2.54 5,115 4,194 0.82 2.73 4,785 3,924 0.82 2.94
28 20 5,720 4,004 0.70 2.61 5,500 3,850 0.70 2.79 5,170 3,619 0.70 2.99
28 22 6,160 3,573 0.58 2.66 5,940 3,445 0.58 2.86 5,610 3,254 0.58 3.04
30 16 4,895 4,895 1.00 2.48 4,675 4,675 1.00 2.66 4,455 4,455 1.00 2.88
30 18 5,280 4,752 0.90 2.54 5,115 4,604 0.90 2.73 4,785 4,307 0.90 2.94
30 20 5,720 4,462 0.78 2.61 5,500 4,290 0.78 2.79 5,170 4,033 0.78 2.99
30 22 6,160 4,066 0.66 2.66 5,940 3,920 0.66 2.86 5,610 3,703 0.66 3.04
32 16 4,895 4,895 1.00 2.48 4,675 4,675 1.00 2.66 4,455 4,455 1.00 2.88
32 18 5,280 5,174 0.98 2.54 5,115 5,013 0.98 2.73 4,785 4,689 0.98 2.94
32 20 5,720 4,919 0.86 2.61 5,500 4,730 0.86 2.79 5,170 4,446 0.86 2.99
32 22 6,160 4,558 0.74 2.66 5,940 4,396 0.74 2.86 5,610 4,151 0.74 3.04
34 16 4,895 4,895 1.00 2.48 4,975 4,675 1.00 2.66 4,455 4,455 1.00 2.88
34 18 5,280 5,280 1.00 2.54 5,115 5,115 1.00 2.73 4,785 4,785 1.00 2.94
34 20 5,720 5,377 0.94 2.61 5,500 5,170 0.94 2.79 5,170 4,860 0.94 2.99
34 22 6,160 5,051 0.82 2.66 5,940 4,871 0.82 2.86 5,610 4,600 0.82 3.04
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
22
COOLING CAPACITY<3>
PCH-P2.5GAH
PCA-P2.5GA
Indoor Indoor 20 Outdoor intake air D.B.(°C) 30
Intake air Intake air 25 CA SHC(W) SHF P.C.
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 6,930 4,505 0.65 2.21 6,720 4,368 0.65 2.33 6,510 4,232 0.65 2.47
20 18 7,420 3,933 0.53 2.25 7,210 3,821 0.53 2.37 6,965 3,691 0.53 2.54
20 20 7,980 3,272 0.41 2.32 7,805 3,200 0.41 2.43 7,595 3,114 0.41 2.59
22 16 6,930 5,059 0.73 2.21 6,720 4,906 0.73 2.33 6,510 4,752 0.73 2.47
22 18 7,420 4,526 0.61 2.25 7,210 4,398 0.61 2.37 6,965 4,249 0.61 2.54
22 20 7,980 3,910 0.49 2.32 7,805 3,824 0.49 2.43 7,595 3,722 0.49 2.59
24 16 6,930 5,613 0.81 2.21 6,720 5,443 0.81 2.33 6,510 5,273 0.81 2.47
24 18 7,420 5,120 0.69 2.25 7,210 4,975 0.69 2.37 6,965 4,806 0.69 2.54
24 20 7,980 4,549 0.57 2.32 7,805 4,449 0.57 2.43 7,595 4,329 0.57 2.59
24 22 8,505 3,827 0.45 2.37 8,330 3,749 0.45 2.51 8,120 3,654 0.45 2.68
26 16 6,930 6,168 0.89 2.21 6,720 5,981 0.89 2.33 6,510 5,794 0.89 2.47
26 18 7,420 5,713 0.77 2.25 7,210 5,552 0.77 2.37 6,965 5,363 0.77 2.54
26 20 7,980 5,187 0.65 2.32 7,805 5,073 0.65 2.43 7,595 4,937 0.65 2.59
26 22 8,505 4,508 0.53 2.37 8,330 4,415 0.53 2.51 8,120 4,304 0.53 2.68
28 16 6,930 6,722 0.97 2.21 6,720 6,518 0.97 2.33 6,510 6,315 0.97 2.47
28 18 7,420 6,307 0.85 2.25 7,210 6,129 0.85 2.37 6,965 5,920 0.85 2.54
28 20 7,980 5,825 0.73 2.32 7,805 5,698 0.73 2.43 7,595 5,544 0.73 2.59
28 22 8,505 5,188 0.61 2.37 8,330 5,081 0.61 2.51 8,120 4,953 0.61 2.68
30 16 6,930 6,930 1.00 2.21 6,720 6,720 1.00 2.33 6,510 6,510 1.00 2.47
30 18 7,420 6,901 0.93 2.25 7,210 6,705 0.93 2.37 6,965 6,477 0.93 2.54
30 20 7,980 6,464 0.81 2.32 7,805 6,322 0.81 2.43 7,595 6,152 0.81 2.59
30 22 8,505 5,868 0.69 2.37 8,330 5,748 0.69 2.51 8,120 5,603 0.69 2.68
32 16 6,930 6,930 1.00 2.21 6,720 6,720 1.00 2.33 6,510 6,510 1.00 2.47
32 18 7,420 7,420 1.00 2.25 7,210 7,210 1.00 2.37 6,965 6,965 1.00 2.54
32 20 7,980 7,102 0.89 2.32 7,805 6,946 0.89 2.43 7,595 6,760 0.89 2.59
32 22 8,505 6,549 0.77 2.37 8,330 6,414 0.77 2.51 8,120 6,252 0.77 2.68
34 16 6,930 6,930 1.00 2.21 6,720 6,720 1.00 2.33 6,510 6,510 1.00 2.47
34 18 7,420 7,420 1.00 2.25 7,210 7,210 1.00 2.37 6,965 6,965 1.00 2.54
34 20 7,980 7,741 0.97 2.32 7,805 7,571 0.97 2.43 7,595 7,367 0.97 2.59
34 22 8,505 7,229 0.85 2.37 8,330 7,081 0.85 2.51 8,120 6,902 0.85 2.68
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
23
COOLING CAPACITY<4>
PCH-P2.5GAH
PCA-P2.5GA
Indoor Indoor 35 Outdoor intake air D.B.(°C) 45
Intake air Intake air 40 CA SHC(W) SHF P.C.
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 6,230 4,050 0.65 2.65 5,950 3,868 0.65 2.84 5,670 3,686 0.65 3.08
20 18 6,720 3,562 0.53 2.72 6,510 3,450 0.53 2.93 6,090 3,228 0.53 3.15
20 20 7,280 2,985 0.41 2.79 7,000 2,870 0.41 2.98 6,580 2,698 0.41 3.20
22 16 6,230 4,548 0.73 2.65 5,950 4,344 0.73 2.84 5,670 4,139 0.73 3.08
22 18 6,720 4,099 0.61 2.72 6,510 3,971 0.61 2.93 6,090 3,715 0.61 3.15
22 20 7,280 3,567 0.49 2.79 7,000 3,430 0.49 2.98 6,580 3,224 0.49 3.20
24 16 6,230 5,046 0.81 2.65 5,950 4,820 0.81 2.84 5,670 4,593 0.81 3.08
24 18 6,720 4,637 0.69 2.72 6,510 4,492 0.69 2.93 6,090 4,202 0.69 3.15
24 20 7,280 4,150 0.57 2.79 7,000 3,990 0.57 2.98 6,580 3,751 0.57 3.20
24 22 7,840 3,528 0.45 2.84 7,560 3,402 0.45 3.06 7,140 3,213 0.45 3.26
26 16 6,230 5,545 0.89 2.65 5,950 5,296 0.89 2.84 5,670 5,046 0.89 3.08
26 18 6,720 5,174 0.77 2.72 6,510 5,013 0.77 2.93 6,090 4,689 0.77 3.15
26 20 7,280 4,732 0.65 2.79 7,000 4,550 0.65 2.98 6,580 4,277 0.65 3.20
26 22 7,840 4,155 0.53 2.84 7,560 4,007 0.53 3.06 7,140 3,784 0.53 3.26
28 16 6,230 6,043 0.97 2.65 5,950 5,772 0.97 2.84 5,670 5,500 0.97 3.08
28 18 6,720 5,712 0.85 2.72 6,510 5,534 0.85 2.93 6,090 5,177 0.85 3.15
28 20 7,280 5,314 0.73 2.79 7,000 5,110 0.73 2.98 6,580 4,803 0.73 3.20
28 22 7,840 4,782 0.61 2.84 7,560 4,612 0.61 3.06 7,140 4,355 0.61 3.26
30 16 6,230 6,230 1.00 2.65 5,950 5,950 1.00 2.84 5,670 5,670 1.00 3.08
30 18 6,720 6,250 0.93 2.72 6,510 6,054 0.93 2.93 6,090 5,664 0.93 3.15
30 20 7,280 5,897 0.81 2.79 7,000 5,670 0.81 2.98 6,580 5,330 0.81 3.20
30 22 7,840 5,410 0.69 2.84 7,560 5,126 0.69 3.06 7,140 4,927 0.69 3.26
32 16 6,230 6,230 1.00 2.65 5,950 5,950 1.00 2.84 5,670 5,670 1.00 3.08
32 18 6,720 6,720 1.00 2.72 6,510 6,510 1.00 2.93 6,090 6,090 1.00 3.15
32 20 7,280 6,479 0.89 2.79 7,000 6,230 0.89 2.98 6,580 5,856 0.89 3.20
32 22 7,840 6,037 0.77 2.84 7,560 5,821 0.77 3.06 7,140 5,498 0.77 3.26
34 16 6,230 6,230 1.00 2.65 5,950 5,950 1.00 2.84 5,670 5,670 1.00 3.08
34 18 6,720 6,720 1.00 2.72 6,510 6,510 1.00 2.93 6,090 6,090 1.00 3.15
34 20 7,280 7,062 0.97 2.79 7,000 6,790 0.97 2.98 6,580 6,383 0.97 3.20
34 22 7,840 6,664 0.85 2.84 7,560 6,426 0.85 3.06 7,140 6,069 0.85 3.26
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
24
COOLING CAPACITY<5>
PCH-P3GAH
PCA-P3GA
Indoor Indoor 20 Outdoor intake air D.B.(°C) 30
25 CA SHC(W) SHF P.C.
Intake air Intake air
CA SHC(W) SHF P.C.
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C.
20 16 7,425 4,678 0.63 2.78 7,200 4,536 0.63 2.93 6,975 4,394 0.63 3.11
20 18 7,950 4,055 0.51 2.83 7,725 3,940 0.51 2.98 7,463 3,806 0.51 3.19
20 20 8,550 3,335 0.39 2.91 7,363 3,261 0.39 3.05 8,183 3,174 0.39 3.26
22 16 7,425 5,272 0.71 2.78 7,200 5,112 0.71 2.93 6,975 4,952 0.71 3.11
22 18 7,950 4,691 0.59 2.83 7,725 4,558 0.59 2.98 7,463 4,403 0.59 3.19
22 20 8,550 4,019 0.47 2.91 8,363 3,930 0.47 3.05 8,138 3,825 0.47 3.26
24 16 7,425 5,866 0.79 2.78 7,200 5,688 0.79 2.93 6,975 5,510 0.79 3.11
24 18 7,950 5,327 0.67 2.83 7,725 5,176 0.67 2.98 7,463 5,000 0.67 3.19
24 20 8,550 4,703 0.55 2.91 8,363 4,599 0.55 3.05 8,138 4,476 0.55 3.26
24 22 9,113 3,918 0.43 2.98 8,925 3,838 0.43 3.16 8,700 3,741 0.43 3.37
26 16 7,425 6,460 0.87 2.78 7,200 6,264 0.87 2.93 6,975 6,068 0.87 3.11
26 18 7,950 5,963 0.75 2.83 7,725 5,794 0.75 2.98 7,463 5,597 0.75 3.19
26 20 8,550 5,387 0.63 2.91 8,363 5,268 0.63 3.05 8,138 5,127 0.63 3.26
26 22 9,113 4,647 0.51 2.98 8,925 4,552 0.51 3.16 8,700 4,437 0.51 3.37
28 16 7,425 7,054 0.95 2.78 7,200 6,840 0.95 2.93 6,975 6,626 0.95 3.11
28 18 7,950 6,599 0.83 2.83 7,725 6,412 0.83 2.98 7,465 6,194 0.83 3.19
28 20 8,550 6,071 0.71 2.91 8,363 5,937 0.71 3.05 8,138 5,778 0.71 3.26
28 22 9,113 5,376 0.59 2.98 8,925 5,266 0.59 3.16 8,700 5,133 0.59 3.37
30 16 7,425 7,425 1.00 2.78 7,200 7,200 1.00 2.93 6,975 6,975 1.00 3.11
30 18 7,950 7,235 0.91 2.83 7,725 7,030 0.91 2.98 7,463 6,791 0.91 3.19
30 20 8,550 6,755 0.79 2.91 8,363 6,606 0.79 3.05 8,138 6,429 0.79 3.26
30 22 9,113 6,105 0.67 2.98 8,925 5,980 0.67 3.16 8,700 5,829 0.67 3.37
32 16 7,425 7,425 1.00 2.78 7,200 7,200 1.00 2.93 6,975 6,975 1.00 3.11
32 18 7,950 7,871 0.99 2.83 7,725 7,648 0.99 2.98 7,463 7,388 0.99 3.19
32 20 8,550 7,439 0.87 2.91 8,363 7,275 0.87 3.05 8,138 7,080 0.87 3.26
32 22 9,113 6,834 0.75 2.98 8,925 6,694 0.75 3.16 8,700 6,525 0.75 3.37
34 16 7,425 7,425 1.00 2.78 7,200 7,200 1.00 2.93 6,975 6,795 1.00 3.11
34 18 7,950 7,950 1.00 2.83 7,725 7,725 1.00 2.98 7,463 7,463 1.00 3.19
34 20 8,550 8,123 0.95 2.91 8,363 7,944 0.95 3.05 8,138 7,731 0.95 3.26
34 22 9,113 7,563 0.83 2.98 8,925 7,408 0.83 3.16 8,700 7,221 0.83 3.37
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
25
COOLING CAPACITY<6>
PCH-P3GAH
PCA-P3GA
Indoor Indoor 35 Outdoor intake air D.B.(°C) 45
Intake air Intake air 40 CA SHC(W) SHF P.C.
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 6,675 4,205 0.63 3.33 6,375 4,016 0.63 3.57 6,075 3,827 0.63 3.87
20 18 7,200 3,672 0.51 3.42 6,975 3,557 0.51 3.68 6,525 3,328 0.51 3.96
20 20 7,800 3,042 0.39 3.50 7,500 2,925 0.39 3.75 7,050 2,750 0.39 4.03
22 16 6,675 4,739 0.71 3.33 6,375 4,526 0.71 3.57 6,075 4,313 0.71 3.87
22 18 7,200 4,248 0.59 3.42 6,975 4,115 0.59 3.68 6,525 3,850 0.59 3.96
22 20 7,800 3,666 0.47 3.50 7,500 3,525 0.47 3.75 7,050 3,314 0.47 4.03
24 16 6,675 5,273 0.79 3.33 6,375 5,036 0.79 3.57 6,075 4,799 0.79 3.87
24 18 7,200 4,824 0.67 3.42 6,975 4,673 0.67 3.68 6,525 4,372 0.67 3.96
24 20 7,800 4,290 0.55 3.50 7,500 4,125 0.55 3.75 7,050 3,878 0.55 4.03
24 22 8,400 3,612 0.43 3.57 8,100 3,483 0.43 3.85 7,650 3,290 0.43 4.09
26 16 6,675 5,807 0.87 3.33 6,375 5,546 0.87 3.57 6,075 5,285 0.87 3.87
26 18 7,200 5,400 0.75 3.42 6,975 5,231 0.75 3.68 6,525 4,894 0.75 3.96
26 20 7,800 4,914 0.63 3.50 7,500 4,725 0.63 3.75 7,050 4,442 0.63 4.03
26 22 8,400 4,284 0.51 3.57 8,100 4,131 0.51 3.85 7,650 3,902 0.51 4.09
28 16 6,675 6,341 0.95 3.33 6,375 6,056 0.95 3.57 6,075 5,771 0.95 3.87
28 18 7,200 5,976 0.83 3.42 6,975 5,789 0.83 3.68 6,525 5,416 0.83 3.96
28 20 7,800 5,538 0.71 3.50 7,500 5,325 0.71 3.75 7,050 5,006 0.71 4.03
28 22 8,400 4,956 0.59 3.57 8,100 4,779 0.59 3.85 7,650 4,514 0.59 4.09
30 16 6,675 6,675 1.00 3.33 6,375 6,375 1.00 3.57 6,075 6,075 1.00 3.87
30 18 7,200 6,552 0.91 3.42 6,975 6,347 0.91 3.68 6,525 5,938 0.91 3.96
30 20 7,800 6,162 0.79 3.50 7,500 5,925 0.79 3.75 7,050 5,570 0.79 4.03
30 22 8,400 5,628 0.67 3.57 8,100 5,427 0.67 3.85 7,650 5,126 0.67 4.09
32 16 6,675 6,675 1.00 3.33 6,375 6,375 1.00 3.57 6,075 6,075 1.00 3.87
32 18 7,200 7,128 0.99 3.42 6,975 6,905 0.99 3.68 6,525 6,460 0.99 3.96
32 20 7,800 6,786 0.87 3.50 7,500 6,525 0.87 3.75 7,050 6,134 0.87 4.03
32 22 8,400 6,300 0.75 3.57 8,100 6,075 0.75 3.85 7,650 5,738 0.75 4.09
34 16 6,675 6,675 1.00 3.33 6,375 6,375 1.00 3.57 6,075 6,075 1.00 3.87
34 18 7,200 7,200 1.00 3.42 6,975 6,975 1.00 3.68 6,525 6,525 1.00 3.96
34 20 7,800 7,410 0.95 3.50 7,500 7,125 0.95 3.75 7,050 6,698 0.95 4.03
34 22 8,400 6,972 0.83 3.57 8,100 6,723 0.83 3.85 7,650 6,350 0.83 4.09
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
26
COOLING CAPACITY<7>
PCH-P4GAH
PCA-P4GA
Indoor Indoor 20 Outdoor intake air D.B.(°C) 30
Intake air Intake air 25 CA SHC(W) SHF P.C.
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 9,603 6,338 0.66 2.82 9,312 6,146 0.66 2.97 9,021 5,954 0.66 3.15
20 18 10,282 5,552 0.54 2.87 9,991 5,395 0.54 3.03 9,652 5,212 0.54 3.24
20 20 11,058 4,644 0.42 2.96 10,816 4,543 0.42 3.10 10,525 4,420 0.42 3.31
22 16 9,603 7,106 0.74 2.82 9,312 6,891 0.74 2.97 9,021 6,676 0.74 3.15
22 18 10,282 6,375 0.62 2.87 9,991 6,194 0.62 3.03 9,652 5,984 0.62 3.24
22 20 11,058 5,529 0.50 2.96 10,816 5,408 0.50 3.10 10,525 5,262 0.50 3.31
24 16 9,603 7,874 0.82 2.82 9,312 7,636 0.82 2.97 9,021 7,397 0.82 3.15
24 18 10,282 7,197 0.70 2.87 9,991 6,994 0.70 3.03 9,652 6,756 0.70 3.24
24 20 11,058 6,414 0.58 2.96 10,816 6,273 0.58 3.10 10,525 6,104 0.58 3.31
24 22 11,786 5,421 0.46 3.03 11,543 5,310 0.46 3.20 11,252 5,176 0.46 3.41
26 16 9,603 8,643 0.90 2.82 9,312 8,381 0.90 2.97 9,021 8,119 0.90 3.15
26 18 10,282 8,020 0.78 2.87 9,991 7,793 0.78 3.03 9,652 7,528 0.78 3.24
26 20 11,058 7,298 0.66 2.96 10,816 7,138 0.66 3.10 10,525 6,946 0.66 3.31
26 22 11,786 6,364 0.54 3.03 11,543 6,233 0.54 3.20 11,252 6,076 0.54 3.41
28 16 9,603 9,411 0.98 2.82 9,312 9,126 0.98 2.97 9,021 8,841 0.98 3.15
28 18 10,282 8,843 0.86 2.87 9,991 8,592 0.86 3.03 9,652 8,300 0.86 3.24
28 20 11,058 8,183 0.74 2.96 10,816 8,003 0.74 3.10 10,525 7,788 0.74 3.31
28 22 11,786 7,307 0.62 3.03 11,543 7,157 0.62 3.20 11,252 6,976 0.62 3.41
30 16 9,603 9,603 1.00 2.82 9,312 9,312 1.00 2.97 9,021 9,021 1.00 3.15
30 18 10,282 9,665 0.94 2.87 9,991 9,392 0.94 3.03 9,652 9,072 0.94 3.24
30 20 11,058 9,068 0.82 2.96 10,816 8,869 0.82 3.10 10,525 8,630 0.82 3.31
30 22 11,786 8,250 0.70 3.03 11,543 8,080 0.70 3.20 11,252 7,876 0.70 3.41
32 16 9,603 9,603 1.00 2.82 9,312 9,312 1.00 2.97 9,021 9,021 1.00 3.15
32 18 10,282 10,282 1.00 2.87 9,991 9,991 1.00 3.03 9,652 9,652 1.00 3.24
32 20 11,058 9,952 0.90 2.96 10,816 9,734 0.90 3.10 10,525 9,472 0.90 3.31
32 22 11,786 9,193 0.78 3.03 11,543 9,004 0.78 3.20 11,252 8,777 0.78 3.41
34 16 9,603 9,603 1.00 2.82 9,312 9,312 1.00 2.97 9,021 9,021 1.00 3.15
34 18 10,282 10,282 1.00 2.87 9,991 9,991 1.00 3.03 9,652 9,652 1.00 3.24
34 20 11,058 10,837 0.98 2.96 10,816 10,599 0.98 3.10 10,525 10,314 0.98 3.31
34 22 11,786 10,136 0.86 3.03 11,543 9,927 0.86 3.20 11,252 9,677 0.86 3.41
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
27
COOLING CAPACITY<8>
PCH-P4GAH
PCA-P4GA
Indoor Indoor 35 Outdoor intake air D.B.(°C) 45
40 CA SHC(W) SHF P.C.
Intake air Intake air
CA SHC(W) SHF P.C.
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C.
20 16 8,633 5,698 0.66 3.38 8,245 5,442 0.66 3.63 7,857 5,186 0.66 3.92
20 18 9,312 5,028 0.54 3.47 9,021 4,871 0.54 3.73 8,439 4,557 0.54 4.01
20 20 10,088 4,237 0.42 3.56 9,700 4,074 0.42 3.80 9,118 3,830 0.42 4.08
22 16 8,633 6,388 0.74 3.38 8,245 6,101 0.74 3.63 7,857 5,814 0.74 3.92
22 18 9,312 5,773 0.62 3.47 9,021 5,593 0.62 3.73 8,439 5,232 0.62 4.01
22 20 10,088 5,044 0.50 3.56 9,700 4,850 0.50 3.80 9,118 4,559 0.50 4.08
24 16 8,633 7,079 0.82 3.38 8,245 6,761 0.82 3.63 7,857 6,443 0.82 3.92
24 18 9,312 6,518 0.70 3.47 9,021 6,315 0.70 3.73 8,439 5,907 0.70 4.01
24 20 10,088 5,851 0.58 3.56 9,700 5,626 0.58 3.80 9,118 5,288 0.58 4.08
24 22 10,864 4,997 0.46 3.63 10,476 4,819 0.46 3.91 9,894 4,551 0.46 4.15
26 16 8,633 7,770 0.90 3.38 8,245 7,421 0.90 3.63 7,857 7,071 0.90 3.92
26 18 9,312 7,263 0.78 3.47 9,021 7,036 0.78 3.73 8,439 6,582 0.78 4.01
26 20 10,088 6,658 0.66 3.56 9,700 6,402 0.66 3.80 9,118 6,018 0.66 4.08
26 22 10,864 5,867 0.54 3.63 10,476 5,657 0.54 3.91 9,894 5,343 0.54 4.15
28 16 8,633 8,460 0.98 3.38 8,245 8,080 0.98 3.63 7,857 7,700 0.98 3.92
28 18 9,312 8,008 0.86 3.47 9,021 7,758 0.86 3.73 8,439 7,258 0.86 4.01
28 20 10,088 7,465 0.74 3.56 9,700 7,178 0.74 3.80 9,118 6,747 0.74 4.08
28 22 10,864 6,736 0.62 3.63 10,476 6,495 0.62 3.91 9,894 6,134 0.62 4.15
30 16 8,633 8,633 1.00 3.38 8,245 8,245 1.00 3.63 7,857 7,857 1.00 3.92
30 18 9,312 8,753 0.94 3.47 9,021 8,480 0.94 3.73 8,439 7,933 0.94 4.01
30 20 10,088 8,272 0.82 3.56 9,700 7,954 0.82 3.80 9,118 7,477 0.82 4.08
30 22 10,864 7,605 0.70 3.63 10,476 7,333 0.70 3.91 9,894 6,926 0.70 4.15
32 16 8,633 8,633 1.00 3.38 8,245 8,245 1.00 3.63 7,857 7,857 1.00 3.92
32 18 9,312 9,312 1.00 3.47 9,021 9,021 1.00 3.73 8,439 8,439 1.00 4.01
32 20 10,088 9,079 0.90 3.56 9,700 8,730 0.90 3.80 9,118 8,206 0.90 4.08
32 22 10,864 8,474 0.78 3.63 10,476 8,171 0.78 3.91 9,894 7,717 0.78 4.15
34 16 8,633 8,633 1.00 3.38 8,245 8,245 1.00 3.63 7,857 7,857 1.00 3.92
34 18 9,312 9,312 1.00 3.47 9,021 9,021 1.00 3.73 8,439 8,439 1.00 4.01
34 20 10,088 9,886 0.98 3.56 9,700 9,506 0.98 3.80 9,118 8,936 0.98 4.08
34 22 10,864 9,343 0.86 3.63 10,476 9,009 0.86 3.91 9,894 8,509 0.86 4.15
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
28
COOLING CAPACITY<9>
PCH-P5GAH
PCA-P5GA
Indoor Indoor 20 Outdoor intake air D.B.(°C) 30
Intake air Intake air 25 CA SHC(W) SHF P.C.
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 12,672 8,490 0.67 4.39 12,288 8,233 0.67 4.64 11,904 7,976 0.67 4.91
20 18 13,568 7,462 0.55 4.47 13,184 7,251 0.55 4.72 12,736 7,005 0.55 5.05
20 20 14,592 6,275 0.43 4.61 14,272 6,137 0.43 4.83 13,888 5,972 0.43 5.16
22 16 12,672 9,504 0.75 4.39 12,288 9,216 0.75 4.64 11,904 8,928 0.75 4.91
22 18 13,568 8,548 0.63 4.47 13,184 8,306 0.63 4.72 12,736 8,024 0.63 5.05
22 20 14,592 7,442 0.51 4.61 14,272 7,279 0.51 4.83 13,888 7,083 0.51 5.16
24 16 12,672 10,518 0.83 4.39 12,288 10,199 0.83 4.64 11,904 9,880 0.83 4.91
24 18 13,568 9,633 0.71 4.47 13,184 9,361 0.71 4.72 12,736 9,043 0.71 5.05
24 20 14,592 8,609 0.59 4.61 14,272 8,420 0.59 4.83 13,888 8,194 0.59 5.16
24 22 15,552 7,309 0.47 4.72 15,232 7,159 0.47 5.00 14,848 6,979 0.47 5.33
26 16 12,672 11,532 0.91 4.39 12,288 11,182 0.91 4.64 11,904 10,833 0.91 4.91
26 18 13,568 10,719 0.79 4.47 13,184 10,415 0.79 4.72 12,736 10,061 0.79 5.05
26 20 14,592 9,777 0.67 4.61 14,272 9,562 0.67 4.83 13,888 9,305 0.67 5.16
26 22 15,552 8,554 0.55 4.72 15,232 8,378 0.55 5.00 14,848 8,166 0.55 5.33
28 16 12,672 12,545 0.99 4.39 12,288 12,165 0.99 4.64 11,904 11,785 0.99 4.91
28 18 13,568 11,804 0.87 4.47 13,184 11,470 0.87 4.72 12,736 11,080 0.87 5.05
28 20 14,592 10,944 0.75 4.61 14,272 10,704 0.75 4.83 13,888 10,416 0.75 5.16
28 22 15,552 9,798 0.63 4.72 15,232 9,596 0.63 5.00 14,848 9,354 0.63 5.33
30 16 12,672 12,672 1.00 4.39 12,288 12,288 1.00 4.64 11,904 11,904 1.00 4.91
30 18 13,568 12,890 0.95 4.47 13,184 12,525 0.95 4.72 12,736 12,099 0.95 5.05
30 20 14,592 12,111 0.83 4.61 14,272 11,846 0.83 4.83 13,888 11,527 0.83 5.16
30 22 15,552 11,042 0.71 4.72 15,232 10,815 0.71 5.00 14,848 10,542 0.71 5.33
32 16 12,672 12,672 1.00 4.39 12,288 12,288 1.00 4.64 11,904 11,904 1.00 4.91
32 18 13,568 13,568 1.00 4.47 13,184 13,184 1.00 4.72 12,736 12,736 1.00 5.05
32 20 14,592 13,279 0.91 4.61 14,272 12,988 0.91 4.83 13,888 12,638 0.91 5.16
32 22 15,552 12,286 0.79 4.72 15,232 12,033 0.79 5.00 14,848 11,730 0.79 5.33
34 16 12,672 12,672 1.00 4.39 12,288 12,288 1.00 4.64 11,904 11,904 1.00 4.91
34 18 13,568 13,568 1.00 4.47 13,184 13,184 1.00 4.72 12,736 12,736 1.00 5.05
34 20 14,592 14,446 0.99 4.61 14,272 14,129 0.99 4.83 13,888 13,749 0.99 5.16
34 22 15,552 13,530 0.87 4.72 15,232 13,252 0.87 5.00 14,848 12,918 0.87 5.33
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
29
COOLING CAPACITY<10>
PCH-P5GAH
PCA-P5GA
Indoor Indoor 35 Outdoor intake air D.B.(°C) 45
40 CA SHC(W) SHF P.C.
Intake air Intake air
CA SHC(W) SHF P.C.
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C.
20 16 11,392 7,633 0.67 5.27 10,880 7,290 0.67 5.65 10,368 6,947 0.67 6.12
20 18 12,288 6,758 0.55 5.41 11,904 6,547 0.55 5.82 11,136 6,125 0.55 6.26
20 20 13,312 5,724 0.43 5.54 12,800 5,504 0.43 5.93 12,032 5,174 0.43 6.37
22 16 11,392 8,544 0.75 5.27 10,880 8,160 0.75 5.65 10,368 7,776 0.75 6.12
22 18 12,288 7,741 0.63 5.41 11,904 7,500 0.63 5.82 11,136 7,016 0.63 6.26
22 20 13,312 6,789 0.51 5.54 12,800 6,528 0.51 5.93 12,032 6,136 0.51 6.37
24 16 11,392 9,455 0.83 5.27 10,880 9,030 0.83 5.65 10,368 8,605 0.83 6.12
24 18 12,288 8,724 0.71 5.41 11,904 8,452 0.71 5.82 11,136 7,607 0.71 6.26
24 20 13,312 7,854 0.59 5.54 12,800 7,552 0.59 5.93 12,032 7,099 0.59 6.37
24 22 14,336 6,738 0.47 5.65 13,824 6,497 0.47 6.09 13,056 6,136 0.47 6.48
26 16 11,392 10,367 0.91 5.27 10,880 9,901 0.91 5.65 10,368 9,435 0.91 6.12
26 18 12,288 9,708 0.79 5.41 11,904 9,404 0.79 5.82 11,136 8,797 0.79 6.26
26 20 13,312 8,919 0.67 5.54 12,800 8,576 0.67 5.93 12,032 8,061 0.67 6.37
26 22 14,336 7,885 0.55 5.65 13,824 7,603 0.55 6.09 13,056 7,181 0.55 6.48
28 16 11,392 11,278 0.99 5.27 10,880 10,771 0.99 5.65 10,368 10,264 0.99 6.12
28 18 12,288 10,691 0.87 5.41 11,904 10,356 0.87 5.82 11,136 9,688 0.87 6.26
28 20 13,312 9,984 0.75 5.54 12,800 9,600 0.75 5.93 12,032 9,024 0.75 6.37
28 22 14,336 9,032 0.63 5.65 13,824 8,709 0.63 6.09 13,056 8,225 0.63 6.48
30 16 11,392 11,392 1.00 5.27 10,880 10,880 1.00 5.65 10,368 10,368 1.00 6.12
30 18 12,288 11,674 0.95 5.41 11,904 11,309 0.95 5.82 11,136 10,579 0.95 6.26
30 20 13,312 11,049 0.83 5.54 12,800 10,624 0.83 5.93 12,032 9,987 0.83 6.37
30 22 14,336 10,179 0.71 5.65 13,824 9,815 0.71 6.09 13,056 9,270 0.71 6.48
32 16 11,392 11,392 1.00 5.27 10,880 10,880 1.00 5.65 10,368 10,368 1.00 6.12
32 18 12,288 12,288 1.00 5.41 11,904 11,904 1.00 5.82 11,136 11,136 1.00 6.26
32 20 13,312 12,114 0.91 5.54 12,800 11,648 0.91 5.93 12,032 10,949 0.91 6.37
32 22 14,336 11,325 0.79 5.65 13,824 10,921 0.79 6.09 13,056 10,314 0.79 6.48
34 16 11,392 11,392 1.00 5.27 10,880 10,880 1.00 5.65 10,368 10,368 1.00 6.12
34 18 12,288 12,288 1.00 5.41 11,904 11,904 1.00 5.82 11,136 11,136 1.00 6.26
34 20 13,312 13,179 0.99 5.54 12,800 12,672 0.99 5.93 12,032 11,912 0.99 6.37
34 22 14,336 12,472 0.87 5.65 13,824 12,027 0.87 6.09 13,056 11,359 0.87 6.48
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
30
COOLING CAPACITY<11>
PCH-P6GAH
PCA-P6GA
Indoor Indoor 20 Outdoor intake air D.B.(°C) 30
Intake air Intake air 25 CA SHC(W) SHF P.C.
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 14,355 9,187 0.64 5.28 13,920 8,909 0.64 5.58 13,485 8,630 0.64 5.91
20 18 15,370 7,992 0.52 5.38 14,935 7,766 0.52 5.68 14,428 7,502 0.52 6.07
20 20 16,530 6,612 0.40 5.54 16,168 6,467 0.40 5.81 15,733 6,293 0.40 6.20
22 16 14,355 10,336 0.72 5.28 13,920 10,022 0.72 5.58 13,485 9,709 0.72 5.91
22 18 15,370 9,222 0.60 5.38 14,935 8,961 0.60 5.68 14,428 8,657 0.60 6.07
22 20 16,530 7,934 0.48 5.54 16,168 7,760 0.48 5.81 15,733 7,552 0.48 6.20
24 16 14,355 11,484 0.80 5.28 13,920 11,136 0.80 5.58 13,485 10,788 0.80 5.91
24 18 15,370 10,452 0.68 5.38 14,935 10,156 0.68 5.68 14,428 9,811 0.68 6.07
24 20 16,530 9,257 0.56 5.54 16,168 9,054 0.56 5.81 15,733 8,810 0.56 6.20
24 22 17,618 7,752 0.44 5.68 17,255 7,592 0.44 6.01 16,820 7,401 0.44 6.40
26 16 14,355 12,632 0.88 5.28 13,920 12,250 0.88 5.58 13,485 11,867 0.88 5.91
26 18 15,370 11,681 0.76 5.38 14,935 11,351 0.76 5.68 14,428 10,965 0.76 6.07
26 20 16,530 10,579 0.64 5.54 16,168 10,347 0.64 5.81 15,733 10,069 0.64 6.20
26 22 17,618 9,161 0.52 5.68 17,255 8,973 0.52 6.01 16,820 8,746 0.52 6.40
28 16 14,355 13,781 0.96 5.28 13,920 13,363 0.96 5.58 13,485 12,946 0.96 5.91
28 18 15,370 12,911 0.84 5.38 14,935 12,545 0.84 5.68 14,428 12,119 0.84 6.07
28 20 16,530 11,902 0.72 5.54 16,168 11,641 0.72 5.81 15,733 11,327 0.72 6.20
28 22 17,618 10,571 0.60 5.68 17,255 10,353 0.60 6.01 16,820 10,092 0.60 6.40
30 16 14,355 14,355 1.00 5.28 13,920 13,920 1.00 5.58 13,485 13,485 1.00 5.91
30 18 15,370 14,140 0.92 5.38 14,935 13,740 0.92 5.68 14,428 13,273 0.92 6.07
30 20 16,530 13,224 0.80 5.54 16,168 12,934 0.80 5.81 15,733 12,586 0.80 6.20
30 22 17,618 11,980 0.68 5.68 17,255 11,733 0.68 6.01 16,820 11,438 0.68 6.40
32 16 14,355 14,355 1.00 5.28 13,920 13,920 1.00 5.58 13,485 13,485 1.00 5.91
32 18 15,370 15,370 1.00 5.38 14,935 14,935 1.00 5.68 14,428 14,428 1.00 6.07
32 20 16,530 14,546 0.88 5.54 16,168 14,227 0.88 5.81 15,733 13,845 0.88 6.20
32 22 17,618 13,389 0.76 5.68 17,255 13,114 0.76 6.01 16,820 12,783 0.76 6.40
34 16 14,355 14,355 1.00 5.28 13,920 13,920 1.00 5.58 13,485 13,485 1.00 5.91
34 18 15,370 15,370 1.00 5.38 14,935 14,935 1.00 5.68 14,428 14,428 1.00 6.07
34 20 16,530 15,869 0.96 5.54 16,168 15,521 0.96 5.81 15,733 15,103 0.96 6.20
34 22 17,618 14,799 0.84 5.68 17,255 14,494 0.84 6.01 16,820 14,129 0.84 6.40
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
31
COOLING CAPACITY<12>
PCH-P6GAH
PCA-P6GA
Indoor Indoor 35 Outdoor intake air D.B.(°C) 45
Intake air Intake air 40 CA SHC(W) SHF P.C.
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 12,905 8,259 0.64 6.34 12,325 7,888 0.64 6.80 11,745 7,517 0.64 7.36
20 18 13,920 7,238 0.52 6.50 13,485 7,012 0.52 7.00 12,615 6,560 0.52 7.52
20 20 15,080 6,032 0.40 6.67 14,500 5,800 0.40 7.13 13,630 5,452 0.40 7.66
22 16 12,905 9,292 0.72 6.34 12,325 8,874 0.72 6.80 11,745 8,456 0.72 7.36
22 18 13,920 8,352 0.60 6.50 13,485 8,091 0.60 7.00 12,615 7,569 0.60 7.52
22 20 15,080 7,238 0.48 6.67 14,500 6,960 0.48 7.13 13,630 6,542 0.48 7.66
24 16 12,905 10,324 0.80 6.34 12,325 9,860 0.80 6.80 11,745 9,396 0.80 7.36
24 18 13,920 9,466 0.68 6.50 13,485 9,170 0.68 7.00 12,615 8,578 0.68 7.52
24 20 15,080 8,445 0.56 6.67 14,500 8,120 0.56 7.13 13,630 9,633 0.56 7.66
24 22 16,240 7,146 0.44 6.80 15,660 6,890 0.44 7.33 14,790 6,508 0.44 7.79
26 16 12,905 11,356 0.88 6.34 12,325 10,846 0.88 6.80 11,745 10,336 0.88 7.36
26 18 13,920 10,579 0.76 6.50 13,485 10,249 0.76 7.00 12,615 9,587 0.76 7.52
26 20 15,080 9,651 0.64 6.67 14,500 9,280 0.64 7.13 13,630 8,723 0.64 7.66
26 22 16,240 8,445 0.52 6.80 15,660 8,143 0.52 7.33 14,790 7,691 0.52 7.79
28 16 12,905 12,389 0.96 6.34 12,325 11,832 0.96 6.80 11,745 11,275 0.96 7.36
28 18 13,920 11,693 0.84 6.50 13,485 11,327 0.84 7.00 12,615 10,597 0.84 7.52
28 20 15,080 10,858 0.72 6.67 14,500 10,440 0.72 7.13 13,630 9,814 0.72 7.66
28 22 16,240 9,744 0.60 6.80 15,660 9,396 0.60 7.33 14,790 8,874 0.60 7.79
30 16 12,905 12,905 1.00 6.34 12,325 12,325 1.00 6.80 11,745 11,745 1.00 7.36
30 18 13,920 12,806 0.92 6.50 13,485 12,406 0.92 7.00 12,615 11,606 0.92 7.52
30 20 15,080 12,064 0.80 6.67 14,500 11,600 0.80 7.13 13,630 10,904 0.80 7.66
30 22 16,240 11,043 0.68 6.80 15,660 10,649 0.68 7.33 14,790 10,057 0.68 7.79
32 16 12,905 12,905 1.00 6.34 12,325 12,325 1.00 6.80 11,745 11,745 1.00 7.36
32 18 13,920 13,920 1.00 6.50 13,485 13,485 1.00 7.00 12,615 12,615 1.00 7.52
32 20 15,080 13,270 0.88 6.67 14,500 12,760 0.88 7.13 13,630 11,994 0.88 7.66
32 22 16,240 12,342 0.76 6.80 15,660 11,902 0.76 7.33 14,790 11,240 0.76 7.79
34 16 12,905 12,905 1.00 6.34 12,325 12,325 1.00 6.80 11,745 11,745 1.00 7.36
34 18 13,920 13,920 1.00 6.50 13,485 13,485 1.00 7.00 12,615 12,615 1.00 7.52
34 20 15,080 14,477 0.96 6.67 14,500 13,920 0.96 7.13 13,630 13,085 0.96 7.66
34 22 16,240 13,642 0.84 6.80 15,660 13,154 0.84 7.33 14,790 12,424 0.84 7.79
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
32
COOLING CAPACITY<13>
PCH-P2GAH1
PCA-P2GA1
Indoor Indoor 20 Outdoor intake air D.B.(°C) 30
Intake air Intake air 25 CA SHC(W) SHF P.C.
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 5,346 3,315 0.62 1.92 5,184 3,214 0.62 2.03 5,022 3,114 0.62 2.15
20 18 5,724 2,862 0.50 1.96 5,562 2,781 0.50 2.06 5,373 2,687 0.50 2.21
20 20 6,156 2,339 0.38 2.02 6,021 2,288 0.38 2.11 5,859 2,226 0.38 2.26
22 16 5,346 3,742 0.70 1.92 5,184 3,629 0.70 2.03 5,022 3,515 0.70 2.15
22 18 5,724 3,320 0.58 1.96 5,562 3,226 0.58 2.06 5,373 3,116 0.58 2.21
22 20 6,156 2,832 0.46 2.02 6,021 2,770 0.46 2.11 5,859 2,695 0.46 2.26
24 16 5,346 4,170 0.78 1.92 5,184 4,044 0.78 2.03 5,022 3,917 0.78 2.15
24 18 5,724 3,778 0.66 1.96 5,562 3,671 0.66 2.06 5,373 3,546 0.66 2.21
24 20 6,156 3,324 0.54 2.02 6,021 3,251 0.54 2.11 5,859 3,164 0.54 2.26
26 16 5,346 4,598 0.86 1.92 5,184 4,458 0.86 2.03 5,022 4,319 0.86 2.15
26 18 5,724 4,236 0.74 1.96 5,562 4,116 0.74 2.06 5,373 3,976 0.74 2.21
26 20 6,156 3,817 0.62 2.02 6,021 3,733 0.62 2.11 5,859 3,633 0.62 2.26
28 16 5,346 5,025 0.94 1.92 5,184 4,873 0.94 2.03 5,022 4,721 0.94 2.15
28 18 5,724 4,694 0.82 1.96 5,562 4,561 0.82 2.06 5,373 4,406 0.82 2.21
28 20 6,156 4,309 0.70 2.02 6,021 4,215 0.70 2.11 5,859 4,101 0.70 2.26
30 16 5,346 5,346 1.00 1.92 5,184 5,184 1.00 2.03 5,022 5,022 1.00 2.15
30 18 5,724 5,152 0.90 1.96 5,562 5,006 0.90 2.06 5,373 4,836 0.90 2.21
30 20 6,156 4,802 0.78 2.02 6,021 4,696 0.78 2.11 5,859 4,570 0.78 2.26
32 16 5,346 5,346 1.00 1.92 5,184 5,184 1.00 2.03 5,022 5,022 1.00 2.15
32 18 5,724 5,610 0.98 1.96 5,562 5,451 0.98 2.06 5,373 5,266 0.98 2.21
32 20 6,156 5,294 0.86 2.02 6,021 5,178 0.86 2.11 5,859 5,039 0.86 2.26
34 16 5,346 5,346 1.00 1.92 5,184 5,184 1.00 2.03 5,022 5,022 1.00 2.15
34 18 5,724 5,724 1.00 1.96 5,562 5,562 1.00 2.06 5,373 5,373 1.00 2.21
34 20 6,156 5,787 0.94 2.02 6,021 5,660 0.94 2.11 5,859 5,507 0.94 2.26
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
33
COOLING CAPACITY<14>
PCH-P2GAH1
PCA-P2GA1
Indoor Indoor 35 Outdoor intake air D.B.(°C) 45
Intake air Intake air 40 CA SHC(W) SHF P.C.
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 4,806 2,980 0.62 2.30 4,590 2,846 0.62 2.47 4,374 2,712 0.62 2.68
20 18 5,184 2,592 0.50 2.36 5,022 2,511 0.50 2.54 4,698 2,349 0.50 2.74
20 20 5,616 2,134 0.38 2.42 5,400 2,052 0.38 2.59 5,076 1,929 0.38 2.78
22 16 4,806 3,364 0.70 2.30 4,590 3,213 0.70 2.47 4,374 3,062 0.70 2.68
22 18 5,184 3,007 0.58 2.36 5,022 2,913 0.58 2.54 4,698 2,725 0.58 2.74
22 20 5,616 2,583 0.46 2.42 5,400 2,484 0.46 2.59 5,076 2,335 0.46 2.78
24 16 4,806 3,749 0.78 2.30 4,590 3,580 0.78 2.47 4,374 3,412 0.78 2.68
24 18 5,184 3,421 0.66 2.36 5,022 3,315 0.66 2.54 4,698 3,101 0.66 2.74
24 20 5,616 3,033 0.54 2.42 5,400 2,916 0.54 2.59 5,076 2,741 0.54 2.78
26 16 4,806 4,133 0.86 2.30 4,590 3,947 0.86 2.47 4,374 3,762 0.86 2.68
26 18 5,184 3,836 0.74 2.36 5,022 3,716 0.74 2.54 4,698 3,477 0.74 2.74
26 20 5,616 3,482 0.62 2.42 5,400 3,348 0.62 2.59 5,076 3,147 0.62 2.78
28 16 4,806 4,518 0.94 2.30 4,590 4,315 0.94 2.47 4,374 4,112 0.94 2.68
28 18 5,184 4,251 0.82 2.36 5,022 4,118 0.82 2.54 4,698 3,852 0.82 2.74
28 20 5,616 3,931 0.70 2.42 5,400 3,780 0.70 2.59 5,076 3,553 0.70 2.78
30 16 4,806 4,806 1.00 2.30 4,590 4,590 1.00 2.47 4,374 4,374 1.00 2.68
30 18 5,184 4,666 0.90 2.36 5,022 4,520 0.90 2.54 4,698 4,228 0.90 2.74
30 20 5,616 4,380 0.78 2.42 5,400 4,212 0.78 2.59 5,076 3,959 0.78 2.78
32 16 4,806 4,806 1.00 2.30 4,590 4,590 1.00 2.47 4,374 4,374 1.00 2.68
32 18 5,184 5,080 0.98 2.36 5,022 4,922 0.98 2.54 4,698 4,604 0.98 2.74
32 20 5,616 4,830 0.86 2.42 5,400 4,644 0.86 2.59 5,076 4,365 0.86 2.78
34 16 4,806 4,806 1.00 2.30 4,590 4,590 1.00 2.47 4,374 4,374 1.00 2.68
34 18 5,184 5,184 1.00 2.36 5,022 5,022 1.00 2.54 4,698 4,698 1.00 2.74
34 20 5,616 5,279 0.94 2.42 5,400 5,076 0.94 2.59 5,076 4,771 0.94 2.78
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
34
COOLING CAPACITY<15>
PCH-P2.5GAH1
PCA-P2.5GA1
Indoor Indoor 20 Outdoor intake air D.B.(°C) 30
Intake air Intake air 25 CA SHC(W) SHF P.C.
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 6,584 4,279 0.65 2.12 6,384 4,150 0.65 2.24 6,185 4,020 0.65 2.37
20 18 7,049 3,736 0.53 2.16 6,850 3,630 0.53 2.28 6,617 3,507 0.53 2.44
20 20 7,581 3,108 0.41 2.23 7,415 3,040 0.41 2.33 7,215 2,958 0.41 2.49
22 16 6,584 4,806 0.73 2.12 6,384 4,660 0.73 2.24 6,185 4,515 0.73 2.37
22 18 7,049 4,300 0.61 2.16 6,850 4,178 0.61 2.28 6,617 4,036 0.61 2.44
22 20 7,581 3,715 0.49 2.23 7,415 3,633 0.49 2.33 7,215 3,535 0.49 2.49
24 16 6,584 5,333 0.81 2.12 6,384 5,171 0.81 2.24 6,185 5,009 0.81 2.37
24 18 7,049 4,864 0.69 2.16 6,850 4,726 0.69 2.28 6,617 4,566 0.69 2.44
24 20 7,581 4,321 0.57 2.23 7,415 4,226 0.57 2.33 7,215 4,113 0.57 2.49
26 16 6,584 5,859 0.89 2.12 6,384 5,682 0.89 2.24 6,185 5,504 0.89 2.37
26 18 7,049 5,428 0.77 2.16 6,850 5,274 0.77 2.28 6,617 5,095 0.77 2.44
26 20 7,581 4,928 0.65 2.23 7,415 4,820 0.65 2.33 7,215 4,690 0.65 2.49
28 16 6,584 6,386 0.97 2.12 6,384 6,192 0.97 2.24 6,185 5,999 0.97 2.37
28 18 7,049 5,992 0.85 2.16 6,850 5,822 0.85 2.28 6,617 5,624 0.85 2.44
28 20 7,581 5,534 0.73 2.23 7,415 5,413 0.73 2.33 7,215 5,267 0.73 2.49
30 16 6,584 6,584 1.00 2.12 6,384 6,384 1.00 2.24 6,185 6,185 1.00 2.37
30 18 7,049 6,556 0.93 2.16 6,850 6,370 0.93 2.28 6,617 6,154 0.93 2.44
30 20 7,581 6,141 0.81 2.23 7,415 6,006 0.81 2.33 7,215 5,844 0.81 2.49
32 16 6,584 6,584 1.00 2.12 6,384 6,384 1.00 2.24 6,185 6,185 1.00 2.37
32 18 7,049 7,049 1.00 2.16 6,850 6,850 1.00 2.28 6,617 6,617 1.00 2.44
32 20 7,581 6,747 0.89 2.23 7,415 6,599 0.89 2.33 7,215 6,422 0.89 2.49
34 16 6,584 6,584 1.00 2.12 6,384 6,384 1.00 2.24 6,185 6,185 1.00 2.37
34 18 7,049 7,049 1.00 2.16 6,850 6,850 1.00 2.28 6,617 6,617 1.00 2.44
34 20 7,581 7,354 0.97 2.23 7,415 7,192 0.97 2.33 7,215 6,999 0.97 2.49
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
35
COOLING CAPACITY<16>
PCH-P2.5GAH1
PCA-P2.5GA1
Indoor Indoor 35 Outdoor intake air D.B.(°C) 45
Intake air Intake air 40 CA SHC(W) SHF P.C.
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 5,919 3,847 0.65 2.54 5,653 3,674 0.65 2.73 5,387 3,501 0.65 2.95
20 18 6,384 3,384 0.53 2.61 6,185 3,278 0.53 2.81 5,786 3,066 0.53 3.02
20 20 6,916 2,836 0.41 2.68 6,650 2,727 0.41 2.86 6,251 2,563 0.41 3.07
22 16 5,919 4,321 0.73 2.54 5,653 4,126 0.73 2.73 5,387 3,932 0.73 2.95
22 18 6,384 3,894 0.61 2.61 6,185 3,773 0.61 2.81 5,786 3,529 0.61 3.02
22 20 6,916 3,389 0.49 2.68 6,650 3,259 0.49 2.86 6,251 3,063 0.49 3.07
24 16 5,919 4,794 0.81 2.54 5,653 4,579 0.81 2.73 5,387 4,363 0.81 2.95
24 18 6,384 4,405 0.69 2.61 6,185 4,267 0.69 2.81 5,786 3,992 0.69 3.02
24 20 6,916 3,942 0.57 2.68 6,650 3,791 0.57 2.86 6,251 3,563 0.57 3.07
26 16 5,919 5,267 0.89 2.54 5,653 5,031 0.89 2.73 5,387 4,794 0.89 2.95
26 18 6,384 4,916 0.77 2.61 6,185 4,762 0.77 2.81 5,786 4,455 0.77 3.02
26 20 6,916 4,495 0.65 2.68 6,650 4,323 0.65 2.86 6,251 4,063 0.65 3.07
28 16 5,919 5,741 0.97 2.54 5,653 5,483 0.97 2.73 5,387 5,225 0.97 2.95
28 18 6,384 5,426 0.85 2.61 6,185 5,257 0.85 2.81 5,786 4,918 0.85 3.02
28 20 6,916 5,049 0.73 2.68 6,650 4,855 0.73 2.86 6,251 4,563 0.73 3.07
30 16 5,919 5,919 1.00 2.54 5,653 5,653 1.00 2.73 5,387 5,387 1.00 2.95
30 18 6,384 5,937 0.93 2.61 6,185 5,752 0.93 2.81 5,786 5,381 0.93 3.02
30 20 6,916 5,602 0.81 2.68 6,650 5,387 0.81 2.86 6,251 5,063 0.81 3.07
32 16 5,919 5,919 1.00 2.54 5,653 5,653 1.00 2.73 5,387 5,387 1.00 2.95
32 18 6,384 6,384 1.00 2.61 6,185 6,185 1.00 2.81 5,786 5,786 1.00 3.02
32 20 6,916 6,155 0.89 2.68 6,650 5,919 0.89 2.86 6,251 5,563 0.89 3.07
34 16 5,919 5,919 1.00 2.54 5,653 5,653 1.00 2.73 5,387 5,387 1.00 2.95
34 18 6,384 6,384 1.00 2.61 6,185 6,185 1.00 2.81 5,786 5,786 1.00 3.02
34 20 6,916 6,709 0.97 2.68 6,650 6,451 0.97 2.86 6,251 6,063 0.97 3.07
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
36
COOLING CAPACITY<17>
PCH-P3GAH1
PCA-P3GA1
Indoor Indoor 20 Outdoor intake air D.B.(°C) 30
25 CA SHC(W) SHF P.C.
Intake air Intake air
CA SHC(W) SHF P.C.
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C.
20 16 7,425 4,678 0.63 2.72 7,200 4,536 0.63 2.87 6,975 4,394 0.63 3.04
20 18 7,950 4,055 0.51 2.77 7,725 3,940 0.51 2.92 7,463 3,806 0.51 3.13
20 20 8,550 3,335 0.39 2.86 8,363 3,261 0.39 2.99 8,138 3,174 0.39 3.20
22 16 7,425 5,272 0.71 2.72 7,200 5,112 0.71 2.87 6,975 4,952 0.71 3.04
22 18 7,950 4,691 0.59 2.77 7,725 4,558 0.59 2.92 7,463 4,403 0.59 3.13
22 20 8,550 4,019 0.47 2.86 8,363 3,930 0.47 2.99 8,183 3,825 0.47 3.20
24 16 7,425 5,866 0.79 2.72 7,200 5,688 0.79 2.87 6,975 5,510 0.79 3.04
24 18 7,950 5,327 0.67 2.77 7,725 5,176 0.67 2.92 7,463 5,000 0.67 3.13
24 20 8,550 4,703 0.55 2.86 8,363 4,599 0.55 2.99 8,183 4,476 0.55 3.20
26 16 7,425 6,460 0.87 2.72 7,200 6,264 0.87 2.87 6,975 6,068 0.87 3.04
26 18 7,950 5,963 0.75 2.77 7,725 5,794 0.75 2.92 7,463 5,597 0.75 3.13
26 20 8,550 5,387 0.63 2.86 8,363 5,268 0.63 2.99 8,183 5,127 0.63 3.20
28 16 7,425 7,054 0.95 2.72 7,200 6,840 0.95 2.87 6,975 6,626 0.95 3.04
28 18 7,950 6,599 0.83 2.77 7,725 6,412 0.83 2.92 7,463 6,194 0.83 3.13
28 20 8,550 6,071 0.71 2.86 8,363 5,937 0.71 2.99 8,183 5,778 0.71 3.20
30 16 7,425 7,425 1.00 2.72 7,200 7,200 1.00 2.87 6,975 6,975 1.00 3.04
30 18 7,950 7,235 0.91 2.77 7,725 7,030 0.91 2.92 7,463 6,791 0.91 3.13
30 20 8,550 6,755 0.79 2.86 8,363 6,606 0.79 2.99 8,183 6,429 0.79 3.20
32 16 7,425 7,425 1.00 2.72 7,200 7,200 1.00 2.87 6,975 6,975 1.00 3.04
32 18 7,950 7,871 0.99 2.77 7,725 7,648 0.99 2.92 7,463 7,388 0.99 3.13
32 20 8,550 7,439 0.87 2.86 8,363 7,275 0.87 2.99 8,183 7,080 0.87 3.20
34 16 7,425 7,425 1.00 2.72 7,200 7,200 1.00 2.87 6,975 6,975 1.00 3.04
34 18 7,950 7,950 1.00 2.77 7,725 7,725 1.00 2.92 7,463 7,463 1.00 3.13
34 20 8,550 8,123 0.95 2.86 8,363 7,944 0.95 2.99 8,183 7,731 0.95 3.20
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
37
COOLING CAPACITY<18>
PCH-P3GAH1
PCA-P3GA1
Indoor Indoor 35 Outdoor intake air D.B.(°C) 45
Intake air Intake air 40 CA SHC(W) SHF P.C.
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 6,675 4,205 0.63 3.26 6,375 4,016 0.63 3.50 6,075 3,827 0.63 3.79
20 18 7,200 3,672 0.51 3.35 6,975 3,557 0.51 3.60 6,525 3,328 0.51 3.88
20 20 7,800 3,042 0.39 3.43 7,500 2,925 0.39 3.67 7,050 2,750 0.39 3.94
22 16 6,675 4,739 0.71 3.26 6,375 4,526 0.71 3.50 6,075 4,313 0.71 3.79
22 18 7,200 4,248 0.59 3.35 6,975 4,115 0.59 3.60 6,525 3,850 0.59 3.88
22 20 7,800 3,666 0.47 3.43 7,500 3,525 0.47 3.67 7,050 3,314 0.47 3.94
24 16 6,675 5,273 0.79 3.26 6,375 5,036 0.79 3.50 6,075 4,799 0.79 3.79
24 18 7,200 4,824 0.67 3.35 6,975 4,673 0.67 3.60 6,525 4,372 0.67 3.88
24 20 7,800 4,290 0.55 3.43 7,500 4,125 0.55 3.67 7,050 3,878 0.55 3.94
26 16 6,675 5,807 0.87 3.26 6,375 5,546 0.87 3.50 6,075 5,285 0.87 3.79
26 18 7,200 5,400 0.75 3.35 6,975 5,231 0.75 3.60 6,525 4,894 0.75 3.88
26 20 7,800 4,914 0.63 3.43 7,500 4,725 0.63 3.67 7,050 4,442 0.63 3.94
28 16 6,675 6,341 0.95 3.26 6,375 6,056 0.95 3.50 6,075 5,771 0.95 3.79
28 18 7,200 5,976 0.83 3.35 6,975 5,789 0.83 3.60 6,525 5,416 0.83 3.88
28 20 7,800 5,538 0.71 3.43 7,500 5,325 0.71 3.67 7,050 5,006 0.71 3.94
30 16 6,675 6,675 1.00 3.26 6,375 6,375 1.00 3.50 6,075 6,075 1.00 3.79
30 18 7,200 6,552 0.91 3.35 6,975 6,347 0.91 3.60 6,525 5,938 0.91 3.88
30 20 7,800 6,162 0.79 3.43 7,500 5,925 0.79 3.67 7,050 5,570 0.79 3.94
32 16 6,675 6,675 1.00 3.26 6,375 6,375 1.00 3.50 6,075 6,075 1.00 3.79
32 18 7,200 7,128 0.99 3.35 6,975 6,905 0.99 3.60 6,525 6,460 0.99 3.88
32 20 7,800 6,786 0.87 3.43 7,500 6,525 0.87 3.67 7,050 6,134 0.87 3.94
34 16 6,675 6,675 1.00 3.26 6,375 6,375 1.00 3.50 6,075 6,075 1.00 3.79
34 18 7,200 7,200 1.00 3.35 6,975 6,975 1.00 3.60 6,525 6,525 1.00 3.88
34 20 7,800 7,410 0.95 3.43 7,500 7,125 0.95 3.67 7,050 6,698 0.95 3.94
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
38
COOLING CAPACITY<19>
PCH-P4GAH1
PCA-P4GA1
Indoor Indoor 20 Outdoor intake air D.B.(°C) 30
Intake air Intake air 25 CA SHC(W) SHF P.C.
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 9,603 6,338 0.66 2.91 9,312 6,146 0.66 3.08 9,021 5,954 0.66 3.26
20 18 10,282 5,552 0.54 2.97 9,991 5,395 0.54 3.13 9,652 5,212 0.54 3.35
20 20 11,058 4,644 0.42 3.06 10,816 4,543 0.42 3.20 10,525 4,420 0.42 3.42
22 16 9,603 7,106 0.74 2.91 9,312 6,891 0.74 3.08 9,021 6,676 0.74 3.26
22 18 10,282 6,375 0.62 2.97 9,991 6,194 0.62 3.13 9,652 5,984 0.62 3.35
22 20 11,058 5,529 0.50 3.06 10,816 5,408 0.50 3.20 10,525 5,262 0.50 3.42
24 16 9,603 7,874 0.82 2.91 9,312 7,636 0.82 3.08 9,021 7,397 0.82 3.26
24 18 10,282 7,197 0.70 2.97 9,991 6,994 0.70 3.13 9,652 6,756 0.70 3.35
24 20 11,058 6,414 0.58 3.06 10,816 6,273 0.58 3.20 10,525 6,104 0.58 3.42
26 16 9,603 8,643 0.90 2.91 9,312 8,381 0.90 3.08 9,021 8,119 0.90 3.26
26 18 10,282 8,020 0.78 2.97 9,991 7,793 0.78 3.13 9,652 7,528 0.78 3.35
26 20 11,058 7,298 0.66 3.06 10,816 7,138 0.66 3.20 10,525 6,946 0.66 3.42
28 16 9,603 9,411 0.98 2.91 9,312 9,126 0.98 3.08 9,021 8,841 0.98 3.26
28 18 10,282 8,843 0.86 2.97 9,991 8,592 0.86 3.13 9,652 8,300 0.86 3.35
28 20 11,058 8,183 0.74 3.06 10,816 8,003 0.74 3.20 10,525 7,788 0.74 3.42
30 16 9,603 9,603 1.00 2.91 9,312 9,312 1.00 3.08 9,021 9,021 1.00 3.26
30 18 10,282 9,665 0.94 2.97 9,991 9,392 0.94 3.13 9,652 9,072 0.94 3.35
30 20 11,058 9,068 0.82 3.06 10,816 8,869 0.82 3.20 10,525 8,630 0.82 3.42
32 16 9,603 9,603 1.00 2.91 9,312 9,312 1.00 3.08 9,021 9,021 1.00 3.26
32 18 10,282 10,282 1.00 2.97 9,991 9,991 1.00 3.13 9,652 9,652 1.00 3.35
32 20 11,058 9,952 0.90 3.06 10,816 9,734 0.90 3.20 10,525 9,472 0.90 3.42
34 16 9,603 9,603 1.00 2.91 9,312 9,312 1.00 3.08 9,021 9,021 1.00 3.26
34 18 10,282 10,282 1.00 2.97 9,991 9,991 1.00 3.13 9,652 9,652 1.00 3.35
34 20 11,058 10,837 0.98 3.06 10,816 10,599 0.98 3.20 10,525 10,314 0.98 3.42
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
39
COOLING CAPACITY<20>
PCH-P4GAH1
PCA-P4GA1
Indoor Indoor 35 Outdoor intake air D.B.(°C) 45
Intake air Intake air 40 CA SHC(W) SHF P.C.
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 8,633 5,698 0.66 3.49 8,245 5,442 0.66 3.75 7,857 5,186 0.66 4.60
20 18 9,312 5,028 0.54 3.59 9,021 4,871 0.54 3.86 8,439 4,557 0.54 4.15
20 20 10,088 4,237 0.42 3.68 9,700 4,074 0.42 3.93 9,118 3,830 0.42 4.22
22 16 8,633 6,388 0.74 3.49 8,245 6,101 0.74 3.75 7,857 5,814 0.74 4.60
22 18 9,312 5,773 0.62 3.59 9,021 5,593 0.62 3.86 8,439 5,232 0.62 4.15
22 20 10,088 5,044 0.50 3.68 9,700 4,850 0.50 3.93 9,118 4,559 0.50 4.22
24 16 8,633 7,079 0.82 3.49 8,245 6,761 0.82 3.75 7,857 6,443 0.82 4.60
24 18 9,312 6,518 0.70 3.59 9,021 6,315 0.70 3.86 8,439 5,907 0.70 4.15
24 20 10,088 5,851 0.58 3.68 9,700 5,626 0.58 3.93 9,118 5,288 0.58 4.22
26 16 8,633 7,770 0.90 3.49 8,245 7,421 0.90 3.75 7,857 7,071 0.90 4.60
26 18 9,312 7,263 0.78 3.59 9,021 7,036 0.78 3.86 8,439 6,582 0.78 4.15
26 20 10,088 6,658 0.66 3.68 9,700 6,402 0.66 3.93 9,118 6,018 0.66 4.22
28 16 8,633 8,460 0.98 3.49 8,245 8,080 0.98 3.75 7,857 7,700 0.98 4.60
28 18 9,312 8,008 0.86 3.59 9,021 7,758 0.86 3.86 8,439 7,258 0.86 4.15
28 20 10,088 7,465 0.74 3.68 9,700 7,178 0.74 3.93 9,118 6,747 0.74 4.22
30 16 8,633 8,633 1.00 3.49 8,245 8,245 1.00 3.75 7,857 7,857 1.00 4.60
30 18 9,312 8,753 0.94 3.59 9,021 8,480 0.94 3.86 8,439 7,933 0.94 4.15
30 20 10,088 8,272 0.82 3.68 9,700 7,954 0.82 3.93 9,118 7,477 0.82 4.22
32 16 8,633 8,633 1.00 3.49 8,245 8,245 1.00 3.75 7,857 7,857 1.00 4.60
32 18 9,312 9,312 1.00 3.59 9,021 9,021 1.00 3.86 8,439 8,439 1.00 4.15
32 20 10,088 9,079 0.90 3.68 9,700 8,730 0.90 3.93 9,118 8,206 0.90 4.22
34 16 8,633 8,633 1.00 3.49 8,245 8,245 1.00 3.75 7,857 7,857 1.00 4.60
34 18 9,312 9,312 1.00 3.59 9,021 9,021 1.00 3.86 8,439 8,439 1.00 4.15
34 20 10,088 9,886 0.98 3.68 9,700 9,506 0.98 3.93 9,118 8,936 0.98 4.22
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
40
COOLING CAPACITY<21>
PCH-P5GAH1
PCA-P5GA1
Indoor Indoor 20 Outdoor intake air D.B.(°C) 30
Intake air Intake air 25 CA SHC(W) SHF P.C.
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 12,276 8,225 0.67 3.95 11,904 7,976 0.67 4.17 11,532 7,726 0.67 4.42
20 18 13,144 7,229 0.55 4.03 12,772 7,025 0.55 4.25 12,338 6,786 0.55 4.54
20 20 14,136 6,078 0.43 4.15 13,826 5,945 0.43 4.35 13,454 5,785 0.43 4.64
22 16 12,276 9,207 0.75 3.95 11,904 8,928 0.75 4.17 11,532 8,649 0.75 4.42
22 18 13,144 8,281 0.63 4.03 12,772 8,046 0.63 4.25 12,338 7,773 0.63 4.54
22 20 14,136 7,209 0.51 4.15 13,826 7,051 0.51 4.35 13,454 6,862 0.51 4.64
24 16 12,276 10,189 0.83 3.95 11,904 9,880 0.83 4.17 11,532 9,572 0.83 4.42
24 18 13,144 9,332 0.71 4.03 12,772 9,068 0.71 4.25 12,338 8,760 0.71 4.54
24 20 14,136 8,340 0.59 4.15 13,826 8,157 0.59 4.35 13,454 7,938 0.59 4.64
26 16 12,276 11,171 0.91 3.95 11,904 10,833 0.91 4.17 11,532 10,494 0.91 4.42
26 18 13,144 10,384 0.79 4.03 12,772 10,090 0.79 4.25 12,338 9,747 0.79 4.54
26 20 14,136 9,471 0.67 4.15 13,826 9,263 0.67 4.35 13,454 9,014 0.67 4.64
28 16 12,276 12,153 0.99 3.95 11,904 11,785 0.99 4.17 11,532 11,417 0.99 4.42
28 18 13,144 11,435 0.87 4.03 12,772 11,112 0.87 4.25 12,338 10,734 0.87 4.54
28 20 14,136 10,602 0.75 4.15 13,826 10,370 0.75 4.35 13,454 10,091 0.75 4.64
30 16 12,276 12,276 1.00 3.95 11,904 11,904 1.00 4.17 11,532 11,532 1.00 4.42
30 18 13,144 12,487 0.95 4.03 12,772 12,133 0.95 4.25 12,338 11,721 0.95 4.54
30 20 14,136 11,733 0.83 4.15 13,826 11,476 0.83 4.35 13,454 11,167 0.83 4.64
32 16 12,276 12,276 1.00 3.95 11,904 11,904 1.00 4.17 11,532 11,532 1.00 4.42
32 18 13,144 13,144 1.00 4.03 12,772 12,772 1.00 4.25 12,338 12,338 1.00 4.54
32 20 14,136 12,864 0.91 4.15 13,826 12,582 0.91 4.35 13,454 12,243 0.91 4.64
34 16 12,276 12,276 1.00 3.95 11,904 11,904 1.00 4.17 11,532 11,532 1.00 4.42
34 18 13,144 13,144 1.00 4.03 12,772 12,772 1.00 4.25 12,338 12,338 1.00 4.54
34 20 14,136 13,995 0.99 4.15 13,826 13,688 0.99 4.35 13,454 13,319 0.99 4.64
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
41
COOLING CAPACITY<22>
PCH-P5GAH1
PCA-P5GA1
Indoor Indoor 35 Outdoor intake air D.B.(°C) 45
Intake air Intake air 40 CA SHC(W) SHF P.C.
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 11,036 7,394 0.67 4.74 10,540 7,062 0.67 5.09 10,044 6,729 0.67 5.51
20 18 11,904 6,547 0.55 4.87 11,532 6,343 0.55 5.24 10,788 5,933 0.55 5.63
20 20 12,896 5,545 0.43 4.99 12,400 5,332 0.43 5.34 11,656 5,012 0.43 5.73
22 16 11,036 8,277 0.75 4.74 10,540 7,905 0.75 5.09 10,044 7,533 0.75 5.51
22 18 11,904 7,500 0.63 4.87 11,532 7,265 0.63 5.24 10,788 6,796 0.63 5.63
22 20 12,896 6,577 0.51 4.99 12,400 6,324 0.51 5.34 11,656 5,945 0.51 5.73
24 16 11,036 9,160 0.83 4.74 10,540 8,748 0.83 5.09 10,044 8,337 0.83 5.51
24 18 11,904 8,452 0.71 4.87 11,532 8,188 0.71 5.24 10,788 7,659 0.71 5.63
24 20 12,896 7,609 0.59 4.99 12,400 7,316 0.59 5.34 11,656 6,877 0.59 5.73
26 16 11,036 10,043 0.91 4.74 10,540 9,591 0.91 5.09 10,044 9,140 0.91 5.51
26 18 11,904 9,404 0.79 4.87 11,532 9,110 0.79 5.24 10,788 8,523 0.79 5.63
26 20 12,896 8,640 0.67 4.99 12,400 8,308 0.67 5.34 11,656 7,810 0.67 5.73
28 16 11,036 10,926 0.99 4.74 10,540 10,435 0.99 5.09 10,044 9,944 0.99 5.51
28 18 11,904 10,356 0.87 4.87 11,532 10,033 0.87 5.24 10,788 9,386 0.87 5.63
28 20 12,896 9,672 0.75 4.99 12,400 9,300 0.75 5.34 11,656 8,742 0.75 5.73
30 16 11,036 11,036 1.00 4.74 10,540 10,540 1.00 5.09 10,044 10,044 1.00 5.51
30 18 11,904 11,309 0.95 4.87 11,532 10,955 0.95 5.24 10,788 10,249 0.95 5.63
30 20 12,896 10,704 0.83 4.99 12,400 10,292 0.83 5.34 11,656 9,674 0.83 5.73
32 16 11,036 11,036 1.00 4.74 10,540 10,540 1.00 5.09 10,044 10,044 1.00 5.51
32 18 11,904 11,904 1.00 4.87 11,532 11,532 1.00 5.24 10,788 10,788 1.00 5.63
32 20 12,896 11,735 0.91 4.99 12,400 11,284 0.91 5.34 11,656 10,607 0.91 5.73
34 16 11,036 11,036 1.00 4.74 10,540 10,540 1.00 5.09 10,044 10,044 1.00 5.51
34 18 11,904 11,904 1.00 4.87 11,532 11,532 1.00 5.24 10,788 10,788 1.00 5.63
34 20 12,896 12,767 0.99 4.99 12,400 12,276 0.99 5.34 11,656 11,539 0.99 5.73
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
42
COOLING CAPACITY<23>
PCH-P6GAH1
PCA-P6GA1
Indoor Indoor 20 Outdoor intake air D.B.(°C) 30
Intake air Intake air 25 CA SHC(W) SHF P.C.
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 14,157 9,060 0.64 4.75 13,728 8,786 0.64 5.02 13,299 8,511 0.64 5.32
20 18 15,158 7,882 0.52 4.84 14,729 7,659 0.52 5.11 14,229 7,399 0.52 5.46
20 20 16,302 6,521 0.40 4.99 15,945 6,378 0.40 5.23 15,516 6,206 0.40 5.58
22 16 14,157 10,193 0.72 4.75 13,728 9,884 0.72 5.02 13,299 9,579 0.72 5.32
22 18 15,158 9,095 0.60 4.84 14,729 8,837 0.60 5.11 14,229 8,537 0.60 5.46
22 20 16,302 7,825 0.48 4.99 15,945 7,653 0.48 5.23 15,516 7,447 0.48 5.58
24 16 14,157 11,326 0.80 4.75 13,728 10,982 0.80 5.02 13,299 10,639 0.80 5.32
24 18 15,158 10,307 0.68 4.84 14,729 10,016 0.68 5.11 14,229 9,675 0.68 5.46
24 20 16,302 9,129 0.56 4.99 15,945 8,929 0.56 5.23 15,516 8,689 0.56 5.58
26 16 14,157 12,458 0.88 4.75 13,728 12,081 0.88 5.02 13,299 11,703 0.88 5.32
26 18 15,158 11,520 0.76 4.84 14,729 11,194 0.76 5.11 14,229 10,814 0.76 5.46
26 20 16,302 10,433 0.64 4.99 15,945 10,204 0.64 5.23 15,516 9,930 0.64 5.58
28 16 14,157 13,591 0.96 4.75 13,728 13,179 0.96 5.02 13,299 12,767 0.96 5.32
28 18 15,158 12,733 0.84 4.84 14,729 12,372 0.84 5.11 14,229 11,952 0.84 5.46
28 20 16,302 11,737 0.72 4.99 15,945 11,480 0.72 5.23 15,516 11,171 0.72 5.58
30 16 14,157 14,157 1.00 4.75 13,728 13,728 1.00 5.02 13,299 13,299 1.00 5.32
30 18 15,158 13,945 0.92 4.84 14,729 13,551 0.92 5.11 14,229 13,090 0.92 5.46
30 20 16,302 13,042 0.80 4.99 15,945 12,756 0.80 5.23 15,516 12,412 0.80 5.58
32 16 14,157 14,157 1.00 4.75 13,728 13,728 1.00 5.02 13,299 13,299 1.00 5.32
32 18 15,158 15,158 1.00 4.84 14,729 14,729 1.00 5.11 14,229 14,229 1.00 5.46
32 20 16,302 14,346 0.88 4.99 15,945 14,031 0.88 5.23 15,516 13,654 0.88 5.58
34 16 14,157 14,157 1.00 4.75 13,728 13,728 1.00 5.02 13,299 13,299 1.00 5.32
34 18 15,158 15,158 1.00 4.84 14,729 14,729 1.00 5.11 14,229 14,229 1.00 5.46
34 20 16,302 15,650 0.96 4.99 15,945 15,307 0.96 5.23 15,516 14,895 0.96 5.58
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
43
COOLING CAPACITY<24>
PCH-P6GAH1
PCA-P6GA1
Indoor Indoor 35 Outdoor intake air D.B.(°C) 45
Intake air Intake air 40 CA SHC(W) SHF P.C.
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 12,727 8,145 0.64 5.70 12,155 7,779 0.64 6.12 11,583 7,413 0.64 6.62
20 18 13,728 7,139 0.52 5.85 13,299 6,915 0.52 6.30 12,441 6,469 0.52 6.77
20 20 14,872 5,949 0.40 6.00 14,300 5,720 0.40 6.42 13,442 5,377 0.40 6.89
22 16 12,727 9,163 0.72 5.70 12,155 8,752 0.72 6.12 11,583 8,340 0.72 6.62
22 18 13,728 8,237 0.60 5.85 13,299 7,979 0.60 6.30 12,441 7,465 0.60 6.77
22 20 14,872 7,139 0.48 6.00 14,300 6,864 0.48 6.42 13,442 6,452 0.48 6.89
24 16 12,727 10,182 0.80 5.70 12,155 9,724 0.80 6.12 11,583 9,266 0.80 6.62
24 18 13,728 9,335 0.68 5.85 13,299 9,043 0.68 6.30 12,441 8,460 0.68 6.77
24 20 14,872 8,328 0.56 6.00 14,300 8,008 0.56 6.42 13,442 7,528 0.56 6.89
26 16 12,727 11,200 0.88 5.70 12,155 10,696 0.88 6.12 11,583 10,193 0.88 6.62
26 18 13,728 10,433 0.76 5.85 13,299 10,107 0.76 6.30 12,441 9,455 0.76 6.77
26 20 14,872 9,518 0.64 6.00 14,300 9,152 0.64 6.42 13,442 8,603 0.64 6.89
28 16 12,727 12,218 0.96 5.70 12,155 11,669 0.96 6.12 11,583 11,120 0.96 6.62
28 18 13,728 11,532 0.84 5.85 13,299 11,171 0.84 6.30 12,441 10,450 0.84 6.77
28 20 14,872 10,708 0.72 6.00 14,300 10,296 0.72 6.42 13,442 9,678 0.72 6.89
30 16 12,727 12,727 1.00 5.70 12,155 12,155 1.00 6.12 11,583 11,583 1.00 6.62
30 18 13,728 12,630 0.92 5.85 13,299 12,235 0.92 6.30 12,441 11,446 0.92 6.77
30 20 14,872 11,898 0.80 6.00 14,300 11,440 0.80 6.42 13,442 10,754 0.80 6.89
32 16 12,727 12,727 1.00 5.70 12,155 12,155 1.00 6.12 11,583 11,583 1.00 6.62
32 18 13,728 13,728 1.00 5.85 13,299 13,299 1.00 6.30 12,441 12,441 1.00 6.77
32 20 14,872 13,087 0.88 6.00 14,300 12,584 0.88 6.42 13,442 11,829 0.88 6.89
34 16 12,727 12,727 1.00 5.70 12,155 12,155 1.00 6.12 11,583 11,583 1.00 6.62
34 18 13,728 13,728 1.00 5.85 13,299 13,299 1.00 6.30 12,441 12,441 1.00 6.77
34 20 14,872 14,277 0.96 6.00 14,300 13,728 0.96 6.42 13,442 12,904 0.96 6.89
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
44
Cooling capacity correction factors
Service Ref. Refrigerant piping length (one way)
PCH-P2GAH 5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
PCA-P2GA 0.984 — —
PCH-P2GAH1 1.00 0.993 0.980 0.978 0.969 0.961 0.956 0.948
PCA-P2GA1 0.968 0.920 0.910
1.00 0.989 0.980 0.970 0.960 0.950 0.940 0.930 0.886 0.874
PCH-P2.5GAH 0.968 0.920 0.910
PCA-P2.5GA 1.00 0.981 0.955 0.952 0.940 0.925 0.913 0.900 0.886 0.874
PCH-P2.5GAH1 0.855 0.840
PCA-P2.5GA1 1.00 0.989 0.970 0.960 0.950 0.940 0.930
PCH-P3GAH 1.00 0.981 0.952 0.940 0.925 0.913 0.900
PCA-P3GA
PCH-P3GAH1 1.00 0.975 0.935 0.918 0.900 0.884 0.869
PCA-P3GA1
PCH-P4GAH
PCA-P4GA
PCH-P4GAH1
PCA-P4GA1
PCH-P5GAH
PCA-P5GA
PCH-P5GAH1
PCA-P5GA1
PCH-P6GAH
PCA-P6GA
PCH-P6GAH1
PCA-P6GA1
CAPACITY (RATIO) Cooling INDOOR W.B.(°C)
1.4 22
1.2 20
1.0 18
0.8 16
TOTAL INPUT (RATIO) 1.2 INDOOR W.B.(°C)
1.0
22
0.8 20
0.6 18
0.4 16
-5 0 10 20 30 40 46
OUTDOOR D.B.(°C)
45
2.) HEATING CAPACITY
Indoor Outdoor intake air W.B.(°C)
Intake
Service Ref. -10 -5 0 5 10 15
air CA P.C. CA P.C. CA P.C. CA P.C.
PCH-P2GAH D.B.(°C) 4,520 1.74 CA P.C. CA P.C. 7,467 2.67 8,319 2.88
PCA-P2GA 4,323 1.87 7,205 2.88 8,024 3.10
15 4,159 1.58 4,192 2.03 5,044 2.00 6,616 2.40 6,943 3.08 7,729 3.32
5,037 1.74 8,322 2.67 9,271 2.88
20 3,996 1.71 4,818 1.87 4,782 2.16 6,386 2.59 8,030 2.88 8,943 3.10
4,672 2.03 7,738 3.08 8,614 3.32
25 3,865 1.82 6,417 2.37 4,585 2.35 6,026 2.75 10,602 3.65 11,811 3.94
6,138 2.56 10,230 3.94 11,393 4.23
PCH-P2.5GAH 15 4,636 1.58 5,952 2.77 5,621 2.00 7373 2.40 9,858 4.22 10,974 4.54
PCA-P2.5GA 20 4,453 1.71 7,349 2.36 12,141 3.63 13,526 3.92
25 4,307 1.82 7,029 2.54 5,329 2.16 7,118 2.59 11,715 3.92 13,046 4.21
6,816 2.76 11,289 4.19 12,567 4.52
11,040 3.71 5,110 2.35 6,716 2.75 18,240 5.71 20,320 6.17
10,560 4.00 17,600 6.17 19,600 6.62
PCH-P3GAH 15 5,906 2.15 10,240 4.34 7,161 2.74 9,393 3.29 16,960 6.60 18,880 7.11
PCA-P3GA 20 5,673 2.34 11,592 4.34 19,152 6.67 21,336 7.20
25 5,487 2.48 11,088 4.67 6,789 2.96 9,068 3.54 18,480 7.20 20,580 7.74
10,752 5.07 17,808 7.70 19,824 8.30
6,510 3.21 8,556 3.76
PCH-P4GAH 15 6,763 2.14 8,201 2.72 10,757 3.27
PCA-P4GA 20 6,497 2.32
25 6,284 2.47 7,775 2.94 10,384 3.52
7,455 3.19 9,798 3.74
PCH-P5GAH 15 10,160 3.37 12,320 4.28 16,160 5.14
PCA-P5GA 20 9,760 3.65
25 9,440 3.88 11,680 4.63 15,600 5.54
11,200 5.02 14,720 5.88
PCH-P6GAH 15 10,668 3.94 12,936 5.00 16,968 6.00
PCA-P6GA 20 10,248 4.27
25 9,912 4.54 12,264 5.40 16,380 6.47
11,760 5.87 15,456 6.87
Indoor Outdoor intake air W.B.(°C)
Intake
Service Ref. -10 -5 0 5 10 15
air CA P.C. CA P.C. CA P.C. CA P.C.
PCH-P2GAH1 D.B.(°C) 4,313 1.56 CA P.C. CA P.C. 7,125 2.40 7,938 2.59
PCA-P2GA1 4,125 1.68 6,875 2.59 7,656 2.78
15 3,969 1.42 4,000 1.82 4,813 1.80 6,313 2.16 6,625 2.77 7,375 2.99
PCH-P2.5GAH1 4,589 1.72 7,581 2.65 8,446 2.86
PCA-P2.5GA1 20 3,813 1.54 4,389 1.86 4,563 1.94 6,094 2.33 7,315 2.86 8,146 3.07
4,256 2.01 7,049 3.06 7,847 3.30
PCH-P3GAH1 25 3,688 1.63 6,348 2.28 4,375 2.11 5,750 2.47 10,488 3.50 11,684 3.78
PCA-P3GA1 6,072 2.45 10,120 3.78 11,270 4.06
15 4,223 1.56 5,888 2.66 5,121 1.99 6,717 2.39 9,752 4.04 10,856 4.36
PCH-P4GAH1 7,349 2.49 12,141 3.83 13,526 4.14
PCA-P4GA1 20 4,057 1.70 7,029 2.68 4,855 2.15 6,484 2.57 11,715 4.14 13,046 4.44
6,816 2.91 11,289 4.42 12,567 4.77
PCH-P5GAH1 25 3,924 1.80 10,281 3.34 4,655 2.33 6,118 2.73 16,986 5.14 18,923 5.55
PCA-P5GA1 9,834 3.60 16,390 5.55 18,253 5.96
15 5,842 2.07 9,536 3.91 7,084 2.63 9,292 3.15 15,794 5.94 17,582 6.40
PCH-P6GAH1 11,799 4.08 19,494 6.27 21,717 6.77
PCA-P6GA1 20 5,612 2.24 11,286 4.39 6,716 2.84 8,970 3.40 18,810 6.77 20,948 7.27
10,944 4.77 18,126 7.24 20,178 7.81
25 5,428 2.38 6,440 3.08 8,464 3.61
15 6,763 2.26 8,201 2.87 10,757 3.45
20 6,497 2.45 7,775 3.10 10,384 3.72
25 6,284 2.60 7,455 3.37 9,798 3.94
15 9,462 3.03 11,473 3.86 15,049 4.63
20 9,089 3.29 10,877 4.16 14,528 4.99
25 8,791 3.50 10,430 4.52 13,708 5.29
15 10,859 3.70 13,167 4.70 17,271 5.64
20 10,431 4.01 12,483 5.08 16,673 6.08
25 10,089 4.26 11,970 5.52 15,732 6.46
Notes CA : Capacity (W)
P.C. : Power consumption (kW)
46
Heating capacity correction factors
Service Ref. Refrigerant piping length (one way)
PCH-P2GAH 5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
PCA-P2GA 0.995 — —
PCH-P2GAH1 1.00 0.998 0.995 0.993 0.990 0.988 0.985 0.983 0.980 0.978
PCA-P2GA1 0.995 0.980 0.978
1.00 0.998 0.995 0.993 0.990 0.988 0.985 0.983 0.980 0.978
PCH-P2.5GAH 0.995 0.980 0.978
PCA-P2.5GA 1.00 0.998 0.995 0.993 0.990 0.988 0.985 0.983 0.980 0.978
PCH-P2.5GAH1
PCA-P2.5GA1 1.00 0.998 0.993 0.990 0.988 0.985 0.983
PCH-P3GAH 1.00 0.998 0.993 0.990 0.988 0.985 0.983
PCA-P3GA
PCH-P3GAH1 1.00 0.998 0.993 0.990 0.988 0.985 0.983
PCA-P3GA1
PCH-P4GAH
PCA-P4GA
PCH-P4GAH1
PCA-P4GA1
PCH-P5GAH
PCA-P5GA
PCH-P5GAH1
PCA-P5GA1
PCH-P6GAH
PCA-P6GA
PCH-P6GAH1
PCA-P6GA1
Heating
Correcting the capacity line influenced by frosting.
Not correcting the capacity line influenced by frosting.
1.4
15
CAPACITY (RATIO) 20 INDOOR D.B. (°C)
1.2 25
1.0
0.8
0.6
0.4
1.4
TOTAL INPUT (RATIO) INDOOR D.B. (°C)
25
1.2 20
15
1.0
0.8
0.6
0.4
-12 -10 -5 0 5 10 15
OUTDOOR W.B. (°C)
47
2. ELECTRICAL DATA
2.1. Heat pump type
Rating Conditions (ISO T1)
Indoor……220V 50Hz Single phase
Outdoor… 220V 50Hz Single phase / 380V 50Hz 3 phase
Service Indoor With heater PCH-P2GAH PCH-P2.5GAH PCH-P3GAH
Ref. unit Without heater PCA-P2GA PCA-P2.5GA PCA-P3GA
PUH-P2.5VGA PUH-P2.5YGA PUH-P3VGA PUH-P3YGA
Outdoor unit PUH-P2VGA PUH-P2YGA
Mode Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating
Capacity (W) 5,400 6,450 5,400 6,450 6,900 7,200 6,900 7,200 7,400 9,100 7,400 9,100
2.48 (7,630) 2.48 (7,630) 2.69 (8,960) 2.69 (8,960) 3.43 (10,860) 3.43 (10,860)
Total Input (kW) (In + Out) Heater) 0.08 0.08 0.11 0.11 0.11 0.11
(In + Out + 2.56 0.38 2.56 0.51 2.60 0.51 2.60 0.51 3.61 0.51 3.61
(3.74) 4.01 (3.74) 11.96 (4.36) 4.31 (4.36) 15.55 (5.37) 5.54 (5.37)
Outdoor Indoor Input (kW) 0.08 0.08 0.11 0.11 0.11 0.11
<1.18> <1.18> <1.76> <1.76> <1.76> <1.76>
Current (A) 0.38 0.38 0.38 0.51 0.51 0.51 0.51
<5.36> <5.36> <8.00> <8.00> <8.00> <8.00>
Current (A) 11.13
11.50 4.14 11.54 4.16 16.40 5.84
Starting current (A) 68 68 28 28 70 70 29 29 84 84 38 38
w ( ) shows the total rating.
< > shows the only booster heater rating.
Indoor……230V 50Hz Single phase
Outdoor… 230V 50Hz Single phase / 400V 50Hz 3 phase
Service Indoor With heater PCH-P2GAH PCH-P2.5GAH PCH-P3GAH
Ref. unit Without heater PCA-P2GA PCA-P2.5GA PCA-P3GA
PUH-P2.5VGA PUH-P2.5YGA PUH-P3VGA PUH-P3YGA
Outdoor unit PUH-P2VGA PUH-P2YGA
Mode Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating
5,450 6,950 7,450
Capacity (W) 5,450 6,500 2.53 6,500 6,950 7,050 2.73 7,050 7,450 9,200 3.45 9,200
2.53 (7,790) 0.09 (7,790) 2.73 (9,180) 0.12 (9,180) 3.45 (11,300) 0.12 (11,300)
Total Input (kW) (In + Out) 0.09 0.41 0.12 0.53 0.12 0.53
(In + Out + Heater) 2.62 3.91 2.62 0.53 2.32 4.19 2.32 0.53 3.63 5.46 3.63
(3.91) (3.91) (4.59) (4.59) (5.56) (5.56)
Outdoor Indoor Input (kW) 0.09 0.09 0.12 0.12 0.12 0.12
<1.29> <1.29> <1.93> <1.93> <1.93> <1.93>
Current (A) 0.41 0.41 0.41 0.53 0.53 0.53 0.53
<5.61> <5.61> <8.39> <8.39> <8.39> <8.39>
Current (A) 11.05 11.45 4.06 11.82 9.86 4.07 15.08 15.89 5.75
Starting current (A) 71 71 29 29 74 52 31 31 89 89 40 40
w ( ) shows the total rating.
< > shows the only booster heater rating.
Indoor……240V 50Hz Single phase
Outdoor… 240V 50Hz Single phase / 415V 50Hz 3 phase
Service Indoor With heater PCH-P2GAH PCH-P2.5GAH PCH-P3GAH
Ref. unit Without heater PCA-P2GA PCA-P2.5GA PCA-P3GA
PUH-P2.5VGA PUH-P2.5YGA PUH-P3VGA PUH-P3YGA
Outdoor unit PUH-P2VGA PUH-P2YGA
Mode Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating
5,500 7,000 7,500 7,500
Capacity (W) 5,500 6,550 2.58 6,550 7,000 7,300 2.76 7,300 3.47 9,300 3.47 9,300
2.58 (7,950) 0.10 (7,950) 2.76 (9,400) 0.13 (9,400) 0.13 (11,400) 0.13 (11,400)
Total Input (kW) (In + Out) Heater) 0.10 0.43 0.13 0.55 0.55 0.55
(In + Out + 2.67 2.67 0.55 2.71 2.71 3.65 3.65
(4.07) (4.07) (4.81) (4.81) (5.75) (5.75)
Outdoor Indoor Input (kW) 0.10 0.10 0.13 0.13 0.13 0.13
<1.40> <1.40> <2.10> <2.10> <2.10> <2.10>
Current (A) 0.43 0.43 0.43 0.55 0.55 0.55 0.55
<5.83> <5.83> <8.75> <8.75> <8.75> <8.75>
Current (A) 11.11 11.51 3.88 4.02 11.78 11.55 4.11 4.03 14.64 15.43 5.46 5.76
Starting current (A) 74 74 30 30 77 77 32 32 93 93 41 41
w ( ) shows the total rating.
< > shows the only booster heater rating.
48
Rating Conditions (ISO T1)
Indoor……220V 50Hz Single phase
Outdoor… 380V 50Hz 3 phase
Service Indoor With heater PCH-P4GAH PCH-P5GAH PCH-P6GAH
Ref. unit Without heater PCA-P4GA PCA-P5GA PCA-P6GA
PUH-P5YGA PUH-P6YGA
Outdoor unit PUH-P4YGA
Mode Cooling Heating Cooling Heating Cooling Heating
Capacity (W) 9,500 10,550 12,600 15,800 14,400 16,400
3.47 (12,820) 5.43 (18,320) 6.48 (18,920)
Total Input (kW) (In + Out) Heater) 0.68 0.20 0.20
(In + Out + 3.65 5.64 6.61
(5.92) (8.16) (9.13)
Outdoor Indoor Input (kW) 0.14 0.20 0.20
<2.27> <2.52> <2.52>
Current (A) 0.38 0.68 0.96 0.96 0.96 0.96
<10.32> <11.46> <11.46>
Current (A) 5.55 5.86 8.92 9.29 10.72 10.94
Starting current (A) 41 41 72 72 77 77
w ( ) shows the total rating.
< > shows the only booster heater rating.
Indoor……230V 50Hz Single phase
Outdoor… 400V 50Hz 3 phase
Service Indoor With heater PCH-P4GAH PCH-P5GAH PCH-P6GAH
Ref. unit Without heater PCA-P4GA PCA-P5GA PCA-P6GA
PUH-P5YGA PUH-P6YGA
Outdoor unit PUH-P4YGA
Mode Cooling Heating Cooling Heating Cooling Heating
Capacity (W) 9,600 10,600 12,700 15,800 14,450 16,600
3.50 (13,080) 5.46 (18,660) 6.54 (19,360)
Total Input (kW) (In + Out) 0.15 0.22 0.22
(In + Out + Heater) 3.68 1.01 5.68 1.01 6.64
(6.16) (8.44) (9.40)
Outdoor Indoor Input (kW) 0.15 0.22 0.22
<2.48> <2.76> <2.76>
Current (A) 0.69 0.69 1.01 1.01
<10.78> <12.00> <12.00>
Current (A) 5.48 5.78 8.59 8.95 10.36 10.53
Starting current (A) 43 43 76 76 81 81
w ( ) shows the total rating.
< > shows the only booster heater rating.
Indoor……240V 50Hz Single phase
Outdoor… 415V 50Hz 3 phase
Service Indoor With heater PCH-P4GAH PCH-P5GAH PCH-P6GAH
Ref. unit Without heater PCA-P4GA PCA-P5GA PCA-P6GA
PUH-P5YGA PUH-P6YGA
Outdoor unit PUH-P4YGA
Mode Cooling Heating Cooling Heating Cooling Heating
Capacity (W) 9,700 10,650 12,800 16,000 14,500 16,800
3.52 (13,350) 5.49 (19,000) 6.60 (19,800)
Total Input (kW) (In + Out) 0.16 0.24 0.24
(In + Out + Heater) 3.70 1.06 5.71 1.06 6.67
(6.40) (8.71) (9.67)
Outdoor Indoor Input (kW) 0.16 0.24 0.24
<2.70> <3.00> <3.00>
Current (A) 0.70 0.70 1.06 1.06
<11.25> <12.50> <12.50>
Current (A) 5.49 5.79 8.39 8.74 10.17 10.28
Starting current (A) 45 45 79 79 84 84
w ( ) shows the total rating.
< > shows the only booster heater rating.
49
2.2. Cooling only type
Rating Conditions (ISO T1)
Indoor……220V 50Hz Single phase
Outdoor… 220V 50Hz Single phase / 380V 50Hz 3 phase
Indoor unit PCA-P2GA PCA-P2.5GA PCA-P3GA
Service Ref. PU-P2.5VGA
PU-P3VGA PU-P3YGA
Outdoor unit PU-P2VGA
Mode Cooling Cooling Cooling Cooling
Capacity (W) 5,400 6,900 7,400 7,400
Total Input (kW) (In + Out) 2.48 2.69 3.43 3.43
Outdoor Indoor Input (kW) 0.08 0.11 0.11 0.11
Current (A) 0.38 0.51 0.51 0.51
Current (A) 11.13 11.96 15.55 5.54
Starting current (A) 68 70 84 38
Indoor……230V 50Hz Single phase
Outdoor… 230V 50Hz Single phase / 400V 50Hz 3 phase
Indoor unit PCA-P2GA PCA-P2.5GA PCA-P3GA
Service Ref. PU-P2VGA PU-P2.5VGA
PU-P3VGA PU-P3YGA
Outdoor unit Cooling Cooling
Mode 5,450 6,950 Cooling Cooling
Capacity (W) 2.53 2.73
Total Input (kW) (In + Out) 0.09 0.12 7,450 7,450
0.41 0.53
Input (kW) 11.05 11.82 3.45 3.45
Current (A)
Current (A)Outdoor Indoor 71 74 0.12 0.12
Starting current (A)
0.53 0.53
15.08 5.46
89 40
Indoor……240V 50Hz Single phase
Outdoor… 240V 50Hz Single phase / 415V 50Hz 3 phase
Indoor unit PCA-P2GA PCA-P2.5GA PCA-P3GA
Service Ref. PU-P2VGA PU-P2.5VGA
PU-P3VGA PU-P3YGA
Outdoor unit Cooling Cooling
Mode 5,500 7,000 Cooling Cooling
Capacity (W) 2.58 2.76
Total Input (kW) (In + Out) 0.10 0.13 7,500 7,500
0.43 0.55
Input (kW) 11.11 11.78 3.47 3.47
Current (A)
Current (A)Outdoor Indoor 74 77 0.13 0.13
Starting current (A)
0.55 0.55
14.64 5.46
93 41
50
Rating Conditions (ISO T1)
Indoor……220V 50Hz Single phase
Outdoor… 380V 50Hz 3 phase
Indoor unitOutdoor IndoorPCA-P4GAPCA-P5GAPCA-P6GA
Service Ref. PU-P4YGA PU-P5YGA PU-P6YGA
Outdoor unit Cooling Cooling Cooling
Mode 9,500 12,600 14,400
Capacity (W) 3.47
Total Input (kW) (In + Out) 0.68 5.43 6.48
0.38 0.20 0.20
Input (kW) 5.55 0.96 0.96
Current (A) 8.92 10.72
Current (A) 41 72 77
Starting current (A)
Indoor……230V 50Hz Single phase
Outdoor… 400V 50Hz 3 phase
Indoor unitOutdoor IndoorPCA-P4GAPCA-P5GAPCA-P6GA
Service Ref. PU-P4YGA PU-P5YGA PU-P6YGA
Outdoor unit Cooling Cooling Cooling
Mode 9,600 12,700 14,450
Capacity (W) 3.50
Total Input (kW) (In + Out) 0.15 5.46 6.54
0.69 0.22 0.22
Input (kW) 5.48 1.01 1.01
Current (A) 8.59 10.36
Current (A) 43 76 81
Starting current (A)
Indoor……240V 50Hz Single phase
Outdoor… 415V 50Hz 3 phase
Indoor unitOutdoor IndoorPCA-P4GAPCA-P5GAPCA-P6GA
Service Ref. PU-P4YGA PU-P5YGA PU-P6YGA
Outdoor unit Cooling Cooling Cooling
Mode 9,700 12,800 14,500
Capacity (W) 3.52
Total Input (kW) (In + Out) 0.16 5.49 6.60
0.70 0.24 0.24
Input (kW) 5.49 1.06 1.06
Current (A) 8.39 10.17
Current (A) 45 79 84
Starting current (A)
51
2.3. Heat pump type
Rating Conditions (ISO T1)
Indoor……220V 50Hz Single phase
Outdoor… 220V 50Hz Singel phase / 380V 50Hz 3 phase
Service Indoor With heater PCH-P2GAH1 PCH-P2.5GAH1 PCH-P3GAH1
Ref. unit Without heater PCA-P2GA1 PCA-P2.5GA1 PCA-P3GA1
Outdoor unit PUH-P2VGAA.UK PUH-P2YGAA.UK PUH-P2.5VGAA.UK PUH-P2.5YGAA.UK PUH-P3VGAA.UK PUH-P3YGAA.UK
Mode Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating
5,300 6,550 6,550 7,400 7,400
Capacity (W) 5,300 6,150 2.31 6,150 2.58 7,200 2.58 7,200 3.36 9,100 3.36 9,100
2.31 (7,330) 0.08 (7,330) 0.11 (8,960) 0.11 (8,960) 0.11 (10,860) 0.11 (10,860)
Total Input (kW) (In + Out) Heater) 0.08 2.30 0.38 2.30 0.51 2.60 0.51 2.60 0.51 0.51
(In + Out + (3.48) (3.48) (4.36) (4.36) 3.47 3.47
0.08 0.08 0.11 0.11 (5.23) (5.23)
Outdoor Indoor Input (kW) <1.18> <1.18> <1.76> <1.76> 0.11 0.11
0.38 0.38 0.51 0.51 <1.76> <1.76>
Current (A) 0.38 <5.36> <5.36> <8.00> <8.00> 0.51 0.51
<8.00> <8.00>
Current (A) 11.19 11.53 4.05 4.17 12.98 12.56 4.89 4.73 16.16 17.19 5.78 6.15
Starting current (A) 62 62 31 31 71 71 32 32 85 85 43 43
w ( ) shows the total rating.
< > shows the only booster heater rating.
Indoor……230V 50Hz Single phase
Outdoor… 230V 50Hz Single phase / 400V 50Hz 3 phase
Service Indoor With heater PCH-P2GAH1 PCH-P2.5GAH1 PCH-P3GAH1
Ref. unit Without heater PCA-P2GA1 PCA-P2.5GA1 PCA-P3GA1
Outdoor unit PUH-P2VGAA.UK PUH-P2YGAA.UK PUH-P2.5VGAA.UK PUH-P2.5YGAA.UK PUH-P3VGAA.UK PUH-P3YGAA.UK
Mode Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating
5,350 6,600 7,450
Capacity (W) 5,350 6,200 2.53 6,200 6,600 7,250 2.62 7,250 7,450 9,150 3.37 9,150
2.35 (6,930) 0.09 (6,930) (9,180) 0.12 (9,180) (11,080) 0.12 (11,080)
0.09 0.41 0.53 0.53
Total Input (kW) (In + Out) Heater) 2.34 3.84 2.34 2.62 2.66 4.65 2.66 3.37 3.48 5.49 3.48
(In + Out + (3.07) (3.07) (4.59) (4.59) (5.41) (5.41)
0.09 0.12 0.12 0.12
Outdoor Indoor Input (kW) <1.29> 0.09 0.12 <1.93> 0.12 0.12 <1.93> <1.93>
0.41 <1.29> 0.53 <1.93> 0.53 0.53
<5.61> <8.39> <8.39> <8.39>
Current (A) 0.41 0.41 0.53 0.53 0.53
11.03 <5.61> 12.01 <8.39> 16.45 5.84
Current (A) 10.71 3.96 12.42 4.50 15.45
Starting current (A) 62 62 31 31 74 74 34 34 89 89 45 45
w ( ) shows the total rating.
< > shows the only booster heater rating.
Indoor……240V 50Hz Single phase
Outdoor… 240V 50Hz Single phase / 415V 50Hz 3 phase
Service Indoor With heater PCH-P2GAH1 PCH-P2.5GAH1 PCH-P3GAH1
Ref. unit Without heater PCA-P2GA1 PCA-P2.5GA1 PCA-P3GA1
Outdoor unit PUH-P2VGAA.UK PUH-P2YGAA.UK PUH-P2.5VGAA.UK PUH-P2.5YGAA.UK PUH-P3VGAA.UK PUH-P3YGAA.UK
Mode Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating
5,400 6,650 7,500 7,500
Capacity (W) 5,400 6,250 2.40 6,250 6,650 7,300 2.65 7,300 3.40 9,200 3.40 9,200
2.40 (7,650) 0.10 (7,650) 2.65 (9,400) 0.13 (9,400) 0.13 (11,300) 0.13 (11,300)
Total Input (kW) (In + Out) 0.10 0.43 0.13 0.55 0.55 0.55
(In + Out + Heater) 2.40 3.70 2.40 0.55 2.71 4.48 2.71 14.81 3.50 5.29 3.50
(3.80) (3.80) (4.81) (4.81) (5.60) (5.60)
Outdoor Indoor Input (kW) 0.10 0.10 0.13 0.13 0.13 0.13
<1.40> <1.40> <2.10> <2.10> <2.10> <2.10>
Current (A) 0.43 0.43 0.43 0.55 0.55 0.55 0.55
<5.83> <5.83> <8.75> <8.75> <8.75> <8.75>
Current (A) 10.26 10.57 3.82 11.90 11.51 4.34 15.76 5.63
Starting current (A) 62 62 31 31 77 77 35 35 93 93 47 47
w ( ) shows the total rating.
< > shows the only booster heater rating.
52
Rating Conditions (ISO T1)
Indoor……220V 50Hz Single phase
Outdoor… 220V 50Hz Single phase / 380V 50Hz 3 phase
Service Indoor With heater PCH-P4GAH1 PCH-P5GAH1 PCH-P6GAH1
Ref. unit Without heater PCA-P4GA1 PCA-P5GA1 PCA-P6GA1
Outdoor unit PUH-P4VGAA.UK PUH-P4YGAA.UK PUH-P5YGAA.UK PUH-P6YGAA.UK
Mode Cooling Heating Cooling Heating Cooling Heating Cooling Heating
9,500 12,200 14,100
Capacity (W) 9,500 10,550 3.59 10,550 14,700 16,900
3.59 (12,820) 0.14 (12,820) 4.89 (17,210) 5.83 (19,420)
Total Input (kW) (In + Out) 0.14 0.68 0.20 0.20
(In + Out + Heater) 3.78 6.06 3.78 0.96 5.08 0.96 6.21
(6.05) (6.05) 8.30 (7.60) 9.86 (8.73)
Outdoor Indoor Input (kW) 0.14 0.14 0.20 0.20
<2.27> <2.27> <2.52> <2.52>
Current (A) 0.68 0.68 0.68 0.96 0.96
<10.32> <10.32> <11.46> <11.46>
Current (A) 17.13
18.08 6.40 8.90 10.44
Starting current (A) 91 91 44 44 65.5 65.5 74 74
w ( ) shows the total rating.
< > shows the only booster heater rating.
Indoor……230V 50Hz Single phase
Outdoor… 230V 50Hz Single phase / 400V 50Hz 3 phase
Service Indoor With heater PCH-P4GAH1 PCH-P5GAH1 PCH-P6GAH1
Ref. unit Without heater PCA-P4GA1 PCA-P5GA1 PCA-P6GA1
Outdoor unit PUH-P4VGAA.UK PUH-P4YGAA.UK PUH-P5YGAA.UK PUH-P6YGAA.UK
Mode Cooling Heating Cooling Heating Cooling Heating Cooling Heating
9,600 12,300 14,200
Capacity (W) 9,600 10,600 3.62 10,600 14,800 17,000
3.62 (13,080) 0.15 (13,080) 4.91 (17,550) 5.89 (19,760)
Total Input (kW) (In + Out) 0.15 0.69 0.22 0.22
(In + Out + Heater) 3.81 5.76 3.81 1.01 5.11 1.01 6.24
(6.29) (6.29) 7.89 (7.87) 9.37 (9.00)
Outdoor Indoor Input (kW) 0.15 0.15 0.22 0.22
<2.48> <2.48> <2.76> <2.76>
Current (A) 0.69 0.69 0.69 1.01 1.01
<10.78> <10.78> <12.00> <12.00>
Current (A) 16.39
17.30 6.08 8.46 9.92
Starting current (A) 95 95 47 47 65.5 65.5 74 74
w ( ) shows the total rating.
< > shows the only booster heater rating.
Indoor……240V 50Hz Single phase
Outdoor… 240V 50Hz Single phase / 415V 50Hz 3 phase
Service Indoor With heater PCH-P4GAH1 PCH-P5GAH1 PCH-P6GAH1
Ref. unit Without heater PCA-P4GA1 PCA-P5GA1 PCA-P6GA1
Outdoor unit PUH-P4VGAA.UK PUH-P4YGAA.UK PUH-P5YGAA.UK PUH-P6YGAA.UK
Mode Cooling Heating Cooling Heating Cooling Heating Cooling Heating
9,700 12,400 14,300
Capacity (W) 9,700 10,650 3.64 10,650 14,900 17,100
3.64 (13,350) 0.16 (13,350) 4.94 (17,880) 5.94 (20,100)
Total Input (kW) (In + Out) Heater) 0.16 0.70 0.24 0.24
(In + Out + 3.83 5.55 3.83 1.06 5.14 1.06 6.27
(6.53) (6.53) 7.60 (8.14) 9.03 (9.27)
Outdoor Indoor Input (kW) 0.16 0.16 0.24 0.24
<2.70> <2.70> <3.00> <3.00>
Current (A) 0.70 0.70 0.70 1.06 1.06
<11.25> <11.25> <12.50> <12.50>
Current (A) 15.71
16.58 5.86 8.15 9.56
Starting current (A) 99 99 49 49 65.5 65.5 74 74
w ( ) shows the total rating.
< > shows the only booster heater rating.
53
2.4. Cooling only type
Rating Conditions (ISO T1)
Indoor……220V 50Hz Single phase
Outdoor… 220V 50Hz Single phase / 380V 50Hz 3 phase
Indoor unit PCA-P2GA1 PCA-P2.5GA1 PCA-P3GA1
Service Ref. Outdoor unit PU-P2VGAA.UK PU-P2YGAA.UK PU-P2.5VGAA.UK PU-P2.5YGAA.UK PU-P3VGAA.UK PU-P3YGAA.UK
Mode Cooling Cooling Cooling Cooling Cooling Cooling
Capacity (W) 5,300 5,300 6,550 6,550 7,400 7,400
Total Input (kW) (In + Out) 2.31 2.31 2.58 2.58 3.36 3.36
Outdoor Indoor Input (kW) 0.08 0.08 0.11 0.11 0.11 0.11
Current (A) 0.38 0.38 0.51 0.51 0.51 0.51
Current (A) 11.19 4.05 12.98 4.89 16.16 5.78
Starting current (A) 62 31 71 32 85 43
Indoor……230V 50Hz Single phase
Outdoor… 230V 50Hz Single phase / 400V 50Hz 3 phase
Indoor unit PCA-P2GA1 PCA-P2.5GA1 PCA-P3GA1
Service Ref. Outdoor unit PU-P2VGAA.UK PU-P2YGAA.UK PU-P2.5VGAA.UK PU-P2.5YGAA.UK PU-P3VGAA.UK PU-P3YGAA.UK
Mode Cooling Cooling Cooling Cooling Cooling Cooling
Capacity (W) 5,350 5,350 6,600 6,600 7,450 7,450
Total Input (kW) (In + Out) 2.35 2.35 2.62 2.62 3.37 3.37
Outdoor Indoor Input (kW) 0.09 0.09 0.12 0.12 0.12 0.12
Current (A) 0.41 0.41 0.53 0.53 0.53 0.53
Current (A) 10.71 3.84 12.42 4.65 15.45 5.49
Starting current (A) 62 31 74 34 89 45
Indoor……240V 50Hz Single phase
Outdoor… 240V 50Hz Single phase / 415V 50Hz 3 phase
Indoor unit PCA-P2GA1 PCA-P2.5GA1 PCA-P3GA1
Service Ref. Outdoor unit PU-P2VGAA.UK PU-P2YGAA.UK PU-P2.5VGAA.UK PU-P2.5YGAA.UK PU-P3VGAA.UK PU-P3YGAA.UK
Mode Cooling Cooling Cooling Cooling Cooling Cooling
Capacity (W) 5,400 5,400 6,650 6,650 7,500 7,500
Total Input (kW) (In + Out) 2.40 2.40 2.65 2.65 3.40 3.40
Outdoor Indoor Input (kW) 0.10 0.10 0.13 0.13 0.13 0.13
Current (A) 0.43 0.43 0.55 0.55 0.55 0.55
Current (A) 10.26 3.70 11.90 4.48 14.81 5.29
Starting current (A) 62 31 77 35 93 47
54
Rating Conditions (ISO T1)
Indoor……220V 50Hz Single phase
Outdoor… 220V 50Hz Single phase / 380V 50Hz 3 phase
Indoor unit PCA-P4GA1 PCA-P5GA1 PCA-P6GA1
Service Ref. Outdoor unit PU-P4VGAA.UK PU-P4YGAA.UK PU-P5YGAA.UK PU-P6YGAA.UK
Mode Cooling Cooling Cooling Cooling
Capacity (W) 9,500 9,500 12,200 14,100
Total Input (kW) (In + Out) 3.59 3.59 4.89 5.83
Outdoor Indoor Input (kW) 0.14 0.14 0.20 0.20
Current (A) 0.68 0.68 0.96 0.96
Current (A) 17.13 6.06 8.30 9.86
Starting current (A) 91 44 65.5 74
Indoor……230V 50Hz Single phase
Outdoor… 230V 50Hz Single phase / 400V 50Hz 3 phase
Indoor unit PCA-P4GA1 PCA-P5GA1 PCA-P6GA1
Service Ref. Outdoor unit PU-P4VGAA.UK PU-P4YGAA.UK PU-P5YGAA.UK PU-P6YGAA.UK
Mode Cooling Cooling Cooling Cooling
Capacity (W) 9,600 9,600 12,300 14,200
Total Input (kW) (In + Out) 3.62 3.62 4.91 5.89
Outdoor Indoor Input (kW) 0.15 0.15 0.22 0.22
Current (A) 0.69 0.69 1.01 1.01
Current (A) 16.39 5.76 7.89 9.37
Starting current (A) 95 47 65.5 74
Indoor……240V 50Hz Single phase
Outdoor… 240V 50Hz Single phase / 415V 50Hz 3 phase
Indoor unit PCA-P4GA1 PCA-P5GA1 PCA-P6GA1
Service Ref. Outdoor unit PU-P4VGAA.UK PU-P4YGAA.UK PU-P5YGAA.UK PU-P6YGAA.UK
Mode Cooling Cooling Cooling Cooling
Capacity (W) 9,700 9,700 12,400 14,300
Total Input (kW) (In + Out) 3.64 3.64 4.94 5.94
Outdoor Indoor Input (kW) 0.16 0.16 0.24 0.24
Current (A) 0.70 0.70 1.06 1.06
Current (A) 15.71 5.55 7.60 9.03
Starting current (A) 99 49 65.5 74
55
3. STANDARD OPERATION DATA
3.1 Heat pump type
Rating Conditions (ISO T1)
Service Ref. With Electric heater PCH-P2GAH PCH-P2.5GAH PCH-P3GAH PCH-P4GAH PCH-P5GAH PCH-P6GAH
Without Electric heater PCA-P2GA PCA-P2.5GA PCA-P3GA PCA-P4GA PCA-P5GA PCA-P6GA
Mode Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating
Capacity
InputTotal W 5,500 6,550 7,000 7,300 7,500 9,300 9,700 10,650 12,800 16,000 14,500 16,800
Indoor unit [7,950] [9,400] [11,400] [13,350] [19,000] [19,800]
KW 2.58 2.67 2.76 2.71 3.47 3.65 3.52 3.70 5.49 5.71 6.60 6.67
[4.07] [4.81] [5.75] [6.40] [8.71] [9.67]
With Electric heater PCH-P2GAH PCH-P2.5GAH PCH-P3GAH PCH-P4GAH PCH-P5GAH PCH-P6GAH
Service Ref. Without Electric heater PCA-P2GA PCA-P2.5GA PCA-P3GA PCA-P4GA PCA-P5GA PCA-P6GA
Phase, Hz 1, 50 1, 50 1, 50 1, 50 1, 50 1, 50
Electrical circuit Volts V 240 240 240 240 240 240
Amperes A 0.43 0.43 0.55 0.55 0.55 0.55 0.70 0.70 1.06 1.06 1.06 1.06
Outdoor unit Service Ref. PUH-P2VGA PUH-P2.5VGA PUH-P3VGA
PUH-P4YGA PUH-P5YGA PUH-P6YGA
PUH-P2YGA PUH-P2.5YGA PUH-P3YGA
Phase, Hz 1/3, 50 1/3, 50 1/3, 50 3, 50 3, 50 3, 50
Volts V 240/415 240/415 240 / 415 415 415 415
Amperes A 11.11/3.88 11.51/4.02 11.78/4.11 11.55/4.03 14.64/5.46 15.43/5.76 5.49 5.79 8.39 8.74 10.17 10.28
Discharge pressure
Refrigerant circuit Suction pressure MPa 2.30 2.23 2.08 2.14 2.28 2.51 1.94 2.04 2.17 2.26 2.30 2.22
Discharge temperature (Of/F) (23.5) (23.7) (21.2) (21.8) (23.3) (25.6) (18.7) (20.8) (22.1) (23.1) (23.5) (22.6)
0.48 0.43 0.50 0.42 0.44 0.40 0.50 0.4 0.44 0.41 0.46 0.42
MPa (4.9) (4.4) (5.1) (4.3) (4.5) (4.1) (5.1) (4.1) (4.5) (4.2) (4.7) (4.3)
(Of/F)
75 67 76 78
°C 86 88 78 82 86 88 79 74
Condensing temperature °C 41 50 49 48 52 52 47 46 51 46 51 48
Suction temperature °C 3.5 0.3 6.0 0.7 3.5 -0.5 10 0.2 4.2 0.5 4 -0.5
Ref. pipe length m5 5 5 5 5 5 5 5 5 5 5 5
side Intake air temperature D.B. °C 27 20 27 20 27 20 27 20 27 20 27 20
W.B. °C 19 15 19 15 19 15 19 15 19 15 19 15
Indoor
Discharge air temperature D.B. °C 12.3 47.7 12.9 41.9 12.3 48.5 12.8 43.1 13.1 45.8 11.9 47.2
Outdoor Intake air temperature D.B. °C 35 7 35 7 35 7 35 7 35 7 35 7
side
W.B. °C 24 6 24 6 24 6 24 6 24 6 24 6
SHF 0.72 — 0.75 — 0.73 — 0.76 — 0.77 — 0.74 —
BF 0.09 — 0.08 — 0.08 — 0.06 — 0.07 — 0.04 —
The unit of pressure has been changed to Mpa on the international system of unit (SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(Mpa)=10.2(Of/F)
56
3.2 Heat pump type
Rating Conditions (ISO T1)
Service Ref. With Electric heater PCH-P2GAH1 PCH-P2.5GAH1 PCH-P3GAH1 PCH-P4GAH1 PCH-P5GAH1 PCH-P6GAH1
Without Electric heater PCA-P2GA1 PCA-P2.5GA1 PCA-P3GA1 PCA-P4GA1 PCA-P5GA1 PCA-P6GA1
Mode Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating
Capacity
InputTotal W 5,400 6,250 6,650 7,300 7,500 9,200 9,700 10,650 12,400 14,900 14,300 17,100
Indoor unit [7,650] [9,400] [11,300] [13,350] [17,800] [20,100]
Service Ref.
Phase, Hz KW 2.40 2.40 2.65 2.71 3.40 3.50 3.64 3.83 4.94 5.14 5.94 6.27
[3.80] [4.81] [5.60] [6.53] [8.14] [9.27]
With Electric heater PCH-P2GAH1 PCH-P2.5GAH1 PCH-P3GAH1 PCH-P4GAH1 PCH-P5GAH1 PCH-P6GAH1
Without Electric heater PCA-P2GA1 PCA-P2.5GA1 PCA-P3GA1 PCA-P4GA1 PCA-P5GA1 PCA-P6GA1
1, 50 1, 50 1, 50 1, 50 1, 50 1, 50
Electrical circuit Volts V 240 240 240 240 240 240
Amperes
A 0.43 0.43 0.55 0.55 0.55 0.55 0.70 0.70 1.06 1.06 1.06 1.06
Outdoor unit Service Ref. PUH-P2VGAA.UK PUH-P2.5VGAA.UK PUH-P3VGAA.UK PUH-P4VGAA.UK
PUH-P5YGAA.UK PUH-P6YGAA.UK
PUH-P2YGAA.UK PUH-P2.5YGAA.UK PUH-P3YGAA.UK PUH-P4YGAA.UK
Phase, Hz 1/3, 50 1/3, 50 1/3, 50 1/3, 50 3, 50 3, 50
Volts V 240/415 240/415 240 / 415 240 / 415 415 415
Amperes A 10.26/3.70 10.57/3.82 11.90/4.48 11.51/4.34 14.81/5.29 15.76/5.63 15.71/5.55 16.58/5.86 7.60 8.15 9.03 9.56
Discharge pressure
Refrigerant circuit Suction pressure MPa 2.30 2.23 2.08 2.14 2.28 2.51 1.94 2.04 2.17 2.26 2.30 2.22
Discharge temperature (Of/F) (23.5) (23.7) (21.2) (21.8) (23.3) (25.6) (18.7) (20.8) (22.1) (23.1) (23.5) (22.6)
Condensing temperature 0.44 0.41 0.46 0.42
Suction temperature MPa 0.48 0.43 0.50 0.42 0.44 0.40 0.50 0.4 (4.5) (4.2) (4.7) (4.3)
Ref. pipe length (Of/F) (4.9) (4.4) (5.1) (4.3) (4.5) (4.1) (5.1) (4.1)
78 79 74
°C 86 88 78 82 86 88 75 67 76
46 51 48
°C 41 50 49 48 52 52 47 46 51
0.5 4 -0.5
°C 3.5 0.3 6.0 0.7 3.5 -0.5 10 0.2 4.2
5 5 5
m5 5 5 5 5 5 5 5 5
side Intake air temperature D.B. °C 27 20 27 20 27 20 27 20 27 20 27 20
W.B. °C 19 15 19 15 19 15 19 15 19 15 19 15
Indoor
Discharge air temperature D.B. °C 12.6 46.4 13.6 41.9 12.3 48.2 12.8 43.1 13.5 44 12.1 47.7
Outdoor Intake air temperature D.B. °C 35 7 35 7 35 7 35 7 35 7 35 7
side
W.B. °C 24 6 24 6 24 6 24 6 24 6 24 6
SHF 0.72 — 0.75 — 0.73 — 0.76 — 0.77 — 0.74 —
BF 0.09 — 0.08 — 0.08 — 0.06 — 0.07 — 0.04 —
The unit of pressure has been changed to Mpa on the international system of unit (SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(Mpa)=10.2(Of/F)
57
3.3 Cooling only type
Rating Conditions (ISO T1)
Service Ref. PCA-P2GA PCA-P2.5GA PCA-P3GA PCA-P4GA PCA-P5GA PCA-P6GA
Cooling Cooling
Mode Cooling Cooling Cooling Cooling 12,800 14,500
5.49 6.60
Total Capacity W 5,500 7,000 7,500 9,700
PCA-P5GA PCA-P6GA
Input KW 2.58 2.76 3.47 3.52 1, 50 1, 50
240 240
Indoor unit Service Ref. PCA-P2GA PCA-P2.5GA PCA-P3GA PCA-P4GA 1.06 1.06
Phase, Hz 1, 50 1, 50 1, 50 1, 50 PU-P5YGA PU-P6YGA
Electrical circuit Volts V 240 240 240 240 3, 50 3, 50
415 415
Amperes A 0.43 0.55 0.55 0.70 8.39 10.17
Outdoor unit Service Ref. PU-P2VGA PU-P2.5VGA PU-P3VGA PU-P4YGA 2.17 2.30
(22.1) (23.5)
PU-P3YGA 0.44 0.46
(4.5) (4.7)
Phase, Hz 1, 50 1, 50 1/3, 50 3, 50
76 79
Volts V 240 240 240 / 415 415 51 51
4.2 4
Amperes A 11.11 11.78 14.64/5.46 5.49 5 5
Discharge pressure 27 27
Refrigerant circuit Suction pressure 2.30 2.08 2.28 1.94 19 19
Discharge temperature (23.5) (21.2) (23.3) (18.7) 13.1 11.9
0.48 0.50 0.44 0.50 35 35
(4.9) (5.1) (4.5) (5.1) 24 24
0.77 0.74
°C 86 78 86 75 0.07 0.04
Condensing temperature °C 41 49 52 47
Suction temperature °C 3.5 6.0 3.5 10
Ref. pipe length m 5 5 5 5
side Intake air temperature D.B. °C 27 27 27 27
Indoor W.B. °C 19 19 19 19
Discharge air temperature D.B. °C 12.3 12.9 12.3 12.8
Outdoor Intake air temperature D.B. °C 35 35 35 35
side
W.B. °C 24 24 24 24
SHF 0.72 0.75 0.73 0.76
BF 0.09 0.08 0.08 0.06
The unit of pressure has been changed to Mpa on the international system of unit (SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(Mpa)=10.2(Of/F)
58
3.4 Cooling only type
Rating Conditions (ISO T1)
Service Ref. PCA-P2GA1 PCA-P2.5GA1 PCA-P3GA1 PCA-P4GA1 PCA-P5GA1 PCA-P6GA1
Mode Cooling Cooling Cooling Cooling Cooling Cooling
Total Capacity W 5,400 6,650 7,500 9,700 12,400 14,300
Input KW 2.40 2.65 3.40 3.64 4.94 5.94
Indoor unit Service Ref. PCA-P2GA1 PCA-P2.5GA1 PCA-P3GA1 PCA-P4GA1 PCA-P5GA1 PCA-P6GA1
Phase, Hz 1, 50 1, 50 1, 50 1, 50 1, 50 1, 50
Electrical circuit Volts V 240 240 240 240 240 240
Amperes A 0.43 0.55 0.55 0.70 1.06 1.06
Outdoor unit Service Ref. PU-P2VGAA.UK PU-P2.5VGAA.UK PU-P3VGAA.UK PU-P4VGAA.UK
PU-P5YGAA.UK PU-P6YGAA.UK
PU-P2YGAA.UK PU-P2.5YGAA.UK PU-P3YGAA.UK PU-P4YGAA.UK
Phase, Hz 1/3, 50 1/3, 50 1/3, 50 1/3, 50 3, 50 3, 50
Volts V 240 / 415 240 / 415 240 / 415 240 / 415 415 415
Amperes A 10.26 / 3.70 11.90 / 4.48 14.81 / 5.29 15.71 / 5.55 7.60 9.03
Discharge pressure
Refrigerant circuit Suction pressure 2.30 2.08 2.28 1.94 2.17 2.30
Discharge temperature (23.5) (21.2) (23.3) (18.7) (22.1) (23.5)
0.48 0.50 0.44 0.50 0.44 0.46
(4.9) (5.1) (4.5) (5.1) (4.5) (4.7)
°C 86 78 86 75 76 79
Condensing temperature °C 41 49 52 47 51 51
Suction temperature °C 3.5 6.0 3.5 10 4.2 4
Ref. pipe length m 5 5 5 5 5 5
side Intake air temperature D.B. °C 27 27 27 27 27 27
Indoor W.B. °C 19 19 19 19 19 19
Discharge air temperature D.B. °C 12.6 13.6 12.3 12.8 13.5 12.1
Outdoor Intake air temperature D.B. °C 35 35 35 35 35 35
side
W.B. °C 24 24 24 24 24 24
SHF 0.72 0.75 0.73 0.76 0.77 0.74
BF 0.09 0.08 0.08 0.06 0.07 0.04
The unit of pressure has been changed to Mpa on the international system of unit (SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(Mpa)=10.2(Of/F)
4. OUTLET AIR SPEED AND COVERAGE RANGE
PCH-P2GAH PCH-P2.5GAH PCH-P3GAH PCH-P4GAH PCH-P5GAH PCH-P6GAH
PCA-P4GA PCA-P5GA PCA-P6GA
PCA-P2GA PCA-P2.5GA PCA-P3GA PCH-P4GAH1 PCH-P5GAH1 PCH-P6GAH1
PCA-P4GA1 PCA-P5GA1 PCA-P6GA1
PCH-P2GAH1 PCH-P2.5GAH1 PCH-P3GAH1
PCA-P2GA1 PCA-P2.5GA1 PCA-P3GA1 25 34 34
4.1 4.4 4.4
Air flow m3/min 13 18 18 12.6 15.2 15.2
Air speed m/sec
Coverage range 3.7 3.8 3.8
m
8.8 10.4 10.4
59
5. NOISE CRITERION CURVES
PCH-P2GAH NOTCH SPL(dB) LINE PCH-P2.5/3GAH NOTCH SPL(dB) LINE
PCA-P2GA PCA-P2.5/3GA
PCH-P2GAH1 Hi 42 PCH-P2.5/3GAH1 Hi 43
PCA-P2GA1 PCA-P2.5/3GA1
Mi1 40 Mi1 41
Mi2 38 Mi2 39
Lo 37 Lo 37
90 90
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR 80
70 70
NC-70 NC-70
60 60
NC-60 NC-60
50 50
NC-50 NC-50
40 40
NC-40 NC-40
30 30
NC-30 NC-30
20 APPROXIMATE 20 APPROXIMATE
TERESHOLD OF TERESHOLD OF
HEARING FOR NC-20 HEARING FOR NC-20
CONTINUOUS CONTINUOUS
NOISE NOISE
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz
PCH-P4GAH NOTCH SPL(dB) LINE PCH-P5GAH NOTCH SPL(dB) LINE
PCA-P4GA PCA-P5GA
PCH-P4GAH1 Hi 45 PCH-P5GAH1 Hi 46
PCA-P4GA1 PCA-P5GA1
Mi1 43 Mi1 45
Mi2 41 Mi2 43
Lo 40 Lo 41
90 90
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR 80
70 70
NC-70 NC-70
60 60
NC-60 NC-60
50 50
NC-50 NC-50
40 40
NC-40 NC-40
30 30
NC-30 NC-30
20 APPROXIMATE 20 APPROXIMATE
TERESHOLD OF TERESHOLD OF
HEARING FOR NC-20 HEARING FOR NC-20
CONTINUOUS CONTINUOUS
NOISE NOISE
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz
60
PCH-P6GAH NOTCH SPL(dB) LINE
PCA-P6GA
PCH-P6GAH1 Hi 48
PCA-P6GA1
Mi1 46
Mi2 44
Lo 42
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR 80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20 APPROXIMATE
TERESHOLD OF
HEARING FOR NC-20
CONTINUOUS
NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
1m ceiling Ambient temperature 27˚C
1m unit Test conditions are based on JIS Z8731
about 1.4m
MICROPHONE
61
7 OUTLINES AND DIMENSIONS
1. INDOOR UNIT Unit : mm
PCH-P2GAH, PCA-P2GA
PCH-P2GAH1, PCA-P2GA1 NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. Please be sure when installing the drain-up machine (option parts).
Refrigerant pipe will be only upper drain pipe arrangement.
6
150 17 80
140 70 320
70 Electrical box 933 (suspension bolt pitch) 85
983 15
7 904 81 76
1000 180
210
157
226 2 182 (3/8F) liquid
201 (5/8F) gas
Air outlet 241 (Drainage)
56
680
506
254
Air intake
161 90
918
3 2 Electrical box [Front view] 5 14
32 Ceiling 8 1 Drainage pipe connection (26mm I.D.)
2 Drainage pipe connection (for the left arrangement)
42 179 161 38 38 79 3 Knock out hole for left drain-piping arrangement
6~7 131 4 Refrigerant-pipe connection (gas pipe side/flared connection)
5 Refrigerant-pipe connection (liquid pipe side/flared connection)
46 175 6 Knock out hole for upper drain pipe arrangement
86 7 Knock out hole for left drain pipe arrangement
8 Knock out hole for wiring arrangement
138
525 171
928 263
352
When electrical
box is pulled
down
62
PCH-P2.5GAH, PCA-P2.5GA Unit : mm
PCH-P2.5GAH1, PCA-P2.5GA1
PCH-P3GAH, PCA-P3GA NOTES:
PCH-P3GAH1, PCA-P3GA1 1. Use M10 or W3/8 screws for anchor bolt.
2. Please be sure when installing the drain-up machine (option parts).
150 17 80
Refrigerant pipe will be only upper drain pipe arrangement.
320
6
140 70
70 Electrical box 1240 (suspension bolt pitch) 85
1290 15
7
1214 81 76
1310 180
210
157
226 2 182 (3/8F liquid)
201 (5/8F gas)
Air outlet 241 (Drainage)
56
680
506
254
Air intake
161 90
1228
2 Electrical box [ Front view ] 5 14
3
8 1 Drainage pipe connection (26mm I.D.)
2 Drainage pipe connection (for the left arrangement)
Ceiling 3 Knock out hole for left drain-piping arrangement
42 179 4 Refrigerant-pipe connection (gas pipe side/flared connection)
6~7 5 Refrigerant-pipe connection (liquid pipe side/flared connection)
6 Knock out hole for upper drain pipe arrangement
161 32 7 Knock out hole for left drain pipe arrangement
38 3879 8 Knock out hole for wiring arrangement
131
46 175 1
86
525
1235 138
171
263
416
When electrical
box is pulled
down
63
PCH-P4GAH, PCA-P4GA Unit : mm
PCH-P4GAH1, PCA-P4GA1
NOTES:
150 18 1. Use M10 or W3/8 screws for anchor bolt.80
2. Please be sure when installing the drain-up machine (option parts).
320
Refrigerant pipe will be only upper drain pipe arrangement.
6
140 70
70 Electrical box 1240 (suspension bolt pitch) 87
16
1214
7 1310 81 96
207
270
217
229 2 182 (3/8F liquid)
198 (3/4F-gas)
Air outlet 245 (Drainage)
56
680
506
254
Air intake
161 90
1228
2 Electrical box [ Front view ] 5 14 1 Drainage pipe connection (26mm I.D.)
3 2 Drainage pipe connection (for the left arrangement)
8 Ceiling93 3 Knock out hole for left drain-piping arrangement
When electrical 4 Refrigerant-pipe connection (gas pipe side/flared connection)
42 239 box is pulled 160 38 38 140 5 Refrigerant-pipe connection (liquid pipe side/flared connection)
down 192 6 Knock out hole for upper drain pipe arrangement
6~7 7 Knock out hole for left drain pipe arrangement
45 236 1 8 Knock out hole for wiring arrangement
86
138
171
263
525 687
1235
64
PCH-P5GAH, PCA-P5GA Unit : mm
PCH-P5GAH1, PCA-P5GA1
PCH-P6GAH, PCA-P6GA NOTES:
PCH-P6GAH1, PCA-P6GA1 1. Use M10 or W3/8 screws for anchor bolt.
2. Please be sure when installing the drain-up machine (option parts).
150 18 80
Refrigerant pipe will be only upper drain pipe arrangement.
320
6
140 70
70 1547(suspension bolt pitch) 87
Electrical box 16
1524
7 1620 81 96
207
270
217
229 2 182 (3/8F liquid)
198 (3/4F gas)
Air outlet 245 (Drainage)
56
680
506
254
Air intake
161 90
1535
2 Electrical box [ Front view ] 8 5 14
3 Ceiling
93
42 239 160 38 38 140 1 Drainage pipe connection (26mm I.D.)
192 2 Drainage pipe connection (for the left arrangement)
6~7 3 Knock out hole for left drain-piping arrangement
45 236 1 4 Refrigerant-pipe connection (gas pipe side/flared connection)
86 5 Refrigerant-pipe connection (liquid pipe side/flared connection)
6 Knock out hole for upper drain pipe arrangement
138 7 Knock out hole for left drain pipe arrangement
171 8 Knock out hole for wiring arrangement
263
525 687
1545
When electrical
box is pulled
down
65
8 WIRING DIAGRAM
PCH-P2GAH, PCH-P2.5GAH, PCH-P3GAH, PCH-P4GAH, PCH-P5GAH, PCH-P6GAH
PCH-P2GAH1, PCH-P2.5GAH1, PCH-P3GAH1, PCH-P4GAH1, PCH-P5GAH1, PCH-P6GAH1
PCA-P2GA, PCA-P2.5GA, PCA-P3GA, PCA-P4GA, PCA-P5GA, PCA-P6GA
PCA-P2GA1, PCA-P2.5GA1, PCA-P3GA1, PCA-P4GA1, PCA-P5GA1, PCA-P6GA1
SYMBOL NAME SYMBOL NAME SYMBOL NAME
P.B INDOOR POWER BOARD MV VANE MOTOR W.B WIRELESS REMOTE CONTROLLER BOARD(OPTION)
F1 FUSE(4A) DP DRAIN-UP MACHINE(OPTION) RU RECEIVING UNIT
ZNR VARISTOR DS DRAIN SENSOR(OPTION) BZ BUZZER
I.B INDOOR CONTROLLER BOARD TB2 TERMINAL BLOCK(HEATER) LED1 LED(RUN INDICATOR)
CN2L CONNECTOR(LOSSNAY) TB4 TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE) LED2 LED(HOT ADJUST)
CN32 CONNECTOR(REMOTE SWITCH) TB5 TERMINAL BLOCK(REMOTE CONTROLLER SW1 SWITCH(HEATING ON/OFF)
CN41 CONNECTOR(HA TERMINAL-A) TRANSMISSION LINE) SW2 SWITCH(COOLING ON/OFF)
SW1 JUMPER WIRE(MODEL SELECTION) TH1 ROOM TEMPERATURE THERMISTOR HEATER
SW2 JUMPER WIRE(CAPACITY CODE) (0;/15k' ,25;/5.4k' DETECT) FS1,2 THERMAL FUSE<98;10A:2GAH / 117;16A:4GAH
SWE SWITCH(EMERGENCY OPERATION) TH2 PIPE TEMPERATURE THERMISTOR/LIQUID 110;16A:2.5,3GAH,5,6GAH>
X1 RELAY(DRAIN PUMP) (0;/15k', 25;/5.4k' DETECT) H1 HEATER
X4 RELAY(FAN MOTOR) TH5 CONDENSER/ EVAPORATOR TEMPERATURE THERMISTOR 26H HEATER THERMAL SWITCH
FC FAN PHASE CONTROL (0;/15k', 25;/5.4k' DETECT) 88H HEATER CONTACTOR
LED1 POWER SUPPLY(I.B) R.B REMOTE CONTROLLER BOARD
LED2 POWER SUPPLY(R.B) CN2 CONNECTOR(PROGRAM TIMER)
LED3 TRANSMISSION(INDOOR-OUTDOOR) TB6 TERMINAL BLOCK(REMOTE CONTROLLER
C CAPACITOR(FAN MOTOR) TRANSMISSION LINE)
MF FAN MOTOR
INDOOR UNIT CN2S(WHT) P.B
2 F1
OUTDOOR UNIT
MF (OPTION) 1 DC14V ZNR YLW TB4 TB1<PU(H)-P2~3VGA(A)>
123 DP ORN S1 S1 POWER SUPPLY
3 1 BRN S2 S2 ~(1PHASE)
C 2 2 S3 S3 220-240V 50Hz
1 3
RED YLW ORN BRN BLK WHT OUTDOOR
WHT CONT.BOARD
BLK
I.B CN02(WHT) CN01(BLU) L
N
FAN 1 3 5 D.U.M 13 POWER 1 3 5 12 VANE 6 6
(WHT) CNP CN03 CN6V
POWER (WHT)
(BLU) (RED) CN2D(WHT) MV S1 TB1<PU(H)-P2~6YGA(A)>
FC X4 X1 CN41 CN2L WIRELESS S2 POWER SUPPLY
S3 3N~(3PHASE 4WIRES)
X4 X1 CN90 9 380-415V 50Hz
CN25 CN32 (WHT) L1
LED3 LED2 LED1 L2
SWE SW2 SW1 D.SENSOR INTAKE LIQUID PIPE REMOCON BZ CNB L3
ON
OFF CN31 CN20 CN21 CN29 CN22 N
J15 (WHT) (RED) (WHT) (BLK) (BLU) RU
J14
J13 123 12 12 12 12
J12
J11
J24
J23
J22
J21
RECEIVER LED1 LED2 SW2 SW1
When installing drain-up BLK BLK BLK BLK BLU W.B
machine(Optional part). BLU 2
1 TRANSMISSION WIRES DC12V
12 12
CN31 DRAIN SENSOR TB5 R.B Please set the voltage using the remote
TH1 TH2 TH5 CN2 controller.
(WHT) 1 2 3 wWhen installing optional 12 For the setting method, please refer to
drain-up machine,disconnect TB6 the indoor unit installation manual.
the CN31 jumper connector
and replace it with the
drain sensor(DS).
DS 88H TB2
H1 FS1 FS2 RED RED 5 3RED L
WHT BLU N
MODELS SW1 SW2 1 POWER SUPPLY
2 ~(1PHASE)
Manufacture Service board 220-240V 50HZ
GRN/YLW
P2 <For manufacture> J21J22J23J24 1234 PCH-P2~P6GAH only HEATER
P2.5 J11 J12 J13 J14 J15 J21J22J23J24 ON CN24
P3 OFF I.B 1 2 (YLW)
J21 J22 J23 J24
1234 YLW 6 RED 26H
ON YLW 5 RED
OFF
6 88H 1 GRY
1234
ON
OFF
P4 1234 ON NOTES:
1.Since the outdoor side electric wiring may change be sure to check the outdoor unit
<For service board> J21J22J23J24 OFF
electric wiring for servicing.
P5 12345 1234 2.Indoor and outdoor connecting wires are made with polarities,make wiring matching
ON ON terminal numbers(S1,S2,S3).
OFF J21J22J23J24 OFF 3.Make sure that the main power supply of the booster heater is independent.
4.Symbols used in wiring diagram above are, :Connector, :Terminal block.
P6 1234 ON
J21 J22 J23 J24 OFF
66
9 REFRIGERANT SYSTEM DIAGRAM
PCH-P2GAH, PCA-P2GA, / PUH-P2VGA, PUH-P2YGA Unit : mm
PCH-P2GAH1, PCA-P2GA1, / PUH-P2VGAA.UK, PUH-P2YGAA.UK
PCH-P2.5GAH, PCA-P2.5GA, / PUH-P2.5VGA, PUH-P2.5YGA
PCH-P2.5GAH1, PCA-P2.5GA1, / PUH-P2.5VGAA.UK, PUH-P2.5YGAA.UK
PCH-P3GAH, PCA-P3GA, / PUH-P3VGA, PUH-P3YGA
PCH-P3GAH1, PCA-P3GA1,
/ PUH-P3VGAA.UK, PUH-P3YGAA.UK <4-way valve solenoid coil>
Indoor unit
Heating : ON
Refrigerant flow in cooling Cooling : OFF
Refrigerant flow in heating
High pressure Outdoor unit
Refrigerant pipe 4-way valve
switch
15.88mm( 5/8") Ball valve Thermistor
(with heat insulator) Strainer (TH6)
Thermistor Flexible tube Service
(TH1) port
Thermistor Service Muffler Thermistor
(TH5) port (TH3)
Thermistor Distributor
Strainer Flared (TH4) with
connection strainer
Distributor Accumulator Compressor
with Drier
strainer Strainer Strainer
Thermistor Refrigerant pipe Ball valve
(TH2) 9.52mm( 3/8") (with service port)
(with heat insulator)
Linear expansion valve
PCH-P4GAH, PCA-P4GA, / PUH-P4YGA
PCH-P4GAH1, PCA-P4GA1, / PUH-P4VGAA.UK, PUH-P4YGAA.UK
Indoor unit Refrigerant pipe High pressure Outdoor unit
19.05mm( 3/4") Ball valve 4-way valve switch Thermistor
Thermistor (with heat insulator) Strainer (TH6)
(TH1)
Thermistor Flexible tube Service Distributor
(TH5) port with
Distributor Service Muffler strainer
with port Capillary
strainer Thermistor tube
Thermistor (TH4)
(TH2) Strainer Flared
connection Thermistor
(TH3)
Accumulator Compressor
Drier
Refrigerant pipe Ball valve Strainer Strainer
9.52mm( 3/8") (with service port) Linear expansion valve
(with heat insulator)
PCH-P5GAH, PCA-P5GA, PUH-P5YGA
PCH-P6GAH, PCA-P6GA, PUH-P6YGA
Outdoor unit
Indoor unit Refrigerant pipe High pressure Thermistor
19.05mm( 3/4") Ball valve 4-way valve switch (TH6)
Thermistor (with heat insulator) Strainer
(TH1) Distributor
Thermistor Flexible tube Service with
(TH5) port strainer
Distributor Service Muffler Capillary
with port tube
strainer Capillary Thermistor
Thermistor (TH4)
(TH2) Strainer Flared tube
connection Thermistor
(TH3)
Bypass
valve
Accumulator Compressor
Drier
Refrigerant pipe Ball valve Strainer Strainer
9.52mm( 3/8") (with service port) Linear expansion valve
(with heat insulator)
67
PCA-P2GA, / PU-P2VGA Unit : mm
PCA-P2GA1, / PU-P2VGAA.UK, PU-P2YGAA.UK
PCA-P2.5GA, / PU-P2.5VGA
PCA-P2.5GA1, / PU-P2.5VGAA.UK, PU-P2.5YGAA.UK
PCA-P3GA, / PU-P3VGA, PU-P3YGA
PCA-P3GA1, / PU-P3VGAA.UK, PU-P3YGAA.UK
Refrigerant flow in cooling
Refrigerant pipe High pressure Outdoor unit
Indoor unit 15.88mm( 5/8") Ball valve switch Thermistor
Thermistor (TH6)
(TH1) (with heat insulator) Strainer
Thermistor
(TH5) Flexible tube Service
port
Service Thermistor Thermistor
port (TH4) (TH3)
Distributor
Strainer Flared with
connection strainer
Distributor Accumulator Compressor
with Drier
strainer Strainer Strainer
Thermistor Refrigerant pipe Ball valve
(TH2) 9.52mm( 3/8") (with service port)
(with heat insulator)
Linear expansion valve
PCA-P4GA, / PU-P4YGA
PCA-P4GA1, / PU-P4YGAA.UK
PCA-P5GA1, / PU-P5YGAA.UK
PCA-P6GA1, / PU-P6YGAA.UK High pressure Outdoor unit
switch Thermistor
Indoor unit Refrigerant pipe (TH6)
19.05mm( 3/4") Ball valve
(with heat insulator) Strainer Distributor
with
Thermistor Flexible tube Service strainer
(TH1) port Capillary
Thermistor Service tube
(TH5) port
Strainer Flared Thermistor
connection (TH4)
Distributor Accumulator Thermistor
with Drier (TH3)
strainer
Thermistor Compressor
(TH2)
Refrigerant pipe Ball valve Strainer Strainer
9.52mm( 3/8") (with service port) Linear expansion valve
(with heat insulator)
PCA-P5GA, / PU-P5YGA
PCA-P6GA, / PU-P6YGA Outdoor unit
Indoor unit Refrigerant pipe High pressure Thermistor
switch (TH6)
Thermistor 19.05mm( 3/4")
(TH1) (with heat insulator) Ball valve Distributor
Thermistor Strainer with
(TH5) strainer
Distributor Flexible tube Service Capillary
with port tube
strainer Service Low
Thermistor port pressure
(TH2) switch
Strainer Flared Thermistor
connection (TH4)
Thermistor
(TH3)
Accumulator Compressor
Drier
Refrigerant pipe Ball valve Strainer Strainer
9.52mm( 3/8") (with service port) Linear expansion valve
(with heat insulator)
68
10 TROUBLESHOOTING
HOW TO CHECK THE PARTS
PCH-P2 / 2.5 / 3 / 4 / 5 / 6GAH, PCH-P2 / 2.5 / 3 / 4 / 5 / 6GAH1
PCA-P2 / 2.5 / 3 / 4 / 5 / 6GA, PCA-P2 / 2.5 / 3 / 4 / 5 / 6GA1
Parts name Check points
Room temperature Disconnect the connector then measure the resistance using a tester.
thermistor (TH1) (Surrounding temperature 10:~30:)
Pipe temperature Normal Abnormal (Refer to the next pege for a detail.)
thermistor (TH2) 4.3k"~9.6k" Open or short
Condenser/evaporator
temperature thermistor
(TH5)
Fan motor Measure the resistance between the terminals using a tester.
Relay connector (Winding temperature 20:)
1 Red 1 Motor terminal Normal
2 White 2 or
3 Black 3 P2 P2.5, P3 P4 P5, P6 Abnormal
Relay connector Open or short
Protector Red–Black 70.6" 45.0" 43.7" 20.4"
OFF : 130i 5: White–Black 69.6" 44.8" 55.3" 20.7"
ON : 80i 20:
Connector Normal
Vane motor
Brown–Yellow
4 Orange Brown–Blue P2 P2.5, P3 Abnormal
Red–Orange
5 Red M
Red–Pink
2 Pink
186~214" 140~160" Open or short
Yellow Brown Blue
361
4 Pink Connector Normal Abnormal
P4, P5, P6
2 Orange M Brown–Yellow
5 Red Brown–Blue 140~160" Open or short
Yellow Blue Red–Orange
31 Red–Pink
Heater Measure the resistance of each heater element by using a tester.
(Only P2~P6GAH) (Surrounding temperature 20:)
Normal Abnormal
Open or short
P2 P2.5, P3 P4 P5, P6
13.7" 9.1" 7.1" 6.4"
0.467kW 80V 0.7kW 80V 0.9kW 80V 1.0kW 80V
Drain-up Measure the resistance between the terminals using a tester.
mechanism (Option) (Winding temperature 20:)
Gray Normal Abnormal
1 195" Open or short
2 Measure the resistance between the terminals using a tester.
Gray
Normal Abnormal
Contactor P2~P6 Open or short
(Only P2~P6GAH) 10 88H 11
107"
69
<Thermistor Characteristic graph>
Thermistor for Room temperature thermistor(TH1) < Thermistor for lower temperature >
lower temperature Pipe temperature thermistor(TH2) 50
Condenser/evaporator temperature
thermistor(TH5) 40
Thermistor R0=15kΩ ± 3% Resistance (K") 30
Fixed number of B=3480kΩ ± 2%
20
Rt=15exp { 3480( 1 1 )}
273+t 273 10
0: 15kΩ 0
10: 9.6kΩ -20 -10 0 10 20 30 40 50
20: 6.3kΩ Temperature (:)
25: 5.4kΩ
30: 4.3kΩ
40: 3.0kΩ
70
11 DISASSEMBLY PROCEDURE
PCH-P3GAH, PCA-P3GA PHOTOS&ILLUSTRATIONS
PCH-P3GAH1, PCA-P3GA1
Figure 1
OPERATING PROCEDURE
1. Removing the air intake grille
(1) Slide the intake grille holding knobs (at two locations)
backward to open the intake grill.
(2) When the intake grille left open, push the stoppers on the
rear hinges (at two locations) to pull out the intake grille.
Intake grill slide
Intake grill
Holding knobs
Hinges
Pull out the intake grill
2. Removing the electrical box Figure 2
(1) Remove the air intake grille.
(2) Remove the screw from the beam and remove the beam. Beam
(3) Remove the screws from the electrical cover, and
remove the electrical cover. Slide to the left
(4) Disconnect CN6V and CN21.
(5) Remove the screws from the electrical box and pull out Screw(electrical cover) Clamp
the electrical box. Electrical cover
<Electrical parts in the electrical box> Screw(electrical box)
Terminal block (for indoor / outdoor connecting line)
Terminal block (for electric heater : PCH-P2~P6GAH only) Photo 1
Terminal block (for remote controller)
Fan motor capacitor
Indoor control board
Relay (PCH-P2~P6GAH only)
Fan motor Relay (PCH-P2~P6GAH only)
capacitor
Power board
Terminal
Indoor Terminal Terminal block
control block (remote control)
board
block (Indoor / outdoor
(Electric heater) connecting line)
71
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
3. Removing the fan motor Photo 2
(1) Remove the intake grille.
(2) Disconnect the fan motor connector. Screws Motor guard
(3) Unscrew screws for removing the motor guard. Motor Set screws
(4) Unscrew screws for removing the fan guard.
(5) Remove the screw for removing the motor support at both
left and right side.
(6) Loosen the set screws at the fan motor side of the con-
necting joint.
(7) Slide the fan motor to the left side and pull it out.
Motor support Connecting joint
4. Removing the sirocco fan Photo 3
(1) Remove the air intake grille.
(2) Remove 1 beam. Motor guard Fan guard
(3) Unscrew screws for removing the motor guard.
(4) Unscrew screws for removing the fan guard. Motor Sirocco fan
(5) Remove the lower casing while pressing the stoppers at
upper side of the casing. Casing
(6) Loosen the set screws at the connecting joint.
(7) Remove the sirocco fan and shaft together by sliding the Connecting joint Bearing
shaft to the left.
Figure 3
(Note)
Make sure that the upper side casing is snapped to the fan Side panel
plate securely with catch.
5. Removing the side panel
(1) Remove the air intake grille.
(2) Remove the screw from the side panel, and remove the
side panel by sliding the panel to the front.
Sliding the panel
to the front
Screw
72
OPERATING PROCEDURE Photo 4 PHOTOS Relay connector of
the pipe thermistor
6. Removing the vane motor Left side Check
(1) Remove the air intake grille. panel Screw panel
(2) Remove the left side panel.
(3) Remove the relay connector of vane motor. Photo 5
(4) Remove the electrical box.
(5) Remove the screws of vane motor, then remove vane
motor.
(Note)
Connect the lead wires and connectors properly and place
them in the proper position so that the wires are not pinched
by other parts.
Hold Indoor coil thermistor Tie up
7. Removing the Indoor coil thermistor Photo 6 Screw
(1) Remove the air intake grille.
(2) Remove the right side panel. Relay connector of
(3) Remove the relay connector of the pipe thermistor. the vane motor
(4) Remove the screw, and remove the check panel.
(5) Extract the indoor coil thermistor from the holder.
<Caution for the installation>
There is a possibility for the short circuit when connector gets
wet by water through the thermistor lead wire.
Therefore, lead wire of the indoor coil thermistor should be
tied as shown in the photo 5.
Vane motor
8. Removing the Under panel Photo 7 Screw
(1) Remove the air intake grille.
(2) Remove the beam.
(3) Remove the side panel (right and left).
(4) Unscrew the screws of the under panel, then remove the
under panel.
w Weight of the under panel : approx. 2kg.
Under panel
73
OPERATING PROCEDURE PHOTOS
9. Removing the drain pan Photo 8
(1) Remove the air intake grille.
(2) Remove the beam.
(3) Remove the side panel (right and left).
(4) Remove the under panel. Remove the screws of the right
and left side drain pan.
(5) Remove the insulation in centre of the drain pan, and
after removing the screw, remove the drain pan.
(Note)
Please aware that there might be drain left in the drain pan
when you remove the drain pump (option).
Screw Drain pan Screw Screw
(Insulation)
10. Removing the guide vane Photo 9
(1) Remove the intake grille.
(2) Remove the beam.
(3) Remove the side panel (right and left).
(4) Remove the under panel.
(5) Remove the drain pan.
(6) Remove the screw from the guide vane, then remove the
guide vane.
Drain pan Screw
Guide vane
11. Removing the Auto vane Photo 10
(1) Remove the intake grille.
(2) Remove the left side panel.
(3) Remove the left side box.
(4) Remove the under panel.
(5) Remove the screw from the auto vane.
(6) Slide the auto vane to the right side and pull the auto
vane out.
Screw
Auto vane
74
OPERATING PROCEDURE Photo 11 PHOTOS
12. Removing the electric heater. (PCH-P2~P6GAH only) Screws
(1) Remove the air intake grille.
(2) Remove the beam.
(3) Remove the side panel (right and left).
(4) Remove the relay connector for the pipe thermistor.
(5) Remove the under panel.
(6) Remove the drain pan.
(7) Remove the screw from the pipe cover, and remove the
pipe cover.
(8) Remove the screw from the pipe support, and remove the
pipe fixed support.
Clamp Connector Service
(heater) panel
Electrical
box
13. Removing the heat exchanger. Photo 12 Screws Heat
(1) Remove the air intake grille. exchanger
(2) Remove the beam. Pipe
(3) Remove the side panel (right and left). support
(4) Disconnect the relay connector.
(5) Remove the under panel. Screws
(6) Remove the drain pan.
(7) Unscrew the screw of the pipe cover, and remove the Pipe cover
pipe cover.
(8) Unscrew the screw of the pipe support, and remove the
pipe support.
(9) Unscrew the screw of the heat exchanger, and remove
the heat exchanger.
Remove the heat exchanger with care. Since this is quite
heavy, removing work should be done with more than 2
people.
wWeight of heat exchanger : approx. 5.3kg
75
12 PARTS LIST
FAN AND HEATER PARTS
PCH-P2GAH, PCH-P2GAH1 10 13
12
PCA-P2GA, PCA-P2GA1 6
4 2 8
5 1 9
17
18 7
4
3 5
16
15
14
11
Q'ty / set Wiring Recom-
Diagram mended
No. Parts No. Parts Name Specifications PCH-P2 PCA-P2 Remarks
(Drawing No.) Symbol Q'ty Unit Amount
MF
GAH GAH1 GA GA1
TH2
1 T7W 23J 762 FAN MOTOR D09B4P54MS 1 1 1 1 H1
26H
2 R01 17J 130 MOTOR LEG 1111
FS1,2
3 R01 43E 126 PIECE (MOTOR) 1111 TH5
4 T7W B06 110 CASING 2222 TH1
5 R01 17J 114 SIROCCO FAN 2222
6 R01 17J 202 PIPE TEMPERATURE THERMISTOR 1111
7 T7W 23J 300 HEATER ELEMENT 80V 466W 33
8 R01 46K 700 THERMAL SWITCH OFF:50: ON:35: 1 1
R01 18J 303 INSULATOR 33
9 11
R01 20J 303 INSULATOR
10 R01 P02 706 THERMAL FUSE 250V 98: 10A 1 1
11 R01 A14 529 DRAIN PAN ASSY 1111
12 T7W E08 202 CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR 1111
13 T7W E13 480 HEAT EXCHANGER 1111
14 R01 17J 524 DRAIN PLUG 1111
15 T7W 17J 675 FAN GUARD 1111
16 T7W 18J 675 FAN GUARD 1111
17 T7W 19J 675 FAN GUARD 1111
18 T7W E02 202 ROOM TEMPERATURE THERMISTOR 1111
76
11 15
FAN AND HEATER PARTS 10
PCH-P2.5GAH, PCA-P2.5GA
PCH-P2.5GAH1, PCA-P2.5GA1
14
13
5 23 9
1 4·18 12
6
2 8
21
22 16
7 17
19
3
20
Q'ty / set Wiring Recom- Price
No. Parts No. Parts Name Specifications PCH-P2.5 PCA-P2.5 Remarks Diagram mended
(Drawing No.)
Symbol Q'ty Unit Amount
GAH GAH1 GA GA1
1 T7W 30J 762 FAN MOTOR DO9C4P70MS 1 1 1 1 MF
2 R01 700 116 SHAFT JOINT 1111
3 R01 29J 100 SHAFT (FAN) 1111
4 R01 705 103 SLEEVE BEARING 1111
5 R01 29J 130 MOTOR LEG 1111
6 R01 29J 114 SIROCCO FAN 2222
7 R01 33J 114 SIROCCO FAN 1111
8 T7W B06 110 CASING 3333
9 T7W 30J 300 HEATER ELEMENT 80V 700W 33 H1
26H
10 R01 46K 700 THERMAL SWITCH OFF:50: ON:35: 1 1 FS1,2
11 T7W 23J 706 THERMAL FUSE 110: 16A 250V 1 1 TH2
TH5
R01 20J 303 INSULATOR 11
12 33
R01 30J 303 INSULATOR
13 R01 17J 202 PIPE TEMPERATURE THERMISTOR 1111
14 T7W E08 202 CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR 1111
15 T7W E15 480 HEAT EXCHANGER 1111
16 R01 A15 529 DRAIN PAN ASSY 1111
17 R01 17J 524 DRAIN PLUG 1111
18 R01 29J 145 BEARING SUPPORT 1111
19 T7W 20J 675 FAN GUARD 1111
20 T7W 21J 675 FAN GUARD 2222
21 T7W 18J 675 FAN GUARD 1111
22 R01 43E 126 PIECE (MOTOR) 1111
23 T7W E02 202 ROOM TEMPERATURE THERMISTOR 1111 TH1
77
PCH-P3GAH, PCA-P3GA 11
PCH-P3GAH1, PCA-P3GA1 15
10
14
13
5 23 9
1 4·18 12
6
2 8
21
22 16
7 17
19
3
20
Q'ty / set Price
No. Parts No. Parts Name Specifications PCH-P3 PCA-P3 Remarks Wiring Recom-
(Drawing No.) Diagram mended
1 T7W 30J 762 FAN MOTOR GAH GAH1 GA GA1 Symbol Q'ty Unit Amount
DO9C4P70MS 1 1 1 1 MF
2 R01 700 116 SHAFT JOINT 1111 H1
26H
3 R01 29J 100 SHAFT (FAN) 1111 FS1,2
TH2
4 R01 705 103 SLEEVE BEARING 1111 TH5
5 R01 29J 130 MOTOR LEG 1111 TH1
6 R01 29J 114 SIROCCO FAN 2222
7 R01 33J 114 SIROCCO FAN 1111
8 T7W B06 110 CASING 3333
9 T7W 30J 300 HEATER ELEMENT 80V 700W 33
10 R01 46K 700 THERMAL SWITCH OFF:50: ON:35: 1 1
11 T7W 23J 706 THERMAL FUSE 110: 16A 250V 1 1
R01 20J 303 INSULATOR 11
12 33
R01 30J 303 INSULATOR
13 R01 17J 202 PIPE TEMPERATURE THERMISTOR 1111
14 T7W E08 202 CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR 1111
15 T7W E15 480 HEAT EXCHANGER 1111
16 R01 A15 529 DRAIN PAN ASSY 1111
17 R01 17J 524 DRAIN PLUG 1111
18 R01 29J 145 BEARING SUPPORT 1111
19 T7W 20J 675 FAN GUARD 1111
20 T7W 21J 675 FAN GUARD 2222
21 T7W 18J 675 FAN GUARD 1111
22 R01 43E 126 PIECE (MOTOR) 1111
23 T7W E02 202 ROOM TEMPERATURE THERMISTOR 1111
78
FAN AND HEATER PARTS 13 15
PCH-P4GAH, PCH-P4GAH1 12
PCA-P4GA, PCA-P4GA1
22 10
9
5
1 23 11
2 4·18
14
7 3 6
19 20
8
21
16
17
Q'ty / set Wiring Recom- Price
No. Parts No. Parts Name Specifications PCH-P4 PCA-P4 Remarks Diagram mended
(Drawing No.)
Symbol Q'ty Unit Amount
GAH GAH1 GA GA1
1 T7W 39J 762 FAN MOTOR D10B4P90MS 1 1 1 1 MF
2 R01 700 116 SHAFT JOINT 1111
3 R01 29J 100 SHAFT 1111
4 R01 705 103 SLEEVE BEARING 1111
5 R01 35J 130 MOTOR LEG 1111
6 R01 35J 114 SIROCCO FAN 2222
7 R01 41J 114 SIROCCO FAN 1111
8 T7W B07 110 CASING 3333
9 R01 17J 202 PIPE TEMPERATURE THERMISTOR 1111 TH2
TH5
10 T7W E08 202 CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR 1111 H1
26H
11 T7W 39J 300 HEATER ELEMENT 80V 900W 33 FS1,2
12 R01 46K 700 THERMAL SWITCH OFF:50: ON:35: 1 1
13 T7W 589 706 THERMAL FUSE 117: 16A 250V 1 1
R01 20J 303 INSULATOR 11
14 33
R01 36J 303 INSULATOR
15 T7W E16 480 HEAT EXCHANGER 1111
16 R01 A16 529 DRAIN PAN ASSY 1111
17 R01 17J 524 DRAIN PLUG 1111
18 R01 35J 145 BEARING SUPPORT 1111
19 T7W 22J 675 FAN GUARD 1111
20 T7W 23J 675 FAN GUARD 2222
21 T7W 24J 675 FAN GUARD 1111
22 R01 43E 126 PIECE (MOTOR) 1111
23 T7W E02 202 ROOM TEMPERATURE THERMISTOR 1111 TH1
79
FAN AND HEATER PARTS 13 14
17
PCH-P5GAH, PCA-P5GA
PCH-P5GAH1, PCA-P5GA1 25
11
10
6 5
24
26 1
2
3 12
15
21 4·20
9
7
23
18
22 8 19
Part numbers that are circled are not shown in the figure.
Q'ty / set Price
No. Parts No. Parts Name Specifications PCH-P5 PCA-P5 Remarks Wiring Recom-
(Drawing No.) Diagram mended
1 T7W 43J 762 FAN MOTOR GAH GAH1 GA GA1 Symbol Q'ty Unit Amount
D10B4P150MS 1 1 1 1 MF
2 R01 700 116 SHAFT JOINT 1111 TH2
TH5
3 R01 29J 100 SHAFT 1111 H1
26H
4 R01 705 103 SLEEVE BEARING 1111 FS1,2
5 R01 41J 130 MOTOR LEG 1111 TH1
6 R01 41J 114 SIROCCO FAN 1111
7 R01 39J 114 SIROCCO FAN 1111
8 R01 35J 114 SIROCCO FAN 2222
9 T7W B07 110 CASING 4444
10 R01 17J 202 PIPE TEMPERATURE THERMISTOR 1111
11 T7W E08 202 CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR 1111
12 T7W 43J 300 HEATER ELEMENT 80V 1000W 33
13 R01 46K 700 THERMAL SWITCH OFF:50: ON:35: 1 1
14 T7W 23J 706 THERMAL FUSE 110: 16A 250V 1 1
15 R01 20J 303 INSULATOR 11
16 R01 36J 303 INSULATOR 66
17 T7W E17 480 HEAT EXCHANGER 1111
18 R01 A17 529 DRAIN PAN ASSY 1111
19 R01 17J 524 DRAIN PLUG 1111
20 R01 35J 145 BEARING SUPPORT 1111
21 T7W 25J 675 FAN GUARD 1111
22 T7W 23J 675 FAN GUARD 2222
23 T7W 24J 675 FAN GUARD 1111
24 T7W 26J 675 FAN GUARD 1111
25 R01 43E 126 PIECE (MOTOR) 1111
26 T7W E02 202 ROOM TEMPERATURE THERMISTOR 1111
80
PCH-P6GAH, PCA-P6GA 13 14
17
PCH-P6GAH1, PCA-P6GA1
25
11
10
6 5
24
26 1
2
3 12
15
21 4·20
9
7
23
18
22 8 19
Part numbers that are circled are not shown in the figure.
Q'ty / set Wiring Recom- Price
No. Parts No. Parts Name Specifications PCH-P6 PCA-P6 Remarks Diagram mended Unit Amount
(Drawing No.) Symbol Q'ty
1 T7W 43J 762 FAN MOTOR GAH GAH1 GA GA1 MF
D10B4P150MS 1 1 1 1
2 R01 700 116 SHAFT JOINT 1111
3 R01 29J 100 SHAFT 1111
4 R01 705 103 SLEEVE BEARING 1111
5 R01 41J 130 MOTOR LEG 1111
6 R01 41J 114 SIROCCO FAN 1111
7 R01 39J 114 SIROCCO FAN 1111
8 R01 35J 114 SIROCCO FAN 2222
9 T7W B07 110 CASING 4444
10 R01 17J 202 PIPE TEMPERATURE THERMISTOR 1111 TH2
TH5
11 T7W E08 202 CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR 1111 H1
26H
12 T7W 43J 300 HEATER ELEMENT 80V 1000W 33 FS1,2
13 R01 46K 700 THERMAL SWITCH OFF:50: ON:35: 1 1
14 T7W 23J 706 THERMAL FUSE 110: 16A 250V 1 1
15 R01 20J 303 INSULATOR 11
16 R01 36J 303 INSULATOR 66
17 T7W E18 480 HEAT EXCHANGER 1111
18 R01 A17 529 DRAIN PAN ASSY 1111
19 R01 17J 524 DRAIN PLUG 1111
20 R01 35J 145 BEARING SUPPORT 1111
21 T7W 25J 675 FAN GUARD 1111
22 T7W 23J 675 FAN GUARD 2222
23 T7W 24J 675 FAN GUARD 1111
24 T7W 26J 675 FAN GUARD 1111
25 R01 43E 126 PIECE (MOTOR) 1111
26 T7W E02 202 ROOM TEMPERATURE THERMISTOR 1111 TH1
81
ELECTRICAL PARTS
PCH-P2GAH, PCH-P2GAH1
PCH-P2.5GAH, PCH-P2.5GAH1
PCH-P3GAH, PCH-P3GAH1
12 3
5
13
2 10
1
7
6
8
CENTRALLY CONTROLLED 1Hr.
˚C
ON OFF
CHECK CLOCK
STAND BY ˚C NOT AVAILABLE FILTER
DEFROST ERROR CODE CHECK MODE
TEST RUN
FUNCTION
TEMP. ON/OFF
4
9
14 11
Q'ty / set Remarks Wiring Recom- Price
PCH-P2 PCH-P2.5/3 Unit Amount
No. Parts No. Parts Name Specifications GAH GAH1 GAH GAH1 (Drawing No.) Diagram mended
Symbol Q'ty
1 T7W E04 310 CONTROLLER BOARD 1111 I.B
2 R01 E00 239 FUSE 250V 4A 1111 F1
3 T7W E01 313 POWER BOARD 1111
4 T7W E00 071 UNDER CASE (REMOCON) 1 1
5 R01 30L 255 RUN CAPACITOR 3MF. 440V 1 1 C
T7W 39J 255 RUN CAPACITOR 4MF. 440V 11 C
6 T7W 521 716 TERMINAL BLOCK 3P (L,N, ) 1 1 1 1 TB2
7 T7W E01 716 TERMINAL BLOCK 3P (S1,S2,S3) 1 1 1 1 TB4
8 T7W 512 716 TERMINAL BLOCK 2P (1,2) 1111 TB5
9 T7W E02 049 REMOTE CONTROLLER COVER 1 1
10 T7W E00 713 REMOTE CONTROLLER 1 1 R.B
T7W E06 713 REMOTE CONTROLLER 1 1 R.B
11 T7W A00 305 REMOTE CONTROLLER CORD 10m 1111
12 R01 71G 215 RELAY JC-1A DC12V 1 1 1 1
13 — CONT BOX 1 1 1 1 (BG00N015G26)
14 — CONT COVER 11 (BG02A804G20)
— CONT COVER 1 1 (BG02A804G21)
82
PCH-P4GAH, PCH-P4GAH1
PCH-P5GAH, PCH-P5GAH1
PCH-P6GAH, PCH-P6GAH1
12 3
5
13
2 1 10
14
7
6
8
CENTRALLY CONTROLLED 1Hr.
˚C
ON OFF
CHECK CLOCK
STAND BY ˚C NOT AVAILABLE FILTER
DEFROST ERROR CODE CHECK MODE
TEST RUN
FUNCTION
TEMP. ON/OFF
4
9
11
Q'ty / set Remarks Wiring Recom- Price
PCH-P4 PCH-P5/6 Unit Amount
No. Parts No. Parts Name Specifications GAH GAH1 GAH GAH1 (Drawing No.) Diagram mended
Symbol Q'ty
1 T7W E04 310 CONTROLLER BOARD 1111 I.B
2 R01 E00 239 FUSE 250V 4A 1111 F1
3 T7W E01 313 POWER BOARD 1111
4 T7W E00 071 UNDER CASE (REMOCON) 1 1
5 T7W 39J 255 RUN CAPACITOR 4MF. 440V 1 1 C
T7W 43J 255 RUN CAPACITOR 6MF. 440V 11 C
6 T7W 521 716 TERMINAL BLOCK 3P (L,N, ) 1 1 1 1 TB2
7 T7W E01 716 TERMINAL BLOCK 3P (S1,S2,S3) 1 1 1 1 TB4
8 T7W 512 716 TERMINAL BLOCK 2P (1,2) 1111 TB5
9 T7W E02 049 REMOTE CONTROLLER COVER 1 1
10 T7W E00 713 REMOTE CONTROLLER 1 1 R.B
T7W E06 713 REMOTE CONTROLLER 1 1 R.B
11 T7W A00 305 REMOTE CONTROLLER CORD 10m 1111
12 R01 71G 215 RELAY JC-1A DC12V 1 1 1 1
13 — CONT BOX 1 1 1 1 (BG00N015G26)
14 — CONT COVER 1 1 (BG02A804G21)
— CONT COVER 11 (BG02A804G22)
83
STRUCTURAL PART
PCH-P2GAH, PCH-P2GAH1
PCA-P2GA, PCH-P2GA1
2 19 13 15 4 12 16 28
10
24
11
5 23
17 14
7 18
8 1
9 6 27 3 20 26 25
84
Part numbers that are circled are not shown in the figure.
Q'ty / set Wiring Recom- Price
Specifications PCH-P2 PCA-P2
No. Parts No. Parts Name Remarks Diagram mended Unit Amount
GAH GAH1 GA GA1 (Drawing No.) Symbol Q'ty
1111
1 R01 17J 661 RIGHT SIDE PANEL
2 R01 17J 662 LEFT SIDE PANEL 1111
3 R01 17J 669 UNDER PANEL 1111
4 R01 17J 676 REAR PANEL 1111
5 R01 A14 500 L.L. FILTER 1111
6 R01 A15 500 L.L. FILTER 1111
7 R01 17J 691 GRILLE ASSY 1111
8 R01 18J 691 GRILLE ASSY 1111
9 R01 17J 054 GRILLE CATCH 4444
10 R01 17J 651 FRONT PANEL 1111
11 R01 37J 085 GUIDE VANE ASSY-6R. 1111
12 R01 37J 086 GUIDE VANE ASSY-6L. 1111
13 R01 29J 223 VANE MOTOR 1111 MV
14 R01 17J 067 RIGHT SIDE BOX 1111
15 R01 17J 068 LEFT SIDE BOX 1111
16 R01 17J 002 AUTO VANE 1111
17 R01 17J 061 GRILLE HINGE 4444
18 R01 17J 808 RIGHT LEG 1111
19 R01 17J 809 LEFT LEG 1111
20 T7W E01 070 WIRELESS BOARD CASE 1111
21 R01 17J 523 JOINT SOCKET 1111
22 T7W E00 072 DRAIN HOSE COVER 1111
23 R01 18J 665 SIDE PLATE-R. 1111
24 R01 57N 666 SIDE PLATE-L. 1111
25 R01 17J 668 SERVICE PANEL 1111
26 — BEAM (GA) 1 1 1 1 (BG17H464H08)
27 — REAR SUPPORT 1 1 1 1 (BG02H454K01)
1 1 1 1 (BG02R321G07)
28 — VANE SUPPORT
85
STRUCTURAL PART
PCH-P2.5GAH, PCH-P2.5GAH1, PCA-P2.5GA, PCA-P2.5GA1
PCH-P3GAH, PCH-P3GAH1, PCA-P3GA, PCA-P3GA1
16 11 13 14 12 27
2
18
15
23
5
4 10
24
8 17
1
9 6 3 7 19 26 25 22
86
Part numbers that are circled are not shown in the figure.
No. Parts No. Parts Name Specifications Q'ty / set Remarks Wiring Recom- Price
Diagram mended Unit Amount
PCH-P2.5/3 PCA-P2.5/3 (Drawing No.) Symbol Q'ty
GAH GAH1 GA GA1
1 R01 17J 661 RIGHT SIDE PANEL
1111
2 R01 17J 662 LEFT SIDE PANEL 1111
3 R01 A14 500 L.L. FILTER 2222
4 R01 29J 676 REAR PANEL 1111
5 R01 29J 651 FRONT PANEL 1111
6 R01 17J 691 GRILLE ASSY 2222
7 R01 29J 669 UNDER PANEL 1111
8 R01 17J 061 GRILLE HINGE 4444
9 R01 17J 054 GRILLE CATCH 4444
10 R01 17J 067 RIGHT SIDE BOX 1111
11 R01 17J 068 LEFT SIDE BOX 1111
12 R01 37J 085 GUIDE VANE ASSY-6R. 1111
13 R01 37J 086 GUIDE VANE ASSY-6L. 1111
14 R01 37J 087 GUIDE VANE ASSY-6C. 1111
15 R01 29J 002 AUTO VANE 1111
16 R01 29J 223 VANE MOTOR 1111 MV
17 R01 17J 808 RIGHT LEG 1111
18 R01 17J 809 LEFT LEG 1111
19 T7W E01 070 WIRELESS BOARD CASE 1111
20 R01 17J 523 JOINT SOCKET 1111
21 T7W E00 072 DRAIN HOSECOVER 1111
22 R01 18J 665 SIDE PLATE-R. 1111
23 R01 57N 666 SIDE PLATE-L. 1111
24 R01 17J 668 SERVICE PANEL 1111
25 — BEAM (GA) 2 2 2 2 (BG17H464H08)
26 — REAR SUPPORT 1 1 1 1 (BG02H454K01)
27 — VANE SUPPORT 2 2 2 2 (BG02R321G07)
87
PCH-P4GAH, PCH-P4GAH1,
PCA-P4GA, PCA-P4GA1
16 11 13 14 12 27
2
18
15
23
5
4 10
24
8 17
1
9 6 3 7 19 26 25 22
88
Part numbers that are circled are not shown in the figure.
Q'ty / set Remarks Wiring Recom- Price
No. Parts No. Parts Name Specifications PCH-P4 PCA-P4 (Drawing No.) Diagram mended Unit Amount
Symbol Q'ty
GAH GAH1 GA GA1
1 R01 35J 661 RIGHT SIDE PANEL 1111
2 R01 35J 662 LEFT SIDE PANEL 1111
3 R01 A14 500 L.L. FILTER 2222
4 R01 35J 676 REAR PANEL 1111
5 R01 36J 651 FRONT PANEL 1111
6 R01 17J 691 GRILLE ASSY 2222
7 R01 29J 669 UNDER PANEL 1111
8 R01 17J 061 GRILLE HINGE 4444
9 R01 17J 054 GRILLE CATCH 4444
10 R01 35J 067 RIGHT SIDE BOX 1111
11 R01 35J 068 LEFT SIDE BOX 1111
12 R01 37J 085 GUIDE VANE ASSY-6R. 1111
13 R01 37J 086 GUIDE VANE ASSY-6L. 1111
14 R01 37J 087 GUIDE VANE ASSY-6C. 1111
15 R01 35J 002 AUTO VANE 1111
16 R01 35J 223 VANE MOTOR 1111 MV
17 R01 17J 808 RIGHT LEG 1111
18 R01 17J 809 LEFT LEG 1111
19 T7W E01 070 WIRELESS BOARD CASE 1111
20 R01 17J 523 JOINT SOCKET 1111
21 T7W E00 072 DRAIN HOSECOVER 1111
22 T7W B07 665 SIDE PLATE-R. 1111
23 R01 35J 666 SIDE PLATE-L. 1111
24 R01 18J 668 SERVICE PANEL 1111
25 — BEAM (GA) 2 2 2 2 (BG17H464H08)
26 — REAR SUPPORT 1 1 1 1 (BG02H454K01)
27 — VANE SUPPORT 2 2 2 2 (BG02R805G05)
89
STRUCTURAL PART
PCH-P5GAH, PCA-P5GA
PCH-P5GAH1, PCA-P5GA1
PCH-P6GAH, PCA-P6GA
PCH-P6GAH1, PCA-P6GA1
20 14 16 12 29 13 11
2
25 17
10
4
24
6
18 15
8 26
19
1
9 7 5 3 21 28 27
90
Part numbers that are circled are not shown in the figure.
Q'ty / set Wiring Recom- Price
Specifications PCH-P5/6 PCA-P5/6
No. Parts No. Parts Name Remarks Diagram mended
GAH GAH1 GA GA1 (Drawing No.)
Symbol Q'ty Unit Amount
1 R01 35J 661 RIGHT SIDE PANEL 1111
2 R01 35J 662 LEFT SIDE PANEL 1111
3 R01 41J 669 UNDER PANEL 1111
4 R01 41J 676 REAR PANEL 1111
5 R01 A14 500 L.L. FILTER 2222
6 R01 A15 500 L.L. FILTER 1111
7 R01 17J 691 GRILLE ASSY 2222
8 R01 18J 691 GRILLE ASSY 1111
9 R01 17J 054 GRILLE CATCH 6666
10 R01 41J 651 FRONT PANEL 1111
11 R01 41J 085 GUIDE VANE ASSY-5R. 1111
12 R01 42J 086 GUIDE VANE ASSY-5L. 1111
13 R01 43J 087 GUIDE VANE ASSY-5C. 2222
14 R01 35J 223 VANE MOTOR 1111 MV
15 R01 35J 067 RIGHT SIDE BOX 1111
16 R01 35J 068 LEFT SIDE BOX 1111
17 R01 41J 002 AUTO VANE 1111
18 R01 17J 061 GRILLE HINGE 6666
19 R01 17J 808 RIGHT LEG 1111
20 R01 17J 809 LEFT LEG 1111
21 T7W E01 070 WIRELESS BOARD CASE 1111
22 R01 17J 523 JOINT SOCKET 1111
23 T7W E00 072 DRAIN HOSE COVER 1111
24 T7W B07 665 SIDE PLATE-R. 1111
25 R01 35J 666 SIDE PLATE-L. 1111
26 R01 18J 668 SERVICE PANEL 1111
27 — BEAM (GA) 3 3 3 3 (BG17H464H08)
28 — REAR SUPPORT 1 1 1 1 (BG02H454K01)
29 — VANE SUPPORT 3 3 3 3 (BG02R805G05)
91
ELECTRICAL PARTS
PCA-P2GA, PCA-P2GA1
PCA-P2.5GA, PCA-P2.5GA1
PCA-P3GA, PCA-P3GA1
3
11
5
2
1 9
6
7 CENTRALLY CONTROLLED 1Hr.
4 ˚C
ON OFF
8
CHECK CLOCK
STAND BY ˚C NOT AVAILABLE FILTER
DEFROST ERROR CODE CHECK MODE
TEST RUN
FUNCTION
TEMP. ON/OFF
12 10
Q'ty / set Wiring Recom- Price
PCA-P2 PCA-P2.5/3
No. Parts No. Parts Name Specifications GA GA1 GA GA1 Remarks Diagram mended
Symbol Q'ty
(Drawing No.) Unit Amount
1 T7W E04 310 CONTROLLER BOARD 1111 I.B
2 R01 E00 239 FUSE 250V 4A 1111 F1
3 T7W E01 313 POWER BOARD 1111
4 T7W E00 071 UNDER CASE (REMOCON) 1 1
5 R01 30L 255 RUN CAPACITOR 3MF. 440V 1 1 C
T7W 39J 255 RUN CAPACITOR 4MF. 440V 11 C
6 T7W E13 716 TERMINAL BLOCK 3P (S1,S2,S3) 1 1 1 1 TB4
7 T7W 512 716 TERMINAL BLOCK 2P (1,2) 1111 TB5
8 T7W E02 049 REMOTE CONTROLLER COVER 1 1
9 T7W E00 713 REMOTE CONTROLLER 1 1 R.B
T7W E06 713 REMOTE CONTROLLER 1 1 R.B
10 T7W A00 305 REMOTE CONTROLLER CORD 10m 1111
11 — CONT BOX 1 1 1 1 (BG00N015G25)
12 — CONT COVER 11 (BG02A804G20)
— CONT COVER 1 1 (BG02A804G21)
92
ELECTRICAL PARTS
PCA-P4GA, PCA-P4GA1
PCA-P5GA, PCA-P5GA1
PCA-P6GA, PCA-P6GA1
3
11
5
2
1 9
6
7 CENTRALLY CONTROLLED 1Hr.
4 ˚C
ON OFF
8
CHECK CLOCK
STAND BY ˚C NOT AVAILABLE FILTER
DEFROST ERROR CODE CHECK MODE
TEST RUN
FUNCTION
TEMP. ON/OFF
12 10
Q'ty / set Wiring Recom- Price
PCA-P4 PCA-P5/6
No. Parts No. Parts Name Specifications GA GA1 GA GA1 Remarks Diagram mended
Symbol Q'ty
(Drawing No.) Unit Amount
1 T7W E04 310 CONTROLLER BOARD 1 1 11 I.B
2 R01 E00 239 FUSE 250V 4A 1 1 11 F1
3 T7W E01 313 POWER BOARD 1 1 11
4 T7W E00 071 UNDER CASE (REMOCON) 1 1
5 T7W 39J 255 RUN CAPACITOR 4MF. 440V 1 1 C
T7W 43J 255 RUN CAPACITOR 6MF. 440V 11 C
6 T7W E13 716 TERMINAL BLOCK 3P (S1,S2,S3) 1 1 1 1 TB4
7 T7W 512 716 TERMINAL BLOCK 2P (1,2) 1 1 11 TB5
8 T7W E02 049 REMOTE CONTROLLER COVER 1 1
9 T7W E00 713 REMOTE CONTROLLER 1 1 R.B
T7W E06 713 REMOTE CONTROLLER 1 1 R.B
10 T7W A00 305 REMOTE CONTROLLER CORD 10m 1 1 11
11 — CONT BOX 1 1 1 1 (BG00N015G25)
12 — CONT COVER 1 1 (BG02A804G21)
— CONT COVER 11 (BG02A804G22)
93
13 OPTIONAL PARTS
1. TIMER PAC-SC32PTA (with set back function)
Program timer
Part No.
Model Name Program timer
PAC-SC32PTA
1-1 Program timer specifications 5-4/32!4-23/32!23/32 (130!120!18mm)
Part name Wall mount
Parts No. Quartz
Exterior dimensions (inch) +_ 50 second / month at 25:
Installation Liquid crystal display
Type of clock Liquid crystal display
Clock accuracy Liquid crystal display
Display-Time 24 hours
-Week 30 minutes
-Timer setting unit 48 / day
Program cycle 5V DC +_5% (Supplied by Remote Controller)
Timer setting unit
No. of set points
Power rating
1-2 Feature of program timer 28˚C 23:00 8:00
(1) Daily timer function
26˚C Setback Normal
Daily timer can be set in 30 minutes units for up to 24 hours. operation operation
Each unit can be set for unit ON, unit OFF, or setback operation. 8:00
(2) Setback operation Normal
Set back operation is useful for reducing running costs operation
e.g. At a hotel with a 24-hour system
8:00~23:00 Cooling operation with set temperature at 26°C
23:00~8:00 Setback operation with 2 degrees of setback
As shown in the chart on the right, the set temperature rises 2 degrees
automatically during the setback operation. When the setback operation
ends, normal operation will begin.
(3) Weekly timer function
Daily timer function can apply to each day of the week.
94
1-3. How to connect program timer
(1) Install the program timer next to the remote controller the same way as the remote controller is installed.
(2) Connect the program timer and the remote controller with a 5-wire cable as shown in the figure below
Connect to indoor unit NOTE:While the program timer is connected to the remote controller, the
with 2-wire cable. 24hour ON/OFF timer on the remote controller will not operate.
SET BACK
SET SMTWT F S
MONITOR
FILTER 0 3 6 12 15
CHECK MODE
TEST RUN 12 15 18 21 24
SET/MONITOR TODAY WEEKLY SET BACK DAILY
SETTING ON SETTING
ON SET BACK
CLOCK OFF DAILY TIMER OFF
PROERAN TIMER
PAC-SC32PTA
4
Connect to CN1 Use 5-wire cable Connect to CN1 SET BACK DISPLAY DAILY TIMER SETTING DISPLAY
1-4. Names and functions Indicates the setting set 24 hours is divided into 48 blocks and each
<PAC-SC32PTA> back range. block express 30 minutes.
The block display consists of 3 pattern.
WEEKLY TIMER SETTING DISPLAY CURRENT TIME DISPLAY
Set back can be done in the range of 1,2,4,6
Used for selection of if or not the day opera- During MONITOR status,current and 8°C.
tion pattern set by PATTERN SETTING is to time is display.
be applied in weekly day unit, During Daily timer setting, a SET BACK SETTING SW
setting. time desire for timer setting is
displayed. Used for set back setting.
SET BACK ON/SET BACK/OFF SW
SET/MONITOR DISPLAY SET SMTWT F S Used to specify the time setting pattern.
MONITOR
During SET is display, clock adjustment, 0 3 6 12 15 DAILY TIMER SW
change of weekly day, daily and weekly timer
setting can be performed. 12 15 18 21 24 Used for timer setting in 30 minutes unit.
During MONITOR is display, all switches
except SET/MONITOR SW are invalidated. SET/MONITOR TODAY WEEKLY SET BACK DAILY
This is normal status. SETTING ON SETTING
WEEK DAY SETTING SW ON SET BACK
Used for week day setting. CLOCK OFF DAILY TIMER OFF
PROERAN TIMER
PAC-SC32PTA
MODE SELECTOR SW CLOCK ADJUSTMENT SW WEEKLY TIMER SW
Using this switch select “MONITOR” or “SET” Used for adjustment of the current time. Used for setting timer in day of week unit.
Mode.
Push SW to advance the time. Each time the button is Pushing SW moves the week day light
“MONITOR” :Indicates the current timer set- pushed the time advance by 1 minute, pushing continuously display in order of
ting. All switch expect MODE advances by 1 minute at 0.5 second interval, and when the S¡M¡T¡W…
SELECTOR SW are invalidated lower digit of minute becomes 0 indication advances in 10 min- enabling to set the week day.
then.This is the normal status. utes unit.
“SET”: Set to “SET” mode for clock adjust- SW is used for reversing the time. Each time the button is
ment, charge of week day, daily and pushed the time reverses by 1 minute, pushing continuously
weekly timer setting. reverses the time by 1 minute at 0.5 second interval, and when
the lower digit of minute becomes 0 indication reverses in 10
minutes unit.
95
2. Drain Lift Up Mechanism PAC-SE85DMA-E PAC-SE86DMA-E
Part No.
PCH-P2/2.5/3GAH PCH-P4/5/6GAH
Applied Service Ref. PCH-P2/2.5/3GAH1 PCH-P4/5/6GAH1
PCA-P2/2.5/3GA PCA-P4/5/6GA
PCA-P2/2.5/3GA1 PCA-P4/5/6GA1
3. High-Efficiency Filter PAC-SE80KF-E PAC-SE81KF-E PAC-SE82KF-E
Part No.
PCH-P2GAH PCH-P2.5/3/4GAH PCH-P5/6GAH
Applied Service Ref. PCH-P2GAH1 PCH-P2.5/3/4GAH1 PCH-P5/6GAH1
PCA-P2GA PCA-P2.5/3/4GA PCA-P5/6GA
PCA-P2GA1 PCA-P2.5/3/4GA1 PCA-P5/6GA1
4. Wireless Remote Controller + Wireless Adapter
Part No. PAC-SW93A-E PAR-SL99A-E
Applied Service Ref. PCH-P2/2.5/3/4/5/6GAH PCH-P2/2.5/3/4/5/6GAH1
PCA-P2/2.5/3/4/5/6GA PCA-P2/2.5/3/4/5/6GA1
5. Remote Sensor PAC-SE41TS-E
Part No.
PCH-P2/2.5/3/4/5/6GAH, PCH-P2/2.5/3/4/5/6GAH1
Applied Service Ref. PCA-P2/2.5/3/4/5/6GA, PCA-P2/2.5/3/4/5/6GA1
6. Remote Operation Adapter PAC-SF40RM-E
Part No.
PCH-P2/2.5/3/4/5/6GAH, PCH-P2/2.5/3/4/5/6GAH1
Applied Service Ref. PCA-P2/2.5/3/4/5/6GA, PCA-P2/2.5/3/4/5/6GA1
7. Remote ON/OFF Adapter PAC-SF55RA-E
Part No.
PCH-P2/2.5/3/4/5/6GAH, PCH-P2/2.5/3/4/5/6GAH1
Applied Service Ref. PCA-P2/2.5/3/4/5/6GA, PCA-P2/2.5/3/4/5/6GA1
96
TM
HEAD OFFICE : MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI,CHIYODA-KU TOKYO 100-8310, JAPAN
cCopyright 1999 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD. New publication, effective Oct. 2001.
Distribted in Oct. 2001. No. CO182 REVISED EDITION-B 350 Specifications subject to change without notice.
Reprinted in Jul. 2001. No. OC182 REVISED EDITION-A 50
Reprinted in Jun. 2000. No. OC182 REVISED EDITION-A 50
Issued in Dec. 1999. No. OC182 REVISED EDITION-A 42
Issued in Mar. 1999. No. OC182 36
Made in Japan